Security Advisory

CVE-2017-5142: Honeywell XL Web II Privilege Flaw

Last updated:
  • CVE-2017-5142

**CVE-2017-5142** lets a user with low privileges open and change parameters by accessing a specific URL on Honeywell XL Web II building controllers (XL1000C500 XLWebExe-2-01-00 and prior, XLWeb 500 XLWebExe-1-02-08 and prior). The controller does not enforce its own roles on that URL. NVD scores it 9.1 on CVSS v3.0; Honeywell fixed it in version 3.04.05.05.

Vulnerability summary

CVSS base score

9.1

Critical severity

EPSS score (FIRST)

1.0%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2017-5142 · Source: NVD

Affected components

ComponentCPEVersion range
Honeywell XL Web II controller XL1000C500cpe:2.3:o:honeywell:xl_web_ii_controller:xlwebexe-2-01-00:*:*:*:*:*:*:*XLWebExe-2-01-00 and prior (CISA ICSA-17-033-01; NVD CPE lists only xlwebexe-2-01-00). Fix: version 3.04.05.05 via the local Honeywell HBS branch
Honeywell XL Web II controller XLWeb 500cpe:2.3:o:honeywell:xl_web_ii_controller:xlwebexe-1-02-08:*:*:*:*:*:*:*XLWebExe-1-02-08 and prior (CISA ICSA-17-033-01; NVD CPE lists only xlwebexe-1-02-08). Fix: version 3.04.05.05 via the local Honeywell HBS branch; FALCON-branded units via Centraline

What does this mean for affected devices?

NVD carries the ICS-CERT description: "An issue was discovered in Honeywell XL Web II controller XL1000C500 XLWebExe-2-01-00 and prior, and XLWeb 500 XLWebExe-1-02-08 and prior. A user with low privileges is able to open and change the parameters by accessing a specific URL because of Improper Privilege Management." The record was published on 2017-02-13 (NVD, CVE.org).

Why does a parameter change matter on a building controller?

An XL Web II controller runs plant such as HVAC from its parameters, so a read-only or operator-level account that can rewrite them can change how the building runs. The attacker needs some account first; on these controllers that bar is lowered by CVE-2017-5139 and CVE-2017-5140, which expose a stored password. Neither CISA nor NVD names the URL or the parameters involved.

How severe is it, and who scored it?

NVD's Primary scores are 9.1 on CVSS v3.0 (CVSS:3.0/AV:N/AC:L/PR:L/UI:N/S:C/C:H/I:L/A:L) and 6.5 on CVSS v2. The changed scope (S:C) reflects impact beyond the web application itself. CISA's CSAF file puts 8.6 in the structured score field of all five CVEs, while its advisory text gives 9.8, 9.8, 6.0, 9.1 and 8.6 for CVE-2017-5139 to CVE-2017-5143, the same as NVD; use the per-CVE scores. NVD and CISA both class it CWE-269 (improper privilege management).

Which controllers are affected, and what fixes it?

CISA's advisory ICSA-17-033-01 (2017-02-02) lists the XL1000C500 on XLWebExe-2-01-00 and prior and the XLWeb 500 on XLWebExe-1-02-08 and prior. Honeywell fixed all five XL Web II flaws in version 3.04.05.05 and asks users to contact their local Honeywell HBS branch to have sites updated. In the Centraline partner channel the same Excel Web controllers were sold under the FALCON brand; those owners get the update from Centraline (CSAF record). Honeywell's product security table lists the advisory as "XL Web II Controller Password Exposure Vulnerabilities", rated Critical. CISA credits independent researcher Maxim Rupp and reported no known public exploits specifically targeting these flaws. NVD's CPE configuration lists only the exact releases xlwebexe-1-02-08 and xlwebexe-2-01-00, while CISA says "and prior", so a scanner matching on CPE alone can miss older units.

Until the update is in, give accounts on the controller only to people who need them, review the controller's parameters for unexpected changes, and keep its web interface off the internet and office networks. The advisory's five CVEs: CVE-2017-5139 password disclosure through a URL, CVE-2017-5140 password stored in clear text, CVE-2017-5141 session fixation, CVE-2017-5142 parameter changes by low-privileged users and CVE-2017-5143 unauthenticated directory traversal. The earlier CVE-2015-0984 hit the same Excel Web controller family through its FTP server. Our Honeywell Experion and ControlEdge guide covers XL Web II alongside the Experion advisories, and the authentication bypass fix guide covers missing access checks in device web interfaces.

