CVE-2017-16740 is a stack-based buffer overflow in Rockwell Automation Allen-Bradley MicroLogix 1400 PLCs, Series B and C, running firmware 21.002 or earlier. A remote attacker with no credentials can trigger it over the network, and it may allow code execution. NVD scores it 10.0, CISA 8.6. The fix is firmware FRN 21.003.
Vulnerability summary
CVSS base score
10
Critical severity
EPSS score (FIRST)
7.2%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2017-16740 · Source: NVD

Affected components
| Component | CPE | Version range |
|---|---|---|
| Rockwell Automation Allen-Bradley MicroLogix 1400 controllers (1766-L32AWA, -L32AWAA, -L32BWA, -L32BWAA, -L32BXB, -L32BXBA) | cpe:2.3:o:rockwellautomation:1766-l32bxba_firmware:*:*:*:*:*:*:*:* | Series B and C, firmware 21.002 and earlier (CISA ICSA-18-009-01, NVD); fixed in FRN 21.003 |
What does this mean for affected devices?
The CVE record from CISA says: "A Buffer Overflow issue was discovered in Rockwell Automation Allen-Bradley MicroLogix 1400 Controllers, Series B and C Versions 21.002 and earlier. The stack-based buffer overflow vulnerability has been identified, which may allow remote code execution." NVD maps it to CWE-119 and CISA to CWE-120, the classic unchecked buffer copy (NVD, CVE record).
Why does NVD score it 10.0 and CISA 8.6?
Both agree on the attack path: network, low complexity, no privileges, no user interaction, changed scope. NVD's Primary score is 10.0 with CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H, which follows the "remote code execution" wording and rates confidentiality, integrity and availability as fully lost; its older CVSS v2 score is 7.5. CISA, which assigned the CVE, scores 8.6 with CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:C/C:N/I:N/A:H, counting only the loss of availability. For a PLC that runs a process, either reading means a controller that can be stopped from the network.
Which MicroLogix 1400 controllers are affected and what fixes it?
CISA's ICSA-18-009-01, released on 2018-01-09, lists the 1766-L32AWA, 1766-L32AWAA, 1766-L32BWA, 1766-L32BWAA, 1766-L32BXB and 1766-L32BXBA catalog numbers, Series B and C, firmware 21.002 and earlier. Rockwell Automation asks users to upgrade to firmware FRN 21.003, and says Modbus TCP can be disabled where the application does not need it. Its own security bulletin sits behind a customer login. CISA adds its usual network advice: keep the controller off the internet, behind a firewall and apart from the business network, with remote access over an up-to-date VPN. The Modbus protocol security guide explains why an unauthenticated Modbus TCP port is worth closing, and the memory corruption fix guide covers the code-level class. More on this controller family in the Rockwell Logix controller guide.
Other MicroLogix pages: CVE-2021-22659, a later Modbus overflow in the same MicroLogix 1400, and CVE-2021-33012 for the MicroLogix 1100.
Is CVE-2017-16740 exploited?
CVE-2017-16740 is not in the CISA KEV catalog as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries), and CISA's advisory noted no known public exploit. FIRST EPSS gives it 0.07204, the 95.08th percentile, in the 2026-11-26 dataset (CISA KEV, FIRST EPSS).


Evidence
- NVD (read 2026-11-27): status Modified; published 2018-01-09; NVD Primary CVSS v3.0 10.0 CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H; NVD Primary CVSS v2 7.5 AV:N/AC:L/Au:N/C:P/I:P/A:P; CWE-119 (NVD Primary), CWE-120 (ICS-CERT); CPEs 1766-L32AWA/AWAA/BWA/BWAA/BXB/BXBA firmware up to and including 21.002. — NVD
- CISA ICSA-18-009-01 CSAF (released 2018-01-09, read 2026-11-27): MicroLogix 1400 Series B and C 21.002 and earlier, six catalog numbers; CWE-120; CISA CVSS v3 8.6 AV:N/AC:L/PR:N/UI:N/S:C/C:N/I:N/A:H; upgrade to FRN 21.003; Modbus TCP can be disabled if not needed; vendor bulletin needs valid credentials; worldwide, HQ Wisconsin; no known public exploits. — CISA ICSA-18-009-01
- CISA advisory page (read 2026-11-27 via a page fetch): title Rockwell Automation Allen-Bradley MicroLogix 1400 Controllers, released 2018-01-09; same catalog numbers, 8.6 score, FRN 21.003 and Modbus TCP workaround. — CISA
- CVE record (read 2026-11-27): state PUBLISHED, CNA ICS-CERT, published 2018-01-09; affected Rockwell Automation Allen-Bradley MicroLogix 1400 Controllers; no CNA CVSS in the record. — CVE.org
- Not in the CISA KEV catalog, catalog version 2026.11.25, 1,805 entries, checked 2026-11-27. — CISA KEV
- EPSS 0.07204, percentile 0.95077, dataset 2026-11-26, read 2026-11-27. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
Which firmware fixes CVE-2017-16740 on the MicroLogix 1400?
Firmware FRN 21.003. CISA ICSA-18-009-01 lists Series B and C controllers on 21.002 and earlier as affected, catalog numbers 1766-L32AWA, -L32AWAA, -L32BWA, -L32BWAA, -L32BXB and -L32BXBA.
What can be done if the firmware cannot be updated right away?
Rockwell Automation says Modbus TCP can be disabled if the application does not need it. CISA also advises keeping the controller off the internet, behind a firewall and separate from the business network, with remote access only over an up-to-date VPN.
Why do NVD and CISA give different scores?
Both rate the attack as network-based with no privileges or user interaction and a changed scope. NVD rates confidentiality, integrity and availability impact high (10.0); CISA counts only the availability impact (8.6).
Is CVE-2017-16740 in the CISA KEV catalog?
No, not as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS rates it 0.07204 (95.08th percentile) in the 2026-11-26 dataset.