**CVE-2017-5140** is cleartext password storage in Honeywell XL Web II building controllers (XL1000C500 XLWebExe-2-01-00 and prior, XLWeb 500 XLWebExe-1-02-08 and prior). Anyone who can read the controller's stored data gets the password as-is, with nothing to crack. NVD scores it 9.8 on CVSS v3.0, and Honeywell fixed it in version 3.04.05.05.
Vulnerability summary
CVSS base score
9.8
Critical severity
EPSS score (FIRST)
1.7%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2017-5140 · Source: NVD
Affected components
| Component | CPE | Version range |
|---|---|---|
| Honeywell XL Web II controller XL1000C500 | cpe:2.3:o:honeywell:xl_web_ii_controller:xlwebexe-2-01-00:*:*:*:*:*:*:* | XLWebExe-2-01-00 and prior (CISA ICSA-17-033-01; NVD CPE lists only xlwebexe-2-01-00). Fix: version 3.04.05.05 via the local Honeywell HBS branch |
| Honeywell XL Web II controller XLWeb 500 | cpe:2.3:o:honeywell:xl_web_ii_controller:xlwebexe-1-02-08:*:*:*:*:*:*:* | XLWebExe-1-02-08 and prior (CISA ICSA-17-033-01; NVD CPE lists only xlwebexe-1-02-08). Fix: version 3.04.05.05 via the local Honeywell HBS branch; FALCON-branded units via Centraline |
What does this mean for affected devices?
NVD carries the ICS-CERT description: "An issue was discovered in Honeywell XL Web II controller XL1000C500 XLWebExe-2-01-00 and prior, and XLWeb 500 XLWebExe-1-02-08 and prior. Password is stored in clear text." The record was published on 2017-02-13 (NVD, CVE.org).
How is it different from CVE-2017-5139?
The two records describe the same weakness from two sides. CVE-2017-5139 is the network path: any user can read a password through a specific URL. CVE-2017-5140 is the storage flaw itself: the password is kept in clear text, so any other way of reading the controller's data, such as a configuration backup or the CVE-2017-5143 directory traversal, also yields it. Neither source says which account the password belongs to.
How severe is it, and who scored it?
NVD's Primary scores are 9.8 on CVSS v3.0 (CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H) and 5.0 on CVSS v2. CISA's CSAF file puts 8.6 in the structured score field of all five CVEs, while its advisory text gives 9.8, 9.8, 6.0, 9.1 and 8.6 for CVE-2017-5139 to CVE-2017-5143, the same as NVD; use the per-CVE scores. NVD and CISA both class it CWE-522 (insufficiently protected credentials).
Which controllers are affected, and what fixes it?
CISA's advisory ICSA-17-033-01 (2017-02-02) lists the XL1000C500 on XLWebExe-2-01-00 and prior and the XLWeb 500 on XLWebExe-1-02-08 and prior. Honeywell fixed all five XL Web II flaws in version 3.04.05.05 and asks users to contact their local Honeywell HBS branch to have sites updated. In the Centraline partner channel the same Excel Web controllers were sold under the FALCON brand; those owners get the update from Centraline (CSAF record). Honeywell's product security table lists the advisory as "XL Web II Controller Password Exposure Vulnerabilities", rated Critical. CISA credits independent researcher Maxim Rupp and reported no known public exploits specifically targeting these flaws. NVD's CPE configuration lists only the exact releases xlwebexe-1-02-08 and xlwebexe-2-01-00, while CISA says "and prior", so a scanner matching on CPE alone can miss older units.
After the update, change the passwords the controller held, since they may already have been read, and keep its web interface off the internet and office networks. The advisory's five CVEs: CVE-2017-5139 password disclosure through a URL, CVE-2017-5140 password stored in clear text, CVE-2017-5141 session fixation, CVE-2017-5142 parameter changes by low-privileged users and CVE-2017-5143 unauthenticated directory traversal. The earlier CVE-2015-0984 hit the same Excel Web controller family through its FTP server. Our Honeywell Experion and ControlEdge guide covers XL Web II alongside the Experion advisories, and the hard-coded credentials fix guide covers how firmware should store credentials.
CVE-2017-5140 is not in the CISA KEV catalog as of 2026-11-23 (catalog version 2026.11.20, 1,790 entries). FIRST EPSS gives it 0.01744, a percentile of 78.4, in the 2026-11-22 dataset (CISA KEV, FIRST EPSS).
Evidence
- NVD (read 2026-11-23): status Modified, published 2017-02-13; NVD Primary CVSS v3.0 9.8 CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H and CVSS v2 5.0; CWE-522; CPEs xl_web_ii_controller xlwebexe-1-02-08 and xlwebexe-2-01-00. — NVD
- CVE record (checked 2026-11-23): state PUBLISHED, CNA ICS-CERT, published 2017-02-13; product Honeywell XL Web II Controller; 'Password is stored in clear text'; no CNA CVSS score. — CVE.org
- CVE-2017-5140 CWE-522; text: password is stored in clear text, CVSS v3 9.8 AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H. ICSA-17-033-01 CSAF: fix version 3.04.05.05 via local Honeywell HBS branch; FALCON-branded Excel Web controllers via Centraline; products XLWeb 500 XLWebExe <= 1-02-08 and XL1000C500 XLWebExe <= 2-01-00; credit Maxim Rupp; no known public exploits; structured score 8.6 on all five CVEs, text scores 9.8/9.8/6.0/9.1/8.6 — CISA CSAF ICSA-17-033-01
- Honeywell lists ICSA-17-033-01 XL Web II Controller Password Exposure Vulnerabilities for XL1000C500 XLWebExe-2-01-00 and prior and XLWeb 500 XLWebExe-1-02-08 and prior, CVE-2017-5139 to CVE-2017-5143, severity Critical, 2017-02-02 (read 2026-11-23). — Honeywell product security notices
- Not in the CISA KEV catalog, version 2026.11.20 (1,790 entries), checked 2026-11-23. — CISA KEV
- EPSS 0.01744, percentile 0.78366, dataset 2026-11-22, read 2026-11-23. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
What does CVE-2017-5140 mean in practice?
The XL Web II controller keeps a password in clear text, so anyone who reads the stored data, for example through the CVE-2017-5139 URL or the CVE-2017-5143 directory traversal, gets the password without cracking anything.
Which XL Web II versions fix CVE-2017-5140?
Version 3.04.05.05, through the local Honeywell HBS branch, per CISA ICSA-17-033-01. Affected: XL1000C500 XLWebExe-2-01-00 and prior and XLWeb 500 XLWebExe-1-02-08 and prior; FALCON-branded units via Centraline.
Should passwords be changed after updating?
Yes. The update stops cleartext storage, but any password read from an unpatched controller is still valid until it is changed. Neither CISA nor Honeywell lists a workaround that protects the stored password before the update.
Is CVE-2017-5140 exploited in the wild?
It is not in the CISA KEV catalog as of 2026-11-23 (catalog version 2026.11.20). FIRST EPSS gives 0.01744, percentile 78.4, in the 2026-11-22 dataset.
Questions about this page?