Security Advisory

CVE-2017-5139: Honeywell XL Web II Password Disclosure

Last updated:
  • CVE-2017-5139

**CVE-2017-5139** lets any user read a password by opening a specific URL on Honeywell XL Web II building controllers (XL1000C500 XLWebExe-2-01-00 and prior, XLWeb 500 XLWebExe-1-02-08 and prior), because the controller stores it in plaintext. A disclosed password hands the attacker the controller's web interface. NVD scores it 9.8 on CVSS v3.0, and Honeywell fixed it in version 3.04.05.05.

Vulnerability summary

CVSS base score

9.8

Critical severity

EPSS score (FIRST)

1.7%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2017-5139 · Source: NVD

Affected components

ComponentCPEVersion range
Honeywell XL Web II controller XL1000C500cpe:2.3:o:honeywell:xl_web_ii_controller:xlwebexe-2-01-00:*:*:*:*:*:*:*XLWebExe-2-01-00 and prior (CISA ICSA-17-033-01; NVD CPE lists only xlwebexe-2-01-00). Fix: version 3.04.05.05 via the local Honeywell HBS branch
Honeywell XL Web II controller XLWeb 500cpe:2.3:o:honeywell:xl_web_ii_controller:xlwebexe-1-02-08:*:*:*:*:*:*:*XLWebExe-1-02-08 and prior (CISA ICSA-17-033-01; NVD CPE lists only xlwebexe-1-02-08). Fix: version 3.04.05.05 via the local Honeywell HBS branch; FALCON-branded units via Centraline

What does this mean for affected devices?

NVD carries the ICS-CERT description: "An issue was discovered in Honeywell XL Web II controller XL1000C500 XLWebExe-2-01-00 and prior, and XLWeb 500 XLWebExe-1-02-08 and prior. Any user is able to disclose a password by accessing a specific URL, because of Plaintext Storage of a Password." The record was published on 2017-02-13 (NVD, CVE.org).

How severe is it, and who scored it?

NVD's Primary scores are 9.8 on CVSS v3.0 (CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H) and 5.0 on CVSS v2. A disclosed password is a full takeover of the controller's web interface, which is why the v3.0 score counts integrity and availability impact as high. CISA's CSAF file puts 8.6 in the structured score field of all five CVEs, while its advisory text gives 9.8, 9.8, 6.0, 9.1 and 8.6 for CVE-2017-5139 to CVE-2017-5143, the same as NVD; use the per-CVE scores. CISA classes it CWE-256 (plaintext storage of a password); NVD maps it to CWE-522 (insufficiently protected credentials).

Which controllers are affected, and what fixes it?

CISA's advisory ICSA-17-033-01 (2017-02-02) lists the XL1000C500 on XLWebExe-2-01-00 and prior and the XLWeb 500 on XLWebExe-1-02-08 and prior. Honeywell fixed all five XL Web II flaws in version 3.04.05.05 and asks users to contact their local Honeywell HBS branch to have sites updated. In the Centraline partner channel the same Excel Web controllers were sold under the FALCON brand; those owners get the update from Centraline (CSAF record). Honeywell's product security table lists the advisory as "XL Web II Controller Password Exposure Vulnerabilities", rated Critical. CISA credits independent researcher Maxim Rupp and reported no known public exploits specifically targeting these flaws. NVD's CPE configuration lists only the exact releases xlwebexe-1-02-08 and xlwebexe-2-01-00, while CISA says "and prior", so a scanner matching on CPE alone can miss older units.

What should a building operator do?

Get the controllers updated to 3.04.05.05. Until then, assume any password the controller holds is known: keep its web interface off the internet and off shared office networks, reach it only through a managed remote access path, and change the passwords after the update. The advisory's five CVEs: CVE-2017-5139 password disclosure through a URL, CVE-2017-5140 password stored in clear text, CVE-2017-5141 session fixation, CVE-2017-5142 parameter changes by low-privileged users and CVE-2017-5143 unauthenticated directory traversal. The earlier CVE-2015-0984 hit the same Excel Web controller family through its FTP server. Our Honeywell Experion and ControlEdge guide covers XL Web II alongside the Experion advisories, and the hard-coded credentials fix guide covers credential storage in firmware.

