Security Advisory

CVE-2020-6990: MicroLogix and RSLogix 500 Hard-Coded Key

Last updated:
  • CVE-2020-6990

CVE-2020-6990 is a hard-coded cryptographic key in Rockwell Automation RSLogix 500 that protects the account password of MicroLogix 1400 and 1100 controllers. NVD and CISA score it 9.8. For MicroLogix 1400 Series B, firmware FRN 21.002 with enhanced password security is the fix; Series A and the 1100 have no mitigation.

Vulnerability summary

CVSS base score

9.8

Critical severity

EPSS score (FIRST)

5.9%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2020-6990 · Source: NVD

CVSS v3.1 severity rating scale: None 0.0, Low 0.1 to 3.9, Medium 4.0 to 6.9, High 7.0 to 8.9, Critical 9.0 to 10.0
How a CVSS v3.1 base score maps to a severity rating. Source: FIRST CVSS v3.1 specification, section 5.

Affected components

ComponentCPEVersion range
Rockwell Automation MicroLogix 1400 Series Bcpe:2.3:o:rockwellautomation:micrologix_1400_b_firmware:*:*:*:*:*:*:*:*21.001 and earlier (CVE record, NVD, CISA ICSA-20-070-06); apply FRN 21.002 or later and use the enhanced password security feature
Rockwell Automation MicroLogix 1400 Series Acpe:2.3:o:rockwellautomation:micrologix_1400_a_firmware:*:*:*:*:*:*:*:*All versions (CVE record, NVD, CISA); Rockwell reports no mitigation
Rockwell Automation MicroLogix 1100cpe:2.3:o:rockwellautomation:micrologix_1100_firmware:*:*:*:*:*:*:*:*All versions (CVE record, NVD, CISA); Rockwell reports no mitigation
Rockwell Automation RSLogix 500cpe:2.3:a:rockwellautomation:rslogix_500:*:*:*:*:*:*:*:*12.001 and earlier (CVE record, NVD, CISA); use v11 or later together with FRN 21.001 or later on MicroLogix 1400 Series B (CISA)

What does this mean for affected devices?

The CVE record from CISA says that in Rockwell Automation MicroLogix 1400 controllers Series B v21.001 and prior, Series A (all versions), the MicroLogix 1100 controller (all versions) and RSLogix 500 software v12.001 and prior, "the cryptographic key utilized to help protect the account password is hard coded into the RSLogix 500 binary file", and that an attacker could identify the key and use it for further cryptographic attacks "that could ultimately lead to a remote attacker gaining unauthorized access to the controller." NVD's Primary score is 9.8 (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H, CVSS 2.0 10.0) with CWE-798. CISA gives the same 9.8 vector in CVSS 3.0 and maps it to CWE-321, use of a hard-coded cryptographic key (NVD, CVE record).

Which MicroLogix controllers are affected?

CISA advisory ICSA-20-070-06, released on 2020-03-10, lists RSLogix 500 12.001 and earlier, MicroLogix 1400 Series B 21.001 and earlier, MicroLogix 1400 Series A and the MicroLogix 1100, deployed worldwide across multiple sectors. It covers four flaws found by researchers from ScadaX Security, Positive Technologies and 307 Lab: this key, a risky cryptographic algorithm for the password (CVE-2020-6984, NVD 7.5), client-side authentication (CVE-2020-6988, NVD 7.5) and cleartext storage of sensitive project data (CVE-2020-6980, NVD 3.3). CISA's risk summary is that an attacker could gain access to sensitive project file information, including passwords.

How do you fix CVE-2020-6990?

Rockwell's guidance, as CISA records it, depends on the hardware:

  • MicroLogix 1400 Series B: apply firmware FRN 21.002 or later and use the enhanced password security feature.
  • RSLogix 500: use v11 or later together with FRN 21.001 or later on MicroLogix 1400 Series B; other configurations have no direct mitigation.
  • MicroLogix 1400 Series A and MicroLogix 1100: Rockwell reports no mitigations.

