Security Advisory

CVE-2012-4690: MicroLogix, SLC 500, PLC-5 Fault Generation

Last updated:
  • CVE-2012-4690

CVE-2012-4690 is a denial-of-service flaw in Rockwell Automation Allen-Bradley MicroLogix 1100, 1200, 1400 and 1500, SLC 500 and PLC-5 controllers: network messages that modify status bits can fault the controller when its status file is not set to Static. NVD scores it 7.1 (CVSS v2). Rockwell released MicroLogix firmware and configuration fixes for SLC 500 and PLC-5.

Vulnerability summary

CVSS base score

7.1

High severity

EPSS score (FIRST)

4.0%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2012-4690 · Source: NVD

CVSS v3.1 severity rating scale: None 0.0, Low 0.1 to 3.9, Medium 4.0 to 6.9, High 7.0 to 8.9, Critical 9.0 to 10.0
How a CVSS v3.1 base score maps to a severity rating. Source: FIRST CVSS v3.1 specification, section 5.

Affected components

ComponentCPEVersion range
Rockwell Automation Allen-Bradley MicroLogix 1100, 1200, 1400, 1500; SLC 500; PLC-5 controllerscpe:2.3:h:rockwellautomation:ab_micrologix_controller:1400:*:*:*:*:*:*:*CISA ICSA-12-342-01B: all versions; firmware releases available for MicroLogix 1100/1200/1400/1500 (Rockwell advisory 511407); SLC 500: set the Status file to Static; PLC-5: enable Passwords and Privileges

What does this mean for affected devices?

NVD's description reads: "Rockwell Automation Allen-Bradley MicroLogix controller 1100, 1200, 1400, and 1500; SLC 500 controller platform; and PLC-5 controller platform, when Static status is not enabled, allow remote attackers to cause a denial of service via messages that trigger modification of status bits." NVD's Primary score is CVSS v2 7.1 (AV:N/AC:M/Au:N/C:N/I:N/A:C) with CWE-16, configuration; there is no NVD v3 score. ICS-CERT assigned the record with vendor and product n/a and no CNA score; NVD published it on 2012-12-08 (NVD, CVE record).

What does CISA say?

CISA's advisory ICSA-12-342-01B (CSAF), "Rockwell Allen-Bradley MicroLogix, SLC 500, and PLC-5 Fault Generation Vulnerability (Update B)", lists all versions of the six controller families, classes the flaw as CWE-471, modification of assumed-immutable data, and gives the same CVSS v2 7.1. Update B records that on August 2, 2013 Rockwell updated its product security advisory 511407, "MicroLogix, SLC 500 and PLC5 Controller Vulnerability", and that "there are now firmware releases available for MicroLogix 1100 controller, MicroLogix 1200 controller, MicroLogix 1400 controller, and MicroLogix 1500 controller". CISA does not name the firmware numbers; they are in Rockwell's advisory 511407.

How do I fix it?

Update MicroLogix 1100, 1200, 1400 and 1500 controllers to the firmware named in Rockwell advisory 511407. For the other platforms, Rockwell recommends changing the controller to the non-vulnerable state: on SLC 500, set the Status file to "Static"; on PLC-5, enable the Passwords and Privileges feature. Rockwell also recommends blocking all EtherNet/IP and other CIP traffic from outside the Manufacturing Zone by restricting TCP and UDP ports 2222 and 44818 at a firewall, and restricting physical and electronic access to authorised staff.

The EtherNet/IP and CIP security guide explains why those ports matter, and the Rockwell Logix controller guide covers the larger Rockwell line. CVE-2017-16740 and CVE-2017-7903 are later MicroLogix flaws.

CVE-2012-4690 is not in the CISA KEV catalog as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS gives it 0.0405, a percentile of 91.4, in the 2026-11-26 dataset (CISA KEV, FIRST EPSS).

