CVE-2022-2277 is a denial-of-service flaw in the ICCP stack of Hitachi Energy MicroSCADA X SYS600 10.2 to 10.3.1: when ICCP is asked to forward data item updates with timestamps too far in the future to a remote ICCP system, the service fails. ICCP is off by default. NVD scores it 7.5. Update SYS600 to 10.4, or keep ICCP disabled where unused.
Vulnerability summary
CVSS base score
7.5
High severity
EPSS score (FIRST)
0.8%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2022-2277 · Source: NVD
Affected components
| Component | CPE | Version range |
|---|---|---|
| Hitachi Energy MicroSCADA X SYS600 | cpe:2.3:a:hitachienergy:microscada_x_sys600:*:*:*:*:*:*:*:* | 10.2 to 10.3.1 inclusive (NVD, CVE record); fixed in 10.4 or later (CISA ICSA-22-272-01). The CISA advisory, which bundles five CVEs, also lists SYS600 9.4 FP2 Hotfix 4 and earlier, with an upgrade to 10.4 |
| Hitachi Energy Gateway Station (GWS) | — | 3.0.0.0, 3.1.0.0 and 3.2.0.0; fixed in 3.3.0.0 or later (CISA ICSA-23-059-02, Hitachi advisory 8DBD000116); not in NVD's CPE configuration |
What does this mean for affected devices?
Hitachi Energy, the CNA, describes CVE-2022-2277 as an improper input validation flaw in the ICCP stack of MicroSCADA X SYS600 "during the ICCP communication establishment" that "causes a denial-of-service when ICCP of SYS600 is request to forward any data item updates with timestamps too distant in the future to any remote ICCP system. By default, ICCP is not configured and not enabled." NVD's Primary score is CVSS v3.1 7.5 (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H), the same vector Hitachi Energy gives, so both score 7.5. NVD and the CVE record list CWE-1284, improper validation of specified quantity in input, a class whose MITRE definition names time among the quantities; a timestamp too far in the future is that case. CISA's advisory files it under CWE-20. The record was published on 2022-09-14 (NVD, CVE record).
Which Hitachi Energy products are affected?
The CVE record and NVD's CPE configuration name MicroSCADA X SYS600 versions 10.2, 10.2.1, 10.3 and 10.3.1 (NVD: 10.2 up to and including 10.3.1). CISA published the SYS600 advisory as ICSA-22-272-01 on 2022-09-29. It bundles CVE-2022-2277 with four other SYS600 flaws (CVE-2022-1778, CVE-2022-29490, CVE-2022-29492, CVE-2022-29922) and lists the affected versions for the whole advisory as SYS600 10.3.1 and earlier and SYS600 9.4 FP2 Hotfix 4 and earlier, so the 9.x line is in scope for the bundle even though the CVE record for this flaw starts at 10.2. The same ICCP stack flaw also appears in Hitachi Energy Gateway Station (GWS) 3.0.0.0, 3.1.0.0 and 3.2.0.0, per CISA ICSA-23-059-02 (Hitachi advisory 8DBD000116). The vector needs no privileges and no user interaction, but the flaw only matters where ICCP is configured and enabled, which is the inter-control-centre link. Our ICCP / TASE.2 security guide covers how those links are exposed and segmented.
How do you fix CVE-2022-2277?
Hitachi Energy's remediation, as published by CISA in the ICSA-22-272-01 CSAF document, is to update SYS600 10.x to at least version 10.4 and to upgrade SYS600 9.x to at least 10.4. For Gateway Station, ICSA-23-059-02 recommends at least GWS 3.3.0.0. Until the update is installed, the vendor's mitigation is "Do not enable ICCP if it is not used", together with the MicroSCADA X Cyber Security Deployment Guideline (1MRK511518), firewalling process control networks with a minimal set of open ports, and keeping control systems away from the internet. The vendor document is Hitachi Energy advisory 8DBD000106. For NERC CIP-012 entities, an availability bug in the ICCP endpoint matters as much as confidentiality on the link; see our CIP-012 control-centre communications guide. Another Hitachi Energy grid-automation flaw reachable over a telecontrol protocol is CVE-2023-6711 in the RTU500 IEC 60870-5-104 stack.
