CVE-2016-3949 lets a remote attacker push a Siemens SIMATIC S7-300 CPU into defect mode with crafted packets to port 102/tcp (ISO-TSAP) or via PROFIBUS; only a cold restart recovers it. NVD scores it 7.5 (CWE-399). Siemens SSA-818183 fixes it in firmware V3.2.12 (Profinet CPUs) and V3.3.12 (non-Profinet CPUs), including ET200 and SIPLUS variants.
Vulnerability summary
CVSS base score
7.5
High severity
EPSS score (FIRST)
4.5%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2016-3949 · Source: NVD
Affected components
| Component | CPE | Version range |
|---|---|---|
| SIMATIC S7-300 CPU family with Profinet support (incl. related ET200 CPUs and SIPLUS variants) | cpe:2.3:o:siemens:simatic_s7-300_with_profitnet_support_firmware:3.2.11:*:*:*:*:*:*:* | All versions before V3.2.12; fixed in V3.2.12 (Siemens SSA-818183). NVD's CPE lists only firmware 3.2.11 |
| SIMATIC S7-300 CPU family without Profinet support (incl. related ET200 CPUs and SIPLUS variants) | cpe:2.3:o:siemens:simatic_s7-300_without_profitnet_support_firmware:3.3.11:*:*:*:*:*:*:* | All versions before V3.3.12; fixed in V3.3.12 (Siemens SSA-818183). NVD's CPE lists only firmware 3.3.11 |
What does this mean for affected devices?
NVD carries MITRE's description: S7-300 Profinet-enabled CPUs "with firmware before 3.2.12" and Profinet-disabled CPUs "with firmware before 3.3.12 allow remote attackers to cause a denial of service (defect-mode transition) via crafted (1) ISO-TSAP or (2) Profibus packets." NVD's Primary score is CVSS v3.0 7.5 (CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H) with CWE-399 (resource management errors). The record was published on 2016-06-27 (NVD, CVE record).
What happens to the PLC?
Siemens ProductCERT SSA-818183 states that "specially crafted packets sent to port 102/tcp (ISO-TSAP) or via Profibus could cause the affected device to go into defect mode. A cold restart is required to recover the system." The CPU stops controlling the process until someone restarts it on site, so this is a stop-the-line risk on any network segment or PROFIBUS line an attacker can reach. Siemens scores it 7.5 with CVSS v3.1 and classes it CWE-20 (improper input validation); CISA's ICSA-16-161-01 CSAF uses 7.5 as well with CWE-664. Siemens credits Mate J. Csorba of DNV GL and Amund Sole of NTNU.
Which firmware versions are affected and fixed?
| Product (incl. related ET200 CPUs and SIPLUS variants) | Affected | Fixed |
|---|---|---|
| SIMATIC S7-300 CPU family with Profinet support | All versions before V3.2.12 | V3.2.12 |
| SIMATIC S7-300 CPU family without Profinet support | All versions before V3.3.12 | V3.3.12 |
SSA-818183 V1.1 (2020-02-10) added the SIPLUS variants. NVD's CPE configuration lists only firmware 3.2.11 and 3.3.11, so a scanner keyed to NVD misses older S7-300 firmware, ET200 CPUs and SIPLUS units. CISA's CSAF product tree writes the ranges as "<=3.2.12" and "<=3.3.12", while its own remediation text says those versions fix the flaw; go by Siemens.
How do you fix or mitigate it?
Update to V3.2.12 or V3.3.12 or later. Where an update has to wait, Siemens lists two mitigations: apply protection level 3 (read/write protection) and operate the device only within trusted networks. Block port 102/tcp at the cell boundary and keep PROFIBUS segments physically controlled; our PROFIBUS security guide covers that, and our input handling fix guide covers the CWE-20 pattern. The same CPUs face other packet-triggered stops: CVE-2017-2680 (PROFINET DCP), CVE-2018-4843 and CVE-2019-10936.
CVE-2016-3949 is not in the CISA KEV catalog as of 2026-11-19 (catalog version 2026.11.18, 1,786 entries). FIRST EPSS gives it 0.04492, the 91.7th percentile, in the 2026-11-18 dataset (CISA KEV, FIRST EPSS).
Evidence
- NVD: status Modified; S7-300 Profinet-enabled CPUs before 3.2.12 and Profinet-disabled CPUs before 3.3.12 allow remote DoS (defect-mode transition) via crafted ISO-TSAP or Profibus packets; NVD Primary CVSS v3.0 7.5 AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H, v2 7.8; CWE-399; CPE configuration only firmware 3.2.11 (with Profinet) and 3.3.11 (without); references SSA-818183 and ICSA-16-161-01; published 2016-06-27. — NVD
- Siemens SSA-818183 V1.1 (published 2016-06-08, updated 2020-02-10): crafted packets to port 102/tcp (ISO-TSAP) or via Profibus cause defect mode, cold restart required; CVSS v3.1 7.5 (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H/E:P/RL:O/RC:C); CWE-20; affected S7-300 with Profinet support all versions < V3.2.12 (fix V3.2.12), without Profinet support < V3.3.12 (fix V3.3.12), incl. related ET200 CPUs and SIPLUS variants; mitigations protection level 3 (read/write protection) and trusted networks only; credits Mate J. Csorba (DNV GL), Amund Sole (NTNU), Artem Zinenko (Kaspersky) for the SIPLUS note. — Siemens ProductCERT SSA-818183
- ICSA-16-161-01 CSAF 'Siemens SIMATIC S7-300 Denial-of-Service Vulnerability': CVSS v3.0 7.5, CWE-664; product tree S7-300 with Profinet support <=3.2.12 and without <=3.3.12; remediation says V3.2.12 and V3.3.12 fix the vulnerability and points to SSA-818183; CISA note that the CSAF was extracted from unstructured data and may contain inaccuracies. — CISA CSAF ICSA-16-161-01
- CVE record: state PUBLISHED, CNA MITRE, published 2016-06-27; references SSA-818183 and ICSA-16-161-01. — CVE.org
- Not in the CISA KEV catalog, version 2026.11.18 (released 2026-11-18, 1,786 entries), checked 2026-11-19. — CISA KEV
- EPSS 0.04492, percentile 0.91666, dataset 2026-11-18, read 2026-11-19. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
Which firmware fixes CVE-2016-3949?
V3.2.12 for SIMATIC S7-300 CPUs with Profinet support and V3.3.12 for S7-300 CPUs without Profinet support, including related ET200 CPUs and SIPLUS variants (per Siemens SSA-818183 and CISA ICSA-16-161-01).
How does an S7-300 recover after CVE-2016-3949 is triggered?
Only with a cold restart. Siemens states that crafted packets to port 102/tcp (ISO-TSAP) or via PROFIBUS put the CPU into defect mode, so the controlled process stops until the CPU is restarted (per SSA-818183).
What can I do if I cannot update the S7-300 firmware?
Siemens lists protection level 3 (read/write protection) and operating the device only within trusted networks. In practice that means blocking port 102/tcp from untrusted zones and restricting physical access to PROFIBUS segments (per SSA-818183).
Is CVE-2016-3949 exploited in the wild?
It is not in the CISA KEV catalog as of 2026-11-19 (catalog version 2026.11.18). FIRST EPSS gives it 0.04492, the 91.7th percentile, in the 2026-11-18 dataset.
Questions about this page?