CVE-2012-1800 is a stack-based buffer overflow in the Profinet DCP protocol stack of Siemens Scalance S602, S612 and S613 V2 industrial security firewalls with firmware before 2.3.0.3. A crafted DCP frame from the adjacent network makes the firewall unresponsive and drops its VPN tunnels. NVD scores it 6.1 (CVSS v2). Siemens fixed it by firmware update.
Vulnerability summary
CVSS base score
6.1
Medium severity
EPSS score (FIRST)
1.6%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2012-1800 · Source: NVD

Affected components
| Component | CPE | Version range |
|---|---|---|
| Siemens Scalance S602 V2, S612 V2, S613 V2 firmware | cpe:2.3:a:siemens:scalance_s_firmware:*:*:*:*:*:*:*:* | NVD: firmware before 2.3.0.3 (CPE up to and including 2.3.0, plus 2.1.0, 2.2.0); Siemens SSA-268149: fixed by firmware update |
| Siemens Scalance S602 V2 / S612 V2 / S613 V2 (hardware) | cpe:2.3:h:siemens:scalance_s612:v2:*:*:*:*:*:*:* | NVD hardware CPEs scalance_s602 v2, scalance_s612 v2, scalance_s613 v2 with vulnerable firmware |
What does this mean for affected devices?
NVD's description reads: "Stack-based buffer overflow in the Profinet DCP protocol implementation on the Siemens Scalance S Security Module firewall S602 V2, S612 V2, and S613 V2 with firmware before 2.3.0.3 allows remote attackers to cause a denial of service (device outage) or possibly execute arbitrary code via a crafted DCP frame." NVD's Primary score is CVSS v2 6.1 (AV:A/AC:L/Au:N/C:N/I:N/A:C) with CWE-119; there is no NVD v3 score. NVD's CPE data pairs Scalance S firmware up to 2.3.0 with the S602, S612 and S613 V2 hardware. CERT/CC assigned the record with vendor and product n/a and no CNA score; NVD published it on 2012-04-18 (NVD, CVE record).
What does Siemens say?
Siemens ProductCERT advisory SSA-268149 (V1.0, 2012-04-05) says the Scalance S DCP stack "does not handle unexpected input correctly": certain frames render the firewall unresponsive and established VPN tunnels are interrupted. The attack works only from an adjacent network, because DCP is a layer-2 protocol and its frames are not routed, and Scalance S fails secure, blocking all access to the internal network. Siemens gives the same base score of 6.1 and a temporal score of 4.8. The advisory also fixes a second flaw, missing brute-force protection on the web configuration interface, scored 10 base. Siemens credits Adam Hahn and Manimaran Govindarasu of Iowa State University.
CISA's advisory 12-102-05 (CSAF), "Siemens Scalance S Multiple Security Vulnerabilities", lists the same three V2 models, scores the flaw CVSS v2 6.1 and classifies it as CWE-121 (stack-based overflow) where NVD uses CWE-119.
How do I fix it?
Install the Scalance S firmware update that Siemens published for both flaws (version 2.3.0.3 or later, per NVD); SSA-268149 links it from Siemens industry support entry 59869684. Until the update, keep untrusted devices off the layer-2 segment the firewall's interfaces sit on, and use long, regularly changed web passwords against the companion brute-force issue.
CVE-2012-1802 is a web server overflow in Siemens SCALANCE X switches from the same month. The Siemens SCALANCE and RUGGEDCOM guide groups related advisories, and the PROFINET security guide explains DCP exposure.
CVE-2012-1800 is not in the CISA KEV catalog as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS gives it 0.016, a percentile of 76.1, in the 2026-11-27 dataset (CISA KEV, FIRST EPSS).


Evidence
- NVD (read 2026-11-28): status Modified; published 2012-04-18; NVD Primary CVSS v2 6.1 AV:A/AC:L/Au:N/C:N/I:N/A:C; no v3 metric; CWE-119; CPE scalance_s_firmware up to and including 2.3.0 plus 2.1.0, 2.2.0, with hardware scalance_s602/s612/s613 v2; description: firmware before 2.3.0.3. — NVD
- CISA ICSA-12-102-05 CSAF (read 2026-11-28): Scalance S602 V2, S612 V2, S613 V2; CVE-2012-1800 CWE-121, CVSS v2 6.1 AV:A/AC:L/Au:N/C:N/I:N/A:C; Siemens patch resolves both vulnerabilities; links SSA-268149 and firmware update support entry 59869684. — CISA ICSA-12-102-05
- CVE record (read 2026-11-28): state PUBLISHED, assigner certcc, vendor and product n/a, no CNA CVSS. — CVE.org
- Siemens SSA-268149 V1.0 (2012-04-05, read 2026-11-28): Scalance S602/S612/S613 V2; vulnerability #2 DCP stack, frames render firewall unresponsive and interrupt VPN tunnels; adjacent network only; fails secure; CVSS base 6.1, temporal 4.8 (AV:A/AC:L/Au:N/C:N/I:N/A:C/E:POC/RL:OF/RC:C); vulnerability #1 web brute force base 10; firmware fix at support entry 59869684; credit Adam Hahn and Manimaran Govindarasu, Iowa State University. — Siemens ProductCERT
- Not in the CISA KEV catalog, catalog version 2026.11.27, 1,808 entries, checked 2026-11-28. — CISA KEV
- EPSS 0.01598, percentile 0.76141, dataset 2026-11-27, read 2026-11-28. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
Which Scalance S models are affected?
Scalance S602 V2, S612 V2 and S613 V2 security modules with firmware before 2.3.0.3. Siemens fixed the flaw by firmware update (SSA-268149).
Can the flaw be reached from the internet?
No. DCP is a layer-2 Profinet protocol and its frames are not routed, so the attacker needs access to the adjacent network. NVD's vector is AV:A (adjacent network).
What happens to the protected network during an attack?
Siemens says Scalance S fails secure: the firewall becomes unresponsive, VPN tunnels drop, and all access to the internal network is blocked until the device recovers.
Is CVE-2012-1800 in the CISA KEV catalog?
No, not as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS rates it 0.016 (percentile 76.1) in the 2026-11-27 dataset.
Questions about this page?