Security Advisory

CVE-2015-6574: SISCO MMS-EASE SNAP Lite DoS

Last updated:
  • CVE-2015-6574

CVE-2015-6574 is a denial-of-service flaw in the SNAP Lite component of SISCO MMS-EASE and AX-S4 ICCP: a crafted packet drives CPU consumption. NVD and Siemens both score it 7.5. Through the SISCO stack it affects SIPROTEC 5 protection relays, fixed in V7.58, V7.62 or V7.80 by model; otherwise restrict TCP port 102 to trusted hosts.

Vulnerability summary

CVSS base score

7.5

High severity

EPSS score (FIRST)

5.4%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2015-6574 · Source: NVD

Affected components

ComponentCPEVersion range
SISCO MMS-EASEcpe:2.3:a:sisco:mms-ease_firmware:11.2000:*:*:*:*:*:*:*11.2000 (NVD CPE configuration)
SISCO AX-S4 ICCPcpe:2.3:a:sisco:ax-s4_iccp_firmware:6.0000:*:*:*:*:*:*:*6.0000 (NVD CPE configuration)
Siemens SIPROTEC 5 devices (6MD85, 6MD86, 7SA82/84/86/87, 7SD82/84/86/87, 7SJ81/82/85/86, 7SK82/85, 7SL82/86/87, 7SS85, 7UM85, 7UT82/85/86/87, 7VK87; CP100, CP200, CP300 as listed)—All versions before V7.58; fixed in V7.58 (Siemens SSA-223771, CISA ICSA-22-349-14 CSAF revision 5); not in NVD's CPE configuration
Siemens SIPROTEC 5 6MD89 (CP300), 7KE85 (CP200, CP300), 7VE85 (CP300)—All versions before V7.80; fixed in V7.80 (Siemens SSA-223771); not in NVD's CPE configuration
Siemens SIPROTEC 5 7ST85 (CP200)—All versions before V7.62; fixed in V7.62 (Siemens SSA-223771 V1.3); not in NVD's CPE configuration
Siemens SIPROTEC 5 Communication Modules ETH-BA-2EL and ETH-BB-2FO—All versions before V7.58; fixed in V7.58 (Siemens SSA-223771); not in NVD's CPE configuration

What does this mean for affected devices?

NVD describes CVE-2015-6574 in one sentence: "The SNAP Lite component in certain SISCO MMS-EASE and AX-S4 ICCP products allows remote attackers to cause a denial of service (CPU consumption) via a crafted packet." MMS-EASE is SISCO's MMS (ISO 9506) protocol stack and AX-S4 ICCP its ICCP/TASE.2 product, so the flaw sits in the transport layer that inter-control-centre links and IEC 61850 devices use. NVD's Primary score is CVSS v3.0 7.5 (CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H), with CWE-399 (resource management errors). MITRE assigned the record, which carries no CNA score; it was published on 2016-12-15 (NVD, CVE record). NVD's CPE configuration names only MMS-EASE 11.2000 and AX-S4 ICCP 6.0000.

Which devices are affected?

The flaw reached substation equipment through the SISCO stack. Siemens ProductCERT SSA-223771 ("SISCO Stack Vulnerability in SIPROTEC 5 Devices", first published 2022-12-13, version 1.3 of 2023-08-08) states that a vulnerability in the third-party component SISCO MMS-EASE "could allow attackers to cause a denial of service condition with SIPROTEC 5 devices". It lists more than 40 SIPROTEC 5 protection and bay-controller variants (CP100, CP200 and CP300 platforms) and the communication modules ETH-BA-2EL and ETH-BB-2FO. Siemens scores it CVSS v3.1 7.5 (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H/E:P/RL:O/RC:C) and classifies it as CWE-770, allocation of resources without limits or throttling, and credits Vera Mens of Claroty for the report. CISA republished it as ICSA-22-349-14 ("Siemens SISCO MMS-EASE Third Party Component"); the CSAF version carries the same score, CWE and fixes.

Which firmware fixes CVE-2015-6574 on SIPROTEC 5?

Per SSA-223771, most SIPROTEC 5 devices (for example 6MD85, 6MD86, 7SA8x, 7SD8x, 7SJ8x, 7SK8x, 7SL8x, 7SS85, 7UM85, 7UT8x and 7VK87) and the ETH-BA-2EL and ETH-BB-2FO modules are fixed in V7.58. The 6MD89 (CP300), 7KE85 and 7VE85 need V7.80, and the 7ST85 (CP200) needs V7.62. Until an update is installed, Siemens' workarounds are to disable IEC 61850 communications on the affected port and to restrict TCP port 102 to trusted IP addresses. Siemens also points to redundant secondary protection schemes in grid design. For the SISCO products themselves, NVD lists a SISCO security note as the vendor advisory.

What does this mean for control-centre links?

