Security Advisory

CVE-2013-0664: Modicon FactoryCast SOAP Modbus Passthrough

Last updated:
  • CVE-2013-0664

CVE-2013-0664 is a flaw in the FactoryCast web service of Schneider Electric Quantum, Modicon M340 and Premium PLC Ethernet modules: an authenticated user can wrap Modbus messages in SOAP HTTP POST requests and so take control of the PLC. NVD scores it 8.5 under CVSS v2. Schneider patched selected Quantum modules; for M340 and Premium, block HTTP from untrusted addresses.

Vulnerability summary

CVSS base score

8.5

High severity

EPSS score (FIRST)

3.9%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2013-0664 · Source: NVD

CVSS v3.1 severity rating scale: None 0.0, Low 0.1 to 3.9, Medium 4.0 to 6.9, High 7.0 to 8.9, Critical 9.0 to 10.0
How a CVSS v3.1 base score maps to a severity rating. Source: FIRST CVSS v3.1 specification, section 5.

Affected components

ComponentCPEVersion range
Schneider Electric Quantum Ethernet modules 140NOE77111 and 140NWM10000cpe:2.3:h:schneider-electric:modicon_quantum_plc:140noe77111:*:*:*:*:*:*:*Listed without version (NVD); Schneider patch for the HTTP and FTP service on selected Quantum modules adds an option to disable HTTP (CISA ICSA-13-077-01B)
Schneider Electric Modicon M340 BMXNOE0110xcpe:2.3:h:schneider-electric:modicon_m340:bmxnoe0110x:*:*:*:*:*:*:*Listed without version (NVD); no patch at the time of the CISA advisory, network mitigations only (CISA ICSA-13-077-01B)
Schneider Electric Modicon Premium TSXETY5103cpe:2.3:h:schneider-electric:modicon_premium:tsxety5103:*:*:*:*:*:*:*Listed without version (NVD); no patch at the time of the CISA advisory, network mitigations only (CISA ICSA-13-077-01B)

What does this mean for affected devices?

NVD's description: "The FactoryCast service on the Schneider Electric Quantum 140NOE77111 and 140NWM10000, M340 BMXNOE0110x, and Premium TSXETY5103 PLC modules allows remote authenticated users to send Modbus messages, and consequently execute arbitrary code, by embedding these messages in SOAP HTTP POST requests." NVD's Primary score is CVSS v2 8.5 (AV:N/AC:M/Au:S/C:C/I:C/A:C): network reachable, one authentication required. NVD records the weakness as NVD-CWE-noinfo, and its CPE configuration names the four module part numbers without a version (NVD). The CVE record, assigned by ICS-CERT and published on 2013-04-04, carries no CNA score.

What does CISA's advisory say?

CISA's ICSA-13-077-01B, "Schneider Electric PLCs Vulnerabilities (Update B)", covers this CVE and the cross-site request forgery CVE-2013-0663 in the same modules. The ICS Advisory Project index dates it to 2013-03-18, last updated 2019-06-25, and lists critical manufacturing, dams, energy, food and agriculture, government facilities, transportation, and water and wastewater. CISA's CSAF record, which is marked as extracted from unstructured text, gives this CVE CVSS v2 10.0 (AV:N/AC:L/Au:N/C:C/I:C/A:C) and CWE-287, and gives the 8.5 vector to CVE-2013-0663; this page follows NVD's 8.5 for CVE-2013-0664.

Modbus itself has no authentication, so a web service that relays Modbus requests gives anyone who gets through the web login the same control as an engineering station. Our Modbus protocol security guide and Modicon UMAS guide cover the protocol side; related Modicon flaws include CVE-2017-6034 (Modbus command replay) and CVE-2015-7937 (M340 web server overflow).

How do you fix or mitigate CVE-2013-0664?

Per CISA, Schneider Electric issued a patch for the HTTP and FTP service on selected Quantum modules that adds a setting to disable HTTP. For the Modicon M340 and Premium modules Schneider issued no patch but a vulnerability disclosure notification with two mitigations: do not connect the affected PLC modules to an untrusted network, and if a connection is needed, block all HTTP access to the module from untrusted IP addresses with a firewall, allowing HTTP only from known, secured workstations. Use strong, unique credentials for the FactoryCast web login too, since the attack needs a valid login.

