CVE-2012-1802 is a buffer overflow in the web server of Siemens SCALANCE X industrial Ethernet switches: a malformed URL makes the switch reboot, cutting traffic for the machines behind it, and might allow code execution. NVD scores it 7.8 (CVSS v2). Siemens fixed it in firmware V3.7.2 for the X-300 family (X308-2M, X-300EEC, XR-300, X-300) and V3.7.1 for the X414-3E.
Vulnerability summary
CVSS base score
7.8
High severity
EPSS score (FIRST)
6.0%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2012-1802 · Source: NVD

Affected components
| Component | CPE | Version range |
|---|---|---|
| Siemens SCALANCE X-300 switch family: X308-2M, X-300EEC, XR-300, X-300 (incl. SIPLUS NET variants) | cpe:2.3:a:siemens:scalance_x-300_firmware:*:*:*:*:*:*:*:* | Siemens SSA-130874: all versions < V3.7.2; fixed in V3.7.2 (NVD CPEs: up to and including 3.7.0) |
| Siemens SCALANCE X414-3E | cpe:2.3:a:siemens:scalance_x414-3e_firmware:*:*:*:*:*:*:*:* | Siemens SSA-130874: all versions < V3.7.1; fixed in V3.7.1 (NVD CPEs: up to and including 3.7.0) |
What does this mean for affected devices?
NVD's description reads: "Buffer overflow in the embedded web server on the Siemens Scalance X Industrial Ethernet switch X414-3E before 3.7.1, X308-2M before 3.7.2, X-300EEC before 3.7.2, XR-300 before 3.7.2, and X-300 before 3.7.2 allows remote attackers to cause a denial of service (device reboot) or possibly execute arbitrary code via a malformed URL." NVD's Primary score is CVSS v2 7.8 (AV:N/AC:L/Au:N/C:N/I:N/A:C) with CWE-119; there is no NVD v3 score. CERT/CC assigned the record with vendor and product n/a and no CNA score; NVD published it on 2012-04-18 (NVD, CVE record).
What do Siemens and CISA say?
Siemens ProductCERT advisory SSA-130874 says the web server of the affected switches "does not sanitize URLs in HTTP requests properly"; a malformed URL makes the switch reboot, and while it restarts "no data can be transferred over the device". SCALANCE X switches connect PLCs and HMIs, so a reboot interrupts the cell. Version 1.3 of the advisory (2020-02-10) scores the flaw CVSS v3.1 6.8 (CVSS:3.1/AV:N/AC:L/PR:H/UI:N/S:C/C:N/I:N/A:H/E:P/RL:O/RC:C) with CWE-20 and notes that the attacker must be able to reach the administrative interface. Siemens' scorer therefore assumes high privileges, while NVD's v2 vector assumes no authentication. CISA's advisory ICSA-12-102-04 (CSAF), "Siemens Scalance X Buffer Overflow Vulnerability", gives CVSS v2 7.8 and credits Jürgen Bilberger of Daimler TSS GmbH.
How do I fix it?
Update the switch firmware: Siemens lists all versions before V3.7.2 of the SCALANCE X-300 switch family (including SIPLUS NET variants) and all versions before V3.7.1 of the SCALANCE X414-3E as affected, with those releases as the remediation. Note that NVD's CPE ranges stop at 3.7.0, so a scanner keyed only to NVD may not flag an X-300 on 3.7.1; use the Siemens ranges. Siemens has identified no specific workaround. Until the update is in, restrict who can reach the switch's web management interface, for example through a management VLAN or by turning off web management where it is not used.
CVE-2013-5944 is an authentication bypass in the web server of the related SCALANCE X-200 switches, and the SCALANCE and RUGGEDCOM network device guide collects later switch advisories. The memory corruption guide explains this bug class for firmware teams.
CVE-2012-1802 is not in the CISA KEV catalog as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS gives it 0.0605, a percentile of 94.1, in the 2026-11-26 dataset (CISA KEV, FIRST EPSS).


Evidence
- NVD (read 2026-11-27): status Modified; published 2012-04-18; NVD Primary CVSS v2 7.8 AV:N/AC:L/Au:N/C:N/I:N/A:C; no v3 metric; CWE-119; CPE firmware ranges up to and including 3.7.0 for scalance_x414-3e, x308-2m, x-300eec, xr-300, x-300. — NVD
- CISA ICSA-12-102-04 CSAF (read 2026-11-27): CVE-2012-1802, CWE-119, CVSS v2 7.8; Scalance X414-3E, X308-2M, X-300EEC, XR-300, X-300; Siemens firmware updates resolve the vulnerability; references SSA-130874. — CISA ICSA-12-102-04
- CISA ICSA-12-102-04 web page (read 2026-11-27): embedded web server does not properly sanitize URLs; CVSS v2 7.8; researcher Jürgen Bilberger, Daimler TSS GmbH. — CISA ICSA-12-102-04
- Siemens SSA-130874 V1.3 (published 2012-04-05, updated 2020-02-10, read 2026-11-27): X-300 family incl. SIPLUS NET < V3.7.2 update to V3.7.2; X414-3E < V3.7.1 update to V3.7.1; CVSS v3.1 6.8 CVSS:3.1/AV:N/AC:L/PR:H/UI:N/S:C/C:N/I:N/A:H/E:P/RL:O/RC:C; CWE-20; attacker must reach the administrative interface; no specific mitigations or workarounds identified. — Siemens ProductCERT SSA-130874
- CVE record (read 2026-11-27): state PUBLISHED, assigner certcc; affected n/a / n/a; no CNA CVSS. — CVE.org
- Not in the CISA KEV catalog, catalog version 2026.11.25, 1,805 entries, checked 2026-11-27. — CISA KEV
- EPSS 0.06052, percentile 0.94149, dataset 2026-11-26, read 2026-11-27. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
Which firmware fixes CVE-2012-1802?
V3.7.2 for the SCALANCE X-300 switch family (X308-2M, X-300EEC, XR-300, X-300, including SIPLUS NET variants) and V3.7.1 for the SCALANCE X414-3E. All earlier versions are affected.
Why do NVD and Siemens give different scores?
NVD's CVSS v2 7.8 assumes no authentication. Siemens' CVSS v3.1 6.8 assumes the attacker must reach the administrative interface with high privileges (PR:H) and adds a changed scope because a reboot cuts traffic for connected devices.
What happens to the plant if the switch is hit?
The switch reboots and, as Siemens puts it, no data can be transferred over the device while it restarts. PLCs and HMIs behind it lose network connectivity for that time.
Is CVE-2012-1802 in the CISA KEV catalog?
No, not as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS rates it 0.0605 (percentile 94.1) in the 2026-11-26 dataset.