CVE-2012-6437: Rockwell EtherNet/IP Unsigned Firmware Upload

Last updated:
  • CVE-2012-6437

CVE-2012-6437 is a missing authentication check (CWE-287) in Rockwell Automation EtherNet/IP products: the Ethernet card of 1756-ENBT and similar modules, Logix controllers and MicroLogix 1100/1400 accepts a new firmware image from a remote user without proving who sent it. NVD scores it 10.0 under CVSS v2. Rockwell released patches in July 2012 and recommends the signed-firmware 1756-EN2T module.

Vulnerability summary

CVSS base score

10

Critical severity

EPSS score (FIRST)

10.5%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2012-6437 · Source: NVD

CVSS v3.1 severity rating scale: None 0.0, Low 0.1 to 3.9, Medium 4.0 to 6.9, High 7.0 to 8.9, Critical 9.0 to 10.0
How a CVSS v3.1 base score maps to a severity rating. Source: FIRST CVSS v3.1 specification, section 5.

Affected components

ComponentCPEVersion range
Rockwell Automation 1756-ENBT, 1756-EWEB, 1768-ENBT and 1768-EWEB communication modulescpe:2.3:h:rockwellautomation:1756-enbt:-:*:*:*:*:*:*:*All versions (CVE record, CISA ICSA-13-011-03); for the 1756-ENBT Rockwell pointed to the 1756-EN2T, which validates digital signatures from firmware Release 5.028 (CISA)
Rockwell Automation CompactLogix L32E/L35E, 1788-ENBT FLEXLogix adapter, 1794-AENTR FLEX I/O EtherNet/IP adaptercpe:2.3:h:rockwellautomation:1794-aentr_flex_i\/o_ethernet\/ip_adapter:-:*:*:*:*:*:*:*All versions (CVE record, CISA ICSA-13-011-03); Rockwell security patches of 18 July 2012 (CISA)
Rockwell Automation ControlLogix, CompactLogix, GuardLogix and SoftLogix controllerscpe:2.3:a:rockwellautomation:controllogix_controllers:*:*:*:*:*:*:*:*Release 18 and earlier; CompactLogix and SoftLogix 19 and earlier; ControlLogix and GuardLogix 20 and earlier (NVD, CVE record)
Rockwell Automation MicroLogix 1100 and 1400cpe:2.3:a:rockwellautomation:micrologix:*:*:*:*:*:*:*:*Listed as affected without a version (NVD, CVE record)

What does this mean for affected devices?

NVD's description: "The device does not properly authenticate users and the potential exists for a remote user to upload a new firmware image to the Ethernet card, whether it is a corrupt or legitimate firmware image." Success can cost availability, integrity and confidentiality and break communication with connected devices. NVD's Primary score is CVSS v2 10.0 (AV:N/AC:L/Au:N/C:C/I:C/A:C) with CWE-287 (Improper Authentication), the same score and weakness that ICS-CERT, the CNA, gives in the CVE record. CISA's ADP container adds a CVSS v3.1 9.8 (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H), which NVD shows as Secondary. The record was published on 2013-01-24 (NVD).

Which Rockwell products are affected?

CISA's ICSA-13-011-03, "Rockwell Automation ControlLogix PLC Vulnerabilities", lists the 1756-ENBT, 1756-EWEB, 1768-ENBT and 1768-EWEB communication modules, CompactLogix L32E and L35E controllers, the 1788-ENBT FLEXLogix adapter, the 1794-AENTR FLEX I/O EtherNet/IP adapter, ControlLogix, CompactLogix, GuardLogix and SoftLogix release 18 and earlier, CompactLogix and SoftLogix controllers 19 and earlier, ControlLogix and GuardLogix controllers 20 and earlier, and MicroLogix 1100 and 1400. NVD's CPE configuration follows that list. The ICS Advisory Project index dates the advisory to 2013-01-11, last updated 2019-02-13, for critical manufacturing, chemical, food and agriculture, and water and wastewater.

The same advisory carries seven sibling CVEs in the CIP and web stacks of these products: CVE-2012-6435, CVE-2012-6436, CVE-2012-6438, CVE-2012-6439, CVE-2012-6440, CVE-2012-6441 and CVE-2012-6442 (malformed or unauthorised CIP messages that fault the controller, web password replay and an information leak). They are not covered on this page. Our Rockwell Logix controller vulnerabilities guide tracks the later Logix CVEs, such as the ControlLogix EN2/EN3 module flaw CVE-2023-3595 and the Logix key bypass CVE-2021-22681.

How do you fix or mitigate CVE-2012-6437?