Is CVE-2022-2277 exploited?
CVE-2022-2277 is not in the CISA KEV catalog as of 2026-11-19 (catalog version 2026.11.18). CISA's advisory states that no known public exploits specifically target it. FIRST EPSS gives it 0.00785, the 56.8th percentile, in the 2026-11-18 dataset (CISA KEV, FIRST EPSS).
Evidence
- NVD: [email protected] Primary CVSS 3.1 7.5 AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H, CWE-1284; Hitachi Energy ([email protected]) Secondary 7.5 same vector, CWE-1284; CPE microscada_x_sys600 from 10.2 through 10.3.1 inclusive; published 2022-09-14; status Modified, read 2026-11-19. — NVD
- CVE record (CNA Hitachi Energy, state PUBLISHED, 2022-09-14): affected MicroSCADA X SYS600 10.2, 10.2.1, 10.3, 10.3.1; CVSS 3.1 7.5; CWE-1284; workaround: do not enable ICCP if it is not used. — CVE.org
- CISA ICSA-22-272-01 (2022-09-29), Hitachi Energy MicroSCADA Pro X SYS600: five CVEs incl. CVE-2022-2277 (CWE-20, 7.5); affected SYS600 10.3.1 and earlier and 9.4 FP2 Hotfix 4 and earlier; fix: 9.x upgrade and 10.x update to at least 10.4; do not enable ICCP if not used; follow 1MRK511518; no known public exploits specifically target this vulnerability; Hitachi advisory 8DBD000106. — CISA ICS advisory / CSAF
- CISA ICSA-23-059-02 (2023-03-06), Hitachi Energy Gateway Station: CVE-2022-2277 (7.5) affects GWS 3.0.0.0, 3.1.0.0, 3.2.0.0; update to at least GWS 3.3.0.0; Hitachi advisory 8DBD000116. — CISA ICS advisory / CSAF
- Not in the CISA KEV catalog, version 2026.11.18 (1,786 entries), checked 2026-11-19. — CISA KEV
- EPSS 0.00785, percentile 0.56794, dataset 2026-11-18, read 2026-11-19. — FIRST EPSS

Related advisories
Sources
- NVD
- CISA ICSA-22-272-01: Hitachi Energy MicroSCADA Pro X SYS600
- CISA CSAF: ICSA-22-272-01 (machine-readable advisory)
- CISA CSAF: ICSA-23-059-02 Hitachi Energy Gateway Station
- MITRE CWE-1284: Improper Validation of Specified Quantity in Input
- CVE.org record CVE-2022-2277 (CNA: Hitachi Energy)
- CISA KEV
- FIRST EPSS
Frequently asked questions
Which SYS600 version fixes CVE-2022-2277?
SYS600 10.4. Hitachi Energy recommends updating 10.x installations and upgrading 9.x installations to at least SYS600 version 10.4 (per CISA ICSA-22-272-01).
Is SYS600 vulnerable if ICCP is not used?
The flaw sits in the ICCP stack, and ICCP is not configured or enabled by default. Hitachi Energy's workaround is not to enable ICCP if it is not used (per the CVE.org record from Hitachi Energy and CISA ICSA-22-272-01).
Does CVE-2022-2277 affect other Hitachi Energy products?
Yes. Hitachi Energy Gateway Station 3.0.0.0, 3.1.0.0 and 3.2.0.0 carry the same ICCP stack flaw, fixed in GWS 3.3.0.0 or later (per CISA ICSA-23-059-02).
Is CVE-2022-2277 exploited in the wild?
It is not in the CISA KEV catalog as of 2026-11-19 (catalog version 2026.11.18), and CISA reported no known public exploits specifically targeting it. FIRST EPSS gives it 0.00785, the 56.8th percentile, in the 2026-11-18 dataset (per CISA KEV, CISA ICSA-22-272-01 and FIRST EPSS).