ICCP and IEC 61850 MMS both run over the ISO stack on TCP 102, so one crafted packet that pins the CPU of an ICCP server or a relay affects availability on the link. Our NERC CIP-012 control-centre communications guide covers protecting that link, the ICCP / TASE.2 security guide covers segmentation, and the input-handling fix guide covers resource limits in protocol parsers. Another ICCP denial of service is CVE-2022-2277 in Hitachi Energy SYS600, and a SIPROTEC-family crash is CVE-2022-30937 in the EN100 module.

CVE-2015-6574 is not in the CISA KEV catalog as of 2026-11-19 (catalog version 2026.11.18, 1,786 entries). FIRST EPSS gives it 0.05413, the 92.9th percentile, in the 2026-11-18 dataset (CISA KEV, FIRST EPSS).

How to fix this class of issueThis advisory's weakness class is Resource exhaustion. Our practical guide covers how to detect, fix, verify and disclose it: How to fix SQL injection, XSS, resource exhaustion and deserialization flaws in embedded firmware.

Evidence

  • NVD: SNAP Lite component in certain SISCO MMS-EASE and AX-S4 ICCP products allows remote DoS (CPU consumption) via a crafted packet; NVD Primary CVSS v3.0 7.5 AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H, v2 7.8; CWE-399; CPE mms-ease_firmware 11.2000 and ax-s4_iccp_firmware 6.0000; references include a SISCO security note tagged Vendor Advisory and Siemens SSA-223771; published 2016-12-15; status Modified, read 2026-11-19. — NVD
  • Siemens ProductCERT SSA-223771 'SISCO Stack Vulnerability in SIPROTEC 5 Devices' (published 2022-12-13, V1.3 2023-08-08): third-party SISCO MMS-EASE allows DoS on SIPROTEC 5; CVSS v3.1 7.5 AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H/E:P/RL:O/RC:C; CWE-770; fixes V7.58 for most models and ETH-BA-2EL/ETH-BB-2FO, V7.80 for 6MD89 CP300, 7KE85, 7VE85, V7.62 for 7ST85 CP200; workarounds disable IEC 61850 on the affected port, restrict 102/tcp to trusted IPs; credit Vera Mens (Claroty), read 2026-11-19. — Siemens ProductCERT
  • CISA ICSA-22-349-14 'Siemens SISCO MMS-EASE Third Party Component' (CSAF, initial release 2022-12-13, revision 5 of 2025-05-06): CVE-2015-6574, CWE-770, CVSS 3.1 7.5; vendor fixes V7.58, V7.62, V7.80; mitigations disable IEC 61850 on affected port and restrict port 102/tcp, read 2026-11-19. — CISA ICS advisory / CSAF
  • CVE record: state PUBLISHED, assigner MITRE, published 2016-12-15, vendor and product n/a, no CNA CVSS; references SISCO security note, Portcullis advisory, BID 95022 and Siemens SSA-223771, checked 2026-11-19. — CVE.org
  • Not in the CISA KEV catalog version 2026.11.18 (1,786 entries), checked 2026-11-19. — CISA KEV
  • EPSS 0.05413, percentile 0.92851, dataset 2026-11-18, read 2026-11-19. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. Siemens ProductCERT SSA-223771: SISCO Stack Vulnerability in SIPROTEC 5 Devices
  3. Siemens ProductCERT SSA-223771 (signed text version)
  4. CISA ICSA-22-349-14: Siemens SISCO MMS-EASE Third Party Component
  5. CISA CSAF: ICSA-22-349-14 (machine-readable advisory)
  6. CVE.org record CVE-2015-6574
  7. CISA KEV
  8. FIRST EPSS

Frequently asked questions

Which SIPROTEC 5 firmware fixes CVE-2015-6574?

V7.58 for most SIPROTEC 5 devices and the ETH-BA-2EL and ETH-BB-2FO communication modules, V7.80 for the 6MD89 (CP300), 7KE85 and 7VE85, and V7.62 for the 7ST85 (CP200) (per Siemens ProductCERT SSA-223771).

How can CVE-2015-6574 be mitigated without a firmware update?

Siemens recommends disabling IEC 61850 communications on the affected port of the device and restricting access to TCP port 102 to trusted IP addresses only, alongside firewalls, segmentation and redundant protection schemes (per Siemens SSA-223771 and CISA ICSA-22-349-14).

Why do NVD and Siemens list different CWEs?

NVD classifies the flaw as CWE-399 (resource management errors), while Siemens uses the more specific CWE-770, allocation of resources without limits or throttling; both score it CVSS 7.5 with network access, no privileges and high availability impact (per NVD and Siemens SSA-223771).

Is CVE-2015-6574 exploited in the wild?

It is not in the CISA KEV catalog as of 2026-11-19 (catalog version 2026.11.18). FIRST EPSS gives it 0.05413, the 92.9th percentile, in the 2026-11-18 dataset; Siemens rates exploit code maturity as proof of concept (E:P) (per CISA KEV, FIRST EPSS and Siemens SSA-223771).