According to CISA's CSAF record of the advisory, Rockwell released security patches on 18 July 2012 for the issues in ICSA-13-011-03 and recommends updating to the newest firmware. For the unauthenticated firmware update itself, the advisory says Rockwell was still evaluating a digital signature check for the 1756-ENBT and advised moving to the 1756-EN2T EtherNet/IP module for ControlLogix, which "has been able to validate digital signatures since firmware Release 5.028". Rockwell's network mitigations in the same advisory also apply while modules are being replaced: block traffic to EtherNet/IP and CIP devices from outside the manufacturing zone on TCP and UDP ports 2222 and 44818, and consider a firewall that filters CIP messages. Our EtherNet/IP and CIP protocol security guide explains which CIP services a filter should allow. The CSAF record is marked as extracted from unstructured text and names CWE-284 for this CVE, where NVD and the CVE record say CWE-287.

CVE-2012-6437 is not in the CISA KEV catalog as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS gives it 0.10532, the 96th percentile, in the 2026-11-26 dataset (CISA KEV, FIRST EPSS).

Three signals on every advisory: CVSS says how severe the flaw is, EPSS gives the probability of exploitation in the wild in the next 30 days, and a CISA KEV listing means the flaw has been exploited in the wild
CVSS rates severity, EPSS estimates the likelihood of exploitation, and CISA KEV records exploitation seen in the wild. Source: FIRST EPSS; CISA KEV catalog.
How to fix this class of issueThis advisory's weakness class is Authentication bypass. Our practical guide covers how to detect, fix, verify and disclose it: How to fix authentication bypass in embedded firmware.
From advisory to verified fix in four steps: read the advisory, find the affected component in the firmware SBOM, apply the fixed version or vendor mitigation, then re-scan the image to confirm the vulnerable version is gone
Read the advisory, find the component in your firmware SBOM, apply the fix, then re-scan to confirm it.

Evidence

  • NVD: remote user can upload a new firmware image to the Ethernet card without proper authentication; Primary CVSS v2 10.0 AV:N/AC:L/Au:N/C:C/I:C/A:C; CWE-287; CISA ADP Secondary CVSS v3.1 9.8; CPEs for 1756-ENBT/EWEB, 1768-ENBT/EWEB, CompactLogix, ControlLogix <=18/20, MicroLogix 1100/1400; published 2013-01-24. — NVD
  • CVE record (assigner icscert, advisory ICSA-13-011-03): CVSS v2 10.0, CWE-287, affected product list; Rockwell security patches released July 18, 2012. — CVE Services (CVE.org record)
  • CISA ICSA-13-011-03 CSAF: product list; Rockwell patches of July 18, 2012; Rockwell evaluating a digital signature mechanism for 1756-ENBT, recommends 1756-EN2T which validates digital signatures since firmware Release 5.028; block TCP/UDP 2222 and 44818 from outside the Manufacturing Zone; CWE-284; extracted from unstructured data. — CISA CSAF
  • ICS Advisory Project: ICSA-13-011-03 released 1/11/2013, last updated 2/13/2019; sectors critical manufacturing, chemical, food and agriculture, water and wastewater. — ICS Advisory Project
  • CVE-2012-6437 is not in the CISA KEV catalog, version 2026.11.25 (1,805 entries), checked 2026-11-27. — CISA KEV
  • EPSS 0.10532, percentile 0.96497, dataset 2026-11-26. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. CISA ICSA-13-011-03: Rockwell Automation ControlLogix PLC Vulnerabilities
  3. CISA CSAF: icsa-13-011-03.json
  4. ICS Advisory Project: CISA ICS advisory index
  5. CISA KEV
  6. FIRST EPSS

Frequently asked questions

Which Rockwell products does CVE-2012-6437 affect?

The 1756-ENBT, 1756-EWEB, 1768-ENBT and 1768-EWEB modules, CompactLogix L32E/L35E, the 1788-ENBT and 1794-AENTR adapters, Logix controllers up to release 18, 19 or 20 depending on family, and MicroLogix 1100 and 1400 (per NVD and CISA ICSA-13-011-03).

What is the fix for CVE-2012-6437?

Apply the Rockwell security patches released on 18 July 2012 and the newest module firmware. For ControlLogix, Rockwell recommends the 1756-EN2T, which validates firmware signatures from Release 5.028, in place of the 1756-ENBT (per CISA ICSA-13-011-03).

How can you reduce exposure until modules are replaced?

Block EtherNet/IP and CIP traffic from outside the manufacturing zone on TCP and UDP ports 2222 and 44818, use a firewall that filters CIP messages, and limit who can reach the Ethernet modules at all (per the Rockwell mitigations in CISA ICSA-13-011-03).

Is CVE-2012-6437 in the CISA KEV catalog?

No, not as of 2026-11-27 (catalog version 2026.11.25). FIRST EPSS gives it 0.10532, the 96th percentile, in the 2026-11-26 dataset, so it ranks above most CVEs for predicted exploitation even without a KEV listing (per CISA KEV and FIRST EPSS).