CVE-2022-30937 is a memory corruption flaw in the web server of the Siemens EN100 Ethernet module, the network card of SIPROTEC 4, SIPROTEC Compact, Reyrolle and SWT3000 devices: crafted HTTP requests to /txtrace crash it. NVD scores it 7.5. Only the IEC 61850 variant has a fix (V4.37); for the others Siemens advises disabling the web service.
Vulnerability summary
CVSS base score
7.5
High severity
EPSS score (FIRST)
1.3%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2022-30937 · Source: NVD
Affected components
| Component | CPE | Version range |
|---|---|---|
| Siemens EN100 Ethernet module IEC 61850 variant | cpe:2.3:o:siemens:en100_ethernet_module_iec_61850_firmware:*:*:*:*:*:*:*:* | all versions before V4.37; update to V4.37 or later (Siemens SSA-693555, CISA ICSA-22-167-05) |
| Siemens EN100 Ethernet module DNP3 IP variant | cpe:2.3:o:siemens:en100_ethernet_module_dnp3_firmware:-:*:*:*:*:*:*:* | all versions; Siemens lists no fix, apply the workarounds (Siemens SSA-693555) |
| Siemens EN100 Ethernet module IEC 104, Modbus TCP and PROFINET IO variants | cpe:2.3:o:siemens:en100_ethernet_module_modbus_tcp_firmware:-:*:*:*:*:*:*:* | all versions; Siemens lists no fix, apply the workarounds (Siemens SSA-693555) |
What does this mean for affected devices?
NVD's description, taken from Siemens: "Affected applications contains a memory corruption vulnerability while parsing specially crafted HTTP packets to /txtrace endpoint. This could allow an attacker to crash the affected application leading to a denial of service condition." NVD's Primary score is CVSS v3.1 7.5 (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H) with CWE-787. Siemens, the CNA, scores it 8.6 (AV:N/AC:L/PR:N/UI:N/S:C/C:N/I:N/A:H, scope changed) and classes it CWE-119. NVD's CPEs cover the DNP3, IEC 104, Modbus TCP and PROFINET IO firmware in all versions and the IEC 61850 firmware before 4.37. The record was published on 2022-06-14 (NVD).
Which Siemens products are affected?
Siemens SSA-693555 (version 1.0, 14 June 2022) describes the EN100 modules as the cards that provide "process communication on either IEC 61850, PROFINET IO, Modbus TCP, DNP3 IP or IEC 104 protocols via electrical/optical 100 Mbit interfaces on SIPROTEC 4, SIPROTEC Compact, Reyrolle and SWT3000 devices". It lists five firmware variants:
- IEC 61850 variant: all versions before V4.37. Fix: update to V4.37 or later.
- DNP3 IP, IEC 104, Modbus TCP and PROFINET IO variants: all versions. Siemens lists no fix for these and points to its workarounds.
CISA republished it as ICSA-22-167-05 (CSAF), listing multiple critical infrastructure sectors and worldwide deployment. Siemens credits Michael Messner of Siemens Energy with the report. The bug sits in the module's HTTP interface, not in the DNP3 or IEC 61850 stack, so the protocol variant only decides whether a fix exists.
How do you mitigate it?
For the IEC 61850 variant, install V4.37 or later. For every variant, Siemens lists three measures: disable the web service in the device configuration if it is not used, block access to ports 80/tcp and 443/tcp, for example with an external firewall, and apply its secure substation concept and defence in depth. Because the attack needs only network access to the web port, an EN100 card on a flat station bus is the case to fix first. Siemens rates the impact as denial of service of the affected application, and its general recommendations ask operators of critical power systems to check that redundant secondary protection schemes are in place.
Our DNP3 security guide explains why the communication module as a whole is the attack surface, the IEC 61850 guide covers substation networks, and CVE-2020-6996 and CVE-2013-2811 are flaws in DNP3 implementations themselves. CVE-2021-42376 is another memory-safety bug on Siemens network equipment, in BusyBox. The memory corruption fix guide covers the class.
CVE-2022-30937 is not in the CISA KEV catalog as of 2026-11-18 (catalog version 2026.11.17). FIRST EPSS gives it 0.0129, the 70.8th percentile, in the 2026-11-17 dataset (CISA KEV, FIRST EPSS).
Evidence
- NVD: memory corruption parsing specially crafted HTTP packets to /txtrace endpoint, DoS. NVD Primary CVSS v3.1 7.5 AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H; NVD CWE-787; Siemens CWE-119; CPEs en100 dnp3, iec_104, modbus_tcp, profinet_io firmware (all), iec_61850 firmware before 4.37; published 2022-06-14. — NVD
- Siemens SSA-693555 v1.0, 2022-06-14: CVSS 8.6 CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:N/I:N/A:H/E:P/RL:O/RC:C, CWE-119; IEC 61850 variant < V4.37 update to V4.37; DNP3 IP, IEC 104, Modbus TCP, PROFINET IO all versions no fix, see workarounds; workarounds: disable web service if not used, block 80/tcp and 443/tcp, secure substation concept; product description: EN100 modules on SIPROTEC 4, SIPROTEC Compact, Reyrolle and SWT3000 devices; acknowledgment Michael Messner, Siemens Energy. — Siemens ProductCERT
- CISA ICSA-22-167-05 (CSAF converted from Siemens ProductCERT): same products and remediations; critical infrastructure sectors Multiple; deployed worldwide; HQ Germany. — CISA CSAF
- CVE-2022-30937 is not in the CISA KEV catalog, version 2026.11.17 (1,782 entries), checked 2026-11-18. — CISA KEV
- EPSS 0.01294, percentile 0.70825, dataset 2026-11-17. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
Which EN100 variants have a fix for CVE-2022-30937?
Only the IEC 61850 variant, fixed in V4.37. For the DNP3 IP, IEC 104, Modbus TCP and PROFINET IO variants Siemens lists no fix (per Siemens SSA-693555 and CISA ICSA-22-167-05).
How can I protect an EN100 module that has no fix?
Disable the web service in the device configuration if you do not use it, block ports 80/tcp and 443/tcp with an external firewall, and follow Siemens' secure substation concept (per Siemens SSA-693555).
Why do NVD and Siemens give different scores for CVE-2022-30937?
NVD scores 7.5 with scope unchanged; Siemens scores 8.6 with scope changed, which in CVSS terms means the impact reaches beyond the vulnerable component. Both rate it as network-reachable without authentication or user interaction, with availability impact only (per NVD and Siemens SSA-693555).
Is CVE-2022-30937 in the CISA KEV catalog?
No, not as of 2026-11-18 (catalog version 2026.11.17). FIRST EPSS gives it 0.0129, the 70.8th percentile, in the 2026-11-17 dataset (per CISA KEV and FIRST EPSS).