For controllers without a fix, CISA's general advice applies: keep them off the internet, behind firewalls and away from business networks, and use secure remote access. Rockwell's larger Logix family had a comparable shared-key issue, CVE-2021-22681, and our Rockwell Logix controller guide collects them. For device makers, the hard-coded credentials fix guide and the weak cryptography fix guide cover keys embedded in engineering tools and firmware.

Is CVE-2020-6990 exploited?

CVE-2020-6990 is not in the CISA KEV catalog as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS gives it 0.05888, the 93.99th percentile, in the 2026-11-26 dataset (CISA KEV, FIRST EPSS). CISA reported no known public exploits specifically targeting these vulnerabilities.

Three signals on every advisory: CVSS says how severe the flaw is, EPSS gives the probability of exploitation in the wild in the next 30 days, and a CISA KEV listing means the flaw has been exploited in the wild
CVSS rates severity, EPSS estimates the likelihood of exploitation, and CISA KEV records exploitation seen in the wild. Source: FIRST EPSS; CISA KEV catalog.
How to fix this class of issueThis advisory's weakness class is Hard-coded credentials. Our practical guide covers how to detect, fix, verify and disclose it: How to fix hard-coded credentials in embedded firmware.
From advisory to verified fix in four steps: read the advisory, find the affected component in the firmware SBOM, apply the fixed version or vendor mitigation, then re-scan the image to confirm the vulnerable version is gone
Read the advisory, find the component in your firmware SBOM, apply the fix, then re-scan to confirm it.

Evidence

  • NVD (read 2026-11-27): status Modified; published 2020-03-16; [email protected] Primary CVSS 3.1 9.8 AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H, CVSS 2.0 10.0; CISA ADP Secondary 9.8 same vector; NVD CWE-798, ICS-CERT CWE-321; CPEs micrologix_1400_a_firmware (all), micrologix_1400_b_firmware <= 21.001, micrologix_1100_firmware (all), rslogix_500 <= 12.001. — NVD
  • CVE record (CNA icscert, published 2020-03-16): affected products and description as quoted; no CNA CVSS. — CVE.org
  • CISA ICSA-20-070-06 (CSAF, 2020-03-10): CVE-2020-6990 CWE-321 CVSS 3.0 9.8; siblings CVE-2020-6984, -6988, -6980; mitigations: FRN 21.002 or later + enhanced password security for 1400 Series B; no mitigations for 1400 Series A or 1100; RSLogix 500 v11 or later with FRN 21.001 or later; researchers ScadaX Security, Positive Technologies, 307 Lab; sectors Multiple; no known public exploits. — CISA CSAF
  • NVD Primary scores of siblings (read 2026-11-27): CVE-2020-6984 7.5, CVE-2020-6988 7.5, CVE-2020-6980 3.3. — NVD
  • CISA KEV catalog version 2026.11.25, 1,805 entries: CVE-2020-6990 not listed; checked 2026-11-27. — CISA KEV
  • EPSS 0.05888, percentile 0.93989, dataset 2026-11-26, read 2026-11-27. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. CISA ICSA-20-070-06: Rockwell Automation MicroLogix Controllers and RSLogix 500 Software (CSAF)
  3. CISA ICSA-20-070-06 advisory page
  4. CVE.org record CVE-2020-6990
  5. CISA KEV
  6. FIRST EPSS

Frequently asked questions

Which Rockwell products are affected by CVE-2020-6990?

RSLogix 500 12.001 and earlier, MicroLogix 1400 Series B 21.001 and earlier, and all versions of MicroLogix 1400 Series A and MicroLogix 1100, per the CVE record and CISA ICSA-20-070-06.

Which firmware fixes CVE-2020-6990?

For MicroLogix 1400 Series B, Rockwell recommends FRN 21.002 or later with the enhanced password security feature. Rockwell reports no mitigation for MicroLogix 1400 Series A or the MicroLogix 1100.

Why do NVD and CISA list different CWEs for CVE-2020-6990?

CISA maps the flaw to CWE-321, use of a hard-coded cryptographic key, while NVD's own analysis uses CWE-798, use of hard-coded credentials. Both score it 9.8.

Is CVE-2020-6990 in the CISA KEV catalog?

No, not as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS rates it 0.05888, the 93.99th percentile, in the 2026-11-26 dataset.