CVE-2015-7937 is a stack-based buffer overflow in the GoAhead web server embedded in Schneider Electric Modicon M340 PLC CPUs and Ethernet modules. A long password in HTTP Basic Authentication data can let a remote attacker run code on the module. NVD scores it 10.0 (CVSS v2); CISA lists firmware newer than January 16, 2016 as the fix.
Vulnerability summary
CVSS base score
10
Critical severity
EPSS score (FIRST)
7.3%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2015-7937 · Source: NVD

Affected components
| Component | CPE | Version range |
|---|---|---|
| Schneider Electric Modicon M340 PLC CPU and Ethernet modules (GoAhead web server) | cpe:2.3:h:schneider-electric:bmxnoe0100:-:*:*:*:*:*:*:* | CISA ICSA-15-351-01 and NVD CPEs: BMXNOC0401, BMXNOE0100, BMXNOE0100H, BMXNOE0110, BMXNOE0110H, BMXNOR0200, BMXNOR0200H, BMXPRA0100, BMXP342020, BMXP342020H, BMXP342030, BMXP3420302, BMXP3420302H (NVD lists hardware CPEs with no firmware range); fixed in firmware newer than January 16, 2016 |
What does this mean for affected devices?
NVD's description reads: "Stack-based buffer overflow in the GoAhead Web Server on Schneider Electric Modicon M340 PLC BMXNOx and BMXPx devices allows remote attackers to execute arbitrary code via a long password in HTTP Basic Authentication data." NVD's Primary score is CVSS v2 10.0 (AV:N/AC:L/Au:N/C:C/I:C/A:C) with CWE-119; NVD has no CVSS v3 score for it. ICS-CERT assigned the record with vendor and product n/a and no CNA score, and it was published on 2015-12-21 (NVD, CVE record).
Which Modicon M340 modules are affected?
CISA's advisory ICSA-15-351-01 (CSAF) lists thirteen Modicon M340 parts: the Ethernet communication modules BMXNOC0401, BMXNOE0100, BMXNOE0100H, BMXNOE0110, BMXNOE0110H, BMXNOR0200 and BMXNOR0200H, the BMXPRA0100 module, and the CPUs BMXP342020, BMXP342020H, BMXP342030, BMXP3420302 and BMXP3420302H. NVD's CPE list matches the same thirteen hardware parts without a firmware range, so the firmware date is what decides whether a unit is still exposed.
CISA scores the flaw differently from NVD: CVSS v3.0 7.5 (CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H) with CWE-121, stack-based buffer overflow. That vector counts only the availability impact, while NVD's v2 vector assumes complete loss of confidentiality, integrity and availability. Either way the attack needs no credentials: the overflow sits in the code that parses the login itself.
How do I fix CVE-2015-7937?
CISA's remediation is to install firmware newer than January 16, 2016 on the affected modules. Schneider Electric published its own notice as SEVD-2015-344-01, which NVD lists as a reference. As a temporary workaround Schneider Electric recommends blocking port 80, the module web server, with a firewall. CISA adds its usual practices: keep control system devices off the internet, put them behind firewalls separated from business networks, and use a VPN for remote access.
The same embedded web server appears in other device advisories: CVE-2017-17562 covers a later GoAhead CGI flaw, and the embedded web server guide explains how to find which GoAhead build a firmware image ships. Related Modicon pages include CVE-2017-6034 and CVE-2018-7845; the memory corruption fix guide covers bounds checks for parsers like this one.
CVE-2015-7937 is not in the CISA KEV catalog as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS gives it 0.0735, a percentile of 95.2, in the 2026-11-26 dataset (CISA KEV, FIRST EPSS).


Evidence
- NVD (read 2026-11-27): status Modified; published 2015-12-21; NVD Primary CVSS v2 10.0 AV:N/AC:L/Au:N/C:C/I:C/A:C; no v3 metric; CWE-119; CPEs for 13 Modicon M340 hardware parts (BMXNOC0401 ... BMXP3420302H) with no version range; references ICSA-15-351-01 and Schneider SEVD-2015-344-01. — NVD
- CISA ICSA-15-351-01 CSAF (read 2026-11-27): CVE-2015-7937 CWE-121, CVSS v3.0 7.5 CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H; 13 known-affected Modicon M340 parts; mitigation: install firmware newer than January 16, 2016; Schneider Electric recommends blocking port 80 using a firewall as a temporary workaround. — CISA ICSA-15-351-01
- CVE record (checked 2026-11-27): state PUBLISHED, CNA icscert; published 2015-12-21, affected n/a / n/a; no CNA CVSS. — CVE.org
- Not in the CISA KEV catalog, catalog version 2026.11.25, 1,805 entries, checked 2026-11-27. — CISA KEV
- EPSS 0.07351, percentile 0.95165, dataset 2026-11-26, read 2026-11-27. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
Which firmware fixes CVE-2015-7937?
CISA's advisory says to install firmware newer than January 16, 2016 on the affected Modicon M340 CPUs and Ethernet modules. NVD's CPE entries name the hardware parts only, so check the firmware date on each module rather than the part number alone.
Does an attacker need a password?
No. The overflow is triggered by an overlong password inside the HTTP Basic Authentication header, so it happens while the web server parses the login attempt, before any credential check succeeds.
What can I do if I cannot update the module yet?
Schneider Electric recommends blocking port 80 with a firewall as a temporary workaround. CISA also recommends keeping PLCs off the internet, separating control networks from business networks with firewalls, and using a VPN for remote access.
Is CVE-2015-7937 in the CISA KEV catalog?
No, not as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS rates it 0.0735 (percentile 95.2) in the 2026-11-26 dataset.