CVE-2013-0664 is not in the CISA KEV catalog as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS gives it 0.03909, the 91st percentile, in the 2026-11-26 dataset (CISA KEV, FIRST EPSS).

Three signals on every advisory: CVSS says how severe the flaw is, EPSS gives the probability of exploitation in the wild in the next 30 days, and a CISA KEV listing means the flaw has been exploited in the wild
CVSS rates severity, EPSS estimates the likelihood of exploitation, and CISA KEV records exploitation seen in the wild. Source: FIRST EPSS; CISA KEV catalog.
How to fix this class of issueThis advisory's weakness class is Authentication bypass. Our practical guide covers how to detect, fix, verify and disclose it: How to fix authentication bypass in embedded firmware.
From advisory to verified fix in four steps: read the advisory, find the affected component in the firmware SBOM, apply the fixed version or vendor mitigation, then re-scan the image to confirm the vulnerable version is gone
Read the advisory, find the component in your firmware SBOM, apply the fix, then re-scan to confirm it.

Evidence

  • NVD: FactoryCast service on Quantum 140NOE77111 and 140NWM10000, M340 BMXNOE0110x and Premium TSXETY5103 lets remote authenticated users send Modbus messages embedded in SOAP HTTP POST requests and execute arbitrary code; Primary CVSS v2 8.5 AV:N/AC:M/Au:S/C:C/I:C/A:C; NVD-CWE-noinfo; CPEs without version; published 2013-04-04. — NVD
  • CVE record: assigner icscert, published 2013-04-04, no CNA metrics. — CVE Services (CVE.org record)
  • CISA ICSA-13-077-01B CSAF: Modicon M340, Quantum and Premium PLC modules; CVE-2013-0664 CVSS v2 10.0 CWE-287, CVE-2013-0663 8.5 CWE-352; patch for the HTTP and FTP service on selected Quantum PLC adds option to disable HTTP; no patch for M340 or Premium; mitigations: do not connect to untrusted network, block HTTP from untrusted IPs, allow HTTP only from known secured workstations; extracted from unstructured data. — CISA CSAF
  • ICS Advisory Project: ICSA-13-077-01B released 3/18/2013, last updated 6/25/2019; sectors critical manufacturing, dams, energy, food and agriculture, government facilities, transportation systems, water and wastewater. — ICS Advisory Project
  • CVE-2013-0664 is not in the CISA KEV catalog, version 2026.11.25 (1,805 entries), checked 2026-11-27. — CISA KEV
  • EPSS 0.03909, percentile 0.91056, dataset 2026-11-26. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. CISA ICSA-13-077-01B: Schneider Electric PLCs Vulnerabilities (Update B)
  3. CISA CSAF: icsa-13-077-01b.json
  4. ICS Advisory Project: CISA ICS advisory index
  5. CISA KEV
  6. FIRST EPSS

Frequently asked questions

Which Schneider Electric modules does CVE-2013-0664 affect?

Quantum 140NOE77111 and 140NWM10000, Modicon M340 BMXNOE0110x and Premium TSXETY5103 Ethernet modules running the FactoryCast service (per NVD and CISA ICSA-13-077-01B).

Does CVE-2013-0664 need a login?

Yes. NVD's CVSS v2 vector requires single authentication (Au:S): the attacker needs valid web credentials before embedding Modbus messages in SOAP requests, which is why NVD scores 8.5 rather than 10.0 (per NVD).

Is there a patch for M340 and Premium modules?

CISA's advisory lists a patch only for selected Quantum modules, which adds a setting to disable HTTP. For M340 and Premium, keep the modules off untrusted networks and allow HTTP only from known, secured workstations (per CISA ICSA-13-077-01B).

Is CVE-2013-0664 in the CISA KEV catalog?

No, not as of 2026-11-27 (catalog version 2026.11.25). FIRST EPSS gives it 0.03909, the 91st percentile, in the 2026-11-26 dataset, so it ranks above most CVEs for predicted exploitation even without a KEV listing (per CISA KEV and FIRST EPSS).