Three signals on every advisory: CVSS says how severe the flaw is, EPSS gives the probability of exploitation in the wild in the next 30 days, and a CISA KEV listing means the flaw has been exploited in the wild
CVSS rates severity, EPSS estimates the likelihood of exploitation, and CISA KEV records exploitation seen in the wild. Source: FIRST EPSS; CISA KEV catalog.
How to fix this class of issueNo dedicated SoftWSP guide covers this weakness class; the fix is usually the vendor patch or firmware update referenced above. Our related guide explains how to plan and verify it: NIST SP 800-40 Rev. 4: enterprise patch management planning, explained.
From advisory to verified fix in four steps: read the advisory, find the affected component in the firmware SBOM, apply the fixed version or vendor mitigation, then re-scan the image to confirm the vulnerable version is gone
Read the advisory, find the component in your firmware SBOM, apply the fix, then re-scan to confirm it.

Evidence

  • NVD (read 2026-11-27): status Modified; published 2012-12-08; NVD Primary CVSS v2 7.1 AV:N/AC:M/Au:N/C:N/I:N/A:C; no v3 metric; CWE-16; CPEs ab_micrologix_controller 1100, 1200, 1400, 1500, plc-5_controller, slc_500_controller; references ICSA-12-342-01, ICSA-12-342-01A and Rockwell answer 511407. — NVD
  • CISA ICSA-12-342-01B CSAF (read 2026-11-27): CVE-2012-4690, CWE-471, CVSS v2 7.1 AV:N/AC:M/Au:N/C:N/I:N/A:C; MicroLogix 1100/1200/1400/1500, SLC 500, PLC-5 all versions; remediation: on August 2, 2013 Rockwell updated advisory 511407; firmware releases available for MicroLogix 1100/1200/1400/1500; SLC-500 set Status file to Static; PLC-5 enable Passwords and Privileges; block EtherNet/IP and CIP traffic from outside the Manufacturing Zone on TCP and UDP ports 2222 and 44818. — CISA ICSA-12-342-01B
  • CISA ICSA-12-342-01B web page (read 2026-11-27): title Rockwell Allen-Bradley MicroLogix, SLC 500, and PLC-5 Fault Generation Vulnerability (Update B); firmware version numbers not named; directs users to Rockwell advisory 511407. — CISA ICSA-12-342-01B
  • CVE record (read 2026-11-27): state PUBLISHED, assigner icscert; published 2012-12-08; affected n/a / n/a; no CNA CVSS. — CVE.org
  • Not in the CISA KEV catalog, catalog version 2026.11.25, 1,805 entries, checked 2026-11-27. — CISA KEV
  • EPSS 0.04050, percentile 0.91407, dataset 2026-11-26, read 2026-11-27. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. CISA ICSA-12-342-01B: Rockwell Allen-Bradley MicroLogix, SLC 500, and PLC-5 Fault Generation Vulnerability (Update B)
  3. CISA ICSA-12-342-01B CSAF (machine-readable advisory)
  4. CVE record CVE-2012-4690 (CVE Services JSON)
  5. CISA KEV
  6. FIRST EPSS

Frequently asked questions

Is there a firmware fix for CVE-2012-4690?

For the MicroLogix 1100, 1200, 1400 and 1500, yes: CISA's Update B says Rockwell released firmware and lists it in Rockwell advisory 511407. For SLC 500 and PLC-5 the fix is a configuration change.

What configuration change protects SLC 500 and PLC-5?

Rockwell recommends setting the Status file to Static on SLC 500 controllers and enabling the Passwords and Privileges feature on PLC-5 controllers, which puts them in the non-vulnerable state.

Which network ports should be blocked?

Rockwell recommends blocking EtherNet/IP and other CIP traffic from outside the Manufacturing Zone by restricting TCP and UDP ports 2222 and 44818 at a firewall or similar security appliance.

Is CVE-2012-4690 in the CISA KEV catalog?

No, not as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS rates it 0.0405 (percentile 91.4) in the 2026-11-26 dataset.