CVE-2017-5139 is not in the CISA KEV catalog as of 2026-11-23 (catalog version 2026.11.20, 1,790 entries). FIRST EPSS gives it 0.01744, a percentile of 78.4, in the 2026-11-22 dataset (CISA KEV, FIRST EPSS).

How to fix this class of issueNo dedicated SoftWSP guide covers this weakness class; the fix is usually the vendor patch or firmware update referenced above. Our related guide explains how to plan and verify it: NIST SP 800-40 Rev. 4: enterprise patch management planning, explained.

Evidence

  • NVD (read 2026-11-23): status Modified, published 2017-02-13; NVD Primary CVSS v3.0 9.8 CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H and CVSS v2 5.0 AV:N/AC:L/Au:N/C:P/I:N/A:N; CWE-522; CPEs xl_web_ii_controller xlwebexe-1-02-08 and xlwebexe-2-01-00. — NVD
  • CVE record (checked 2026-11-23): state PUBLISHED, CNA ICS-CERT, published 2017-02-13; product Honeywell XL Web II Controller; 'Plaintext Storage of a Password'; no CNA CVSS score. — CVE.org
  • CVE-2017-5139 CWE-256; text: any user is able to disclose a password by accessing a specific URL, CVSS v3 9.8 AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H. ICSA-17-033-01 CSAF: fix version 3.04.05.05 via local Honeywell HBS branch; FALCON-branded Excel Web controllers via Centraline; products XLWeb 500 XLWebExe <= 1-02-08 and XL1000C500 XLWebExe <= 2-01-00; credit Maxim Rupp; no known public exploits; structured score 8.6 on all five CVEs, text scores 9.8/9.8/6.0/9.1/8.6 — CISA CSAF ICSA-17-033-01
  • Honeywell lists ICSA-17-033-01 XL Web II Controller Password Exposure Vulnerabilities for XL1000C500 XLWebExe-2-01-00 and prior and XLWeb 500 XLWebExe-1-02-08 and prior, CVE-2017-5139 to CVE-2017-5143, severity Critical, 2017-02-02 (read 2026-11-23). — Honeywell product security notices
  • Not in the CISA KEV catalog, version 2026.11.20 (1,790 entries), checked 2026-11-23. — CISA KEV
  • EPSS 0.01744, percentile 0.78366, dataset 2026-11-22, read 2026-11-23. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. CVE.org record CVE-2017-5139
  3. CISA ICSA-17-033-01: Honeywell XL Web II Controller Vulnerabilities
  4. CISA CSAF ICSA-17-033-01 (machine-readable advisory)
  5. Honeywell product security notices
  6. CISA KEV catalog
  7. FIRST EPSS

Frequently asked questions

How does CVE-2017-5139 expose the password?

Per CISA and NVD, any user can disclose a password by accessing a specific URL on the controller, because the password is stored in plaintext. Neither source publishes the URL.

Which XL Web II versions fix CVE-2017-5139?

Version 3.04.05.05, through the local Honeywell HBS branch. Affected: XL1000C500 XLWebExe-2-01-00 and prior and XLWeb 500 XLWebExe-1-02-08 and prior. FALCON-branded units sold through Centraline get the update from Centraline.

Why does CISA's CSAF file say 8.6 instead of 9.8?

CISA's machine-readable file puts 8.6 in the score field of all five CVEs in ICSA-17-033-01. Its advisory text gives CVE-2017-5139 a CVSS v3 score of 9.8, which matches NVD.

Is CVE-2017-5139 exploited in the wild?

It is not in the CISA KEV catalog as of 2026-11-23 (catalog version 2026.11.20), and CISA reported no known public exploits in 2017. FIRST EPSS gives 0.01744, percentile 78.4, in the 2026-11-22 dataset.