Security Advisory

CVE-2016-4522: FactoryTalk EnergyMetrix SQL Injection

Last updated:
  • CVE-2016-4522

CVE-2016-4522 is a SQL injection flaw in Rockwell Automation FactoryTalk EnergyMetrix versions 2.10.00 and earlier that lets a remote attacker run arbitrary SQL commands. NVD scores it 9.8; CISA scores it 7.3. Rockwell fixed it in 2.20.00 and recommends installing 2.30.00 or the latest version.

Vulnerability summary

CVSS base score

9.8

Critical severity

EPSS score (FIRST)

6.3%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2016-4522 · Source: NVD

CVSS v3.1 severity rating scale: None 0.0, Low 0.1 to 3.9, Medium 4.0 to 6.9, High 7.0 to 8.9, Critical 9.0 to 10.0
How a CVSS v3.1 base score maps to a severity rating. Source: FIRST CVSS v3.1 specification, section 5.

Affected components

ComponentCPEVersion range
Rockwell Automation FactoryTalk EnergyMetrixcpe:2.3:a:rockwellautomation:factorytalk_energrymetrix:*:*:*:*:*:*:*:*2.10.00 and earlier (CISA ICSA-16-173-03; NVD CPE up to and including 2.10.00, product name spelled energrymetrix); fixed in 2.20.00, Rockwell recommends 2.30.00 or later

What does this mean for affected devices?

The CVE description reads: "SQL injection vulnerability in Rockwell Automation FactoryTalk EnergyMetrix before 2.20.00 allows remote attackers to execute arbitrary SQL commands via unspecified vectors." NVD's Primary score is 9.8 (CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H, CVSS 2.0 7.5) with CWE-89. NVD's CPE configuration covers versions up to and including 2.10.00, under the misspelled product name factorytalk_energrymetrix, so CPE-based scanners that search for the correct spelling may miss it (NVD, CVE record).

Why do NVD and CISA scores differ?

CISA's ICSA-16-173-03 gives 7.3 (CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:L/A:L), rating the impact on confidentiality, integrity and availability as low; NVD rates all three as high. Both treat the attack as remote and unauthenticated, and CISA says an attacker with low skill could exploit it. CISA first shared the advisory on its secure portal on 2016-06-21 and reported no known public exploits.

What else does ICSA-16-173-03 cover?

The same advisory lists CVE-2016-4531 (CISA 7.3): EnergyMetrix before 2.20.00 does not invalidate credentials when a user logs out, so someone at an unattended workstation can reuse the session. Both flaws are fixed by the same release. CISA lists the chemical, commercial facilities, critical manufacturing, energy, government facilities and water sectors, worldwide.

How do you fix CVE-2016-4522?

Rockwell Automation released versions 2.20.00 and 2.30.00, which both address the flaws, and recommends installing 2.30.00 or the latest version, available from its download portal with a valid account. Rockwell's additional mitigations, as quoted by CISA (CISA CSAF):

  • follow least privilege, so the service account reaches the database with only the rights it needs;
  • configure and enable HTTPS on the EnergyMetrix server;
  • use trusted software and antivirus, and train users to spot phishing.

Keep the EnergyMetrix server off the Internet and behind a firewall separated from the business network. The input handling fix guide covers parameterized queries, and the OT security guide for small manufacturers covers zoning. Other Rockwell pages: CVE-2017-16740 (MicroLogix 1400 Modbus TCP buffer overflow) and CVE-2018-17924 (unauthenticated CIP IP change).

Is CVE-2016-4522 exploited?

CVE-2016-4522 is not in the CISA KEV catalog as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS gives it 0.06297, the 94.38th percentile, in the 2026-11-26 dataset (CISA KEV, FIRST EPSS).

Three signals on every advisory: CVSS says how severe the flaw is, EPSS gives the probability of exploitation in the wild in the next 30 days, and a CISA KEV listing means the flaw has been exploited in the wild
CVSS rates severity, EPSS estimates the likelihood of exploitation, and CISA KEV records exploitation seen in the wild. Source: FIRST EPSS; CISA KEV catalog.
How to fix this class of issueThis advisory's weakness class is SQL injection. Our practical guide covers how to detect, fix, verify and disclose it: How to fix SQL injection, XSS, resource exhaustion and deserialization flaws in embedded firmware.
From advisory to verified fix in four steps: read the advisory, find the affected component in the firmware SBOM, apply the fixed version or vendor mitigation, then re-scan the image to confirm the vulnerable version is gone
Read the advisory, find the component in your firmware SBOM, apply the fix, then re-scan to confirm it.

Evidence

  • NVD (read 2026-11-27): status Modified; published 2016-07-28; [email protected] Primary CVSS 3.0 9.8 AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H, CVSS 2.0 7.5; CWE-89; CPE rockwellautomation factorytalk_energrymetrix up to and including 2.10.00. — NVD
  • CISA ICSA-16-173-03 (CSAF): FactoryTalk EnergyMetrix <=2.10.00; CVE-2016-4522 CWE-89 7.3; CVE-2016-4531 CWE-613 7.3; versions 2.20.00 and 2.30.00 address them, install 2.30.00 or latest; least privilege, HTTPS, trusted software, phishing training. — CISA CSAF
  • CISA ICSA-16-173-03 page: originally on the US-CERT secure portal 2016-06-21; sectors chemical, commercial facilities, critical manufacturing, energy, government facilities, water, worldwide; remote, low skill; no known public exploits. — CISA
  • CVE.org record (MITRE-era format): published 2016-07-28; before 2.20.00; no CNA CVSS. — CVE.org
  • CISA KEV catalog version 2026.11.25, 1,805 entries: CVE-2016-4522 not listed; checked 2026-11-27. — CISA KEV
  • EPSS 0.06297, percentile 0.94377, dataset 2026-11-26, read 2026-11-27. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. CISA ICSA-16-173-03: Rockwell FactoryTalk EnergyMetrix (CSAF)
  3. CISA ICSA-16-173-03 advisory page
  4. CVE.org record CVE-2016-4522
  5. CISA KEV
  6. FIRST EPSS

Frequently asked questions

Which FactoryTalk EnergyMetrix versions are affected by CVE-2016-4522?

Versions 2.10.00 and earlier. Version 2.20.00 fixes it, and Rockwell Automation recommends 2.30.00 or the latest version.

Why is CVE-2016-4522 9.8 on NVD but 7.3 at CISA?

CISA rates the confidentiality, integrity and availability impact as low; NVD rates all three as high. Both say no login or user interaction is needed.

Why might a scanner miss CVE-2016-4522?

NVD's CPE uses the misspelled product name factorytalk_energrymetrix. Match EnergyMetrix installs by version (2.10.00 or earlier) as well as by CPE.

Is CVE-2016-4522 in the CISA KEV catalog?

No, not as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS rates it 0.06297, the 94.38th percentile, in the 2026-11-26 dataset.