CVE-2017-5142 is not in the CISA KEV catalog as of 2026-11-23 (catalog version 2026.11.20, 1,790 entries). FIRST EPSS gives it 0.01008, a percentile of 63.9, in the 2026-11-22 dataset (CISA KEV, FIRST EPSS).

How to fix this class of issueNo dedicated SoftWSP guide covers this weakness class; the fix is usually the vendor patch or firmware update referenced above. Our related guide explains how to plan and verify it: NIST SP 800-40 Rev. 4: enterprise patch management planning, explained.

Evidence

  • NVD (read 2026-11-23): status Modified, published 2017-02-13; NVD Primary CVSS v3.0 9.1 CVSS:3.0/AV:N/AC:L/PR:L/UI:N/S:C/C:H/I:L/A:L and CVSS v2 6.5 AV:N/AC:L/Au:S/C:P/I:P/A:P; CWE-269; CPEs xl_web_ii_controller xlwebexe-1-02-08 and xlwebexe-2-01-00. — NVD
  • CVE record (checked 2026-11-23): state PUBLISHED, CNA ICS-CERT, published 2017-02-13; product Honeywell XL Web II Controller; 'Improper Privilege Management'; no CNA CVSS score. — CVE.org
  • CVE-2017-5142 CWE-269; text: a user with low privileges is able to open and change the parameters by accessing a specific URL, CVSS v3 9.1 AV:N/AC:L/PR:L/UI:N/S:C/C:H/I:L/A:L. ICSA-17-033-01 CSAF: fix version 3.04.05.05 via local Honeywell HBS branch; FALCON-branded Excel Web controllers via Centraline; products XLWeb 500 XLWebExe <= 1-02-08 and XL1000C500 XLWebExe <= 2-01-00; credit Maxim Rupp; no known public exploits; structured score 8.6 on all five CVEs, text scores 9.8/9.8/6.0/9.1/8.6 — CISA CSAF ICSA-17-033-01
  • Honeywell lists ICSA-17-033-01 XL Web II Controller Password Exposure Vulnerabilities for XL1000C500 XLWebExe-2-01-00 and prior and XLWeb 500 XLWebExe-1-02-08 and prior, CVE-2017-5139 to CVE-2017-5143, severity Critical, 2017-02-02 (read 2026-11-23). — Honeywell product security notices
  • Not in the CISA KEV catalog, version 2026.11.20 (1,790 entries), checked 2026-11-23. — CISA KEV
  • EPSS 0.01008, percentile 0.63903, dataset 2026-11-22, read 2026-11-23. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. CVE.org record CVE-2017-5142
  3. CISA ICSA-17-033-01: Honeywell XL Web II Controller Vulnerabilities
  4. CISA CSAF ICSA-17-033-01 (machine-readable advisory)
  5. Honeywell product security notices
  6. CISA KEV catalog
  7. FIRST EPSS

Frequently asked questions

Does CVE-2017-5142 need a login?

Yes, a low-privileged one. NVD's vector has PR:L. CISA says a user with low privileges can open and change the parameters by accessing a specific URL; the password disclosure flaws CVE-2017-5139 and CVE-2017-5140 on the same controllers make getting an account easier.

Which XL Web II versions fix CVE-2017-5142?

Version 3.04.05.05, through the local Honeywell HBS branch, per CISA ICSA-17-033-01. Affected: XL1000C500 XLWebExe-2-01-00 and prior and XLWeb 500 XLWebExe-1-02-08 and prior; FALCON-branded units via Centraline.

Why is the score 9.1 and not 8.6?

NVD and CISA's advisory text both give CVE-2017-5142 a CVSS v3 score of 9.1. The 8.6 in CISA's machine-readable CSAF file is the same value repeated for all five CVEs in ICSA-17-033-01.

Is CVE-2017-5142 exploited in the wild?

It is not in the CISA KEV catalog as of 2026-11-23 (catalog version 2026.11.20). FIRST EPSS gives 0.01008, percentile 63.9, in the 2026-11-22 dataset.