**CVE-2012-0254** is a stack-based buffer overflow in the HSCDSPRenderDLL ActiveX control of Honeywell's HMIWeb Browser, the operator display client of Experion and of Honeywell's building management products. A remote attacker could use it to run code on the station. NVD scores it 7.5 on CVSS v2; Honeywell released fixes in 2012.
Vulnerability summary
CVSS base score
7.5
High severity
EPSS score (FIRST)
4.1%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2012-0254 · Source: NVD
Affected components
| Component | CPE | Version range |
|---|---|---|
| Honeywell Experion (HMIWeb Browser) | cpe:2.3:a:honeywell:experion:*:*:*:*:*:*:*:* | R2xx, R30x, R31x and R400.x (CISA ICSA-12-150-01; NVD CPE r200, r300, r310, r400.0). Fix: Honeywell Process Solutions notice SN 2012 03 09 01A |
| Honeywell Enterprise Building Manager | cpe:2.3:a:honeywell:enterprise_building_manager:*:*:*:*:*:*:*:* | R400 and R410.1 (CISA ICSA-12-150-01, NVD CPE). Fix: through the local Honeywell Building Solutions account manager |
| Honeywell SymmetrE | cpe:2.3:a:honeywell:symmetre:r410.1:*:*:*:*:*:*:* | R410.1 (CISA ICSA-12-150-01, NVD CPE). Fix: HMIWeb Browser update from Honeywell ECC, installed on the SymmetrE server and workstation clients |
What does this mean for affected devices?
NVD and the CVE record describe it as: "Stack-based buffer overflow in the HMIWeb Browser HSCDSPRenderDLL ActiveX control in Honeywell Process Solutions (HPS) Experion R2xx, R30x, R31x, and R400.x; Honeywell Building Solutions (HBS) Enterprise Building Manager R400 and R410.1; and Honeywell Environmental Combustion and Controls (ECC) SymmetrE R410.1 allows remote attackers to execute arbitrary code via unspecified vectors." CERT/CC is the CNA; the record was published on 2012-09-08 (NVD, CVE.org).
How severe is it, and who scored it?
NVD's only Primary metric is CVSS v2 7.5 (AV:N/AC:L/Au:N/C:P/I:P/A:P), the same score and vector as CISA's CSAF record. There is no CVSS v3 score. NVD maps it to CWE-787 (out-of-bounds write), CISA to CWE-121 (stack-based buffer overflow). Honeywell's product security table rates the advisory Medium.
Which products are affected, and what fixes it?
| Product | Affected | Fix (CISA ICSA-12-150-01) |
|---|---|---|
| Experion (Honeywell Process Solutions) | R2xx, R30x, R31x, R400.x | Notice SN 2012 03 09 01A, Security Vulnerability in HMIWeb Browser, links the fixes |
| Enterprise Building Manager (Honeywell Building Solutions) | R400, R410.1 | Contact the local Honeywell account manager |
| SymmetrE (Honeywell ECC) | R410.1 | HMIWeb Browser update on the SymmetrE server and workstation clients |
Because the flaw sits in an ActiveX control loaded by the browser, the attack path runs through the station's web browsing. CISA's advisory passes on Honeywell's extra precautions: do not use a Station node to browse the internet, and if a Station node is connected to the internet, do not use Station or Internet Explorer to browse, or limit it to trusted web sites. CISA also recommends keeping control system networks behind firewalls, separate from business networks.
Related Honeywell advisories: CVE-2014-9189, stack overflows in Experion PKS server modules, and CVE-2007-6483, a directory traversal in older Experion releases. Our Honeywell Experion and ControlEdge guide lists every Experion advisory with its fix, and the memory corruption fix guide covers this bug class.
CVE-2012-0254 is not in the CISA KEV catalog as of 2026-11-23 (catalog version 2026.11.20, 1,790 entries). FIRST EPSS gives it 0.04083, a percentile of 91.0, in the 2026-11-22 dataset (CISA KEV, FIRST EPSS).
Evidence
- NVD (read 2026-11-23): status Modified, published 2012-09-08; only Primary metric CVSS v2 7.5 AV:N/AC:L/Au:N/C:P/I:P/A:P, no CVSS v3; NVD CWE-787; CPEs experion r200, r300, r310, r400.0, enterprise_building_manager r400 and r410.1, symmetre r410.1. — NVD
- CVE record (checked 2026-11-23): state PUBLISHED, CNA CERT/CC, published 2012-09-08; product and CWE fields n/a; description names HMIWeb Browser HSCDSPRenderDLL ActiveX control in Experion R2xx, R30x, R31x, R400.x, EBM R400 and R410.1, SymmetrE R410.1. — CVE.org
- ICSA-12-150-01 CSAF: CWE-121, CVSS v2 7.5 AV:N/AC:L/Au:N/C:P/I:P/A:P; HPS fixes via notice SN 2012 03 09 01A Security Vulnerability in HMIWeb Browser; HBS customers contact local account manager; ECC SymmetrE customers install HMIWeb Browser update on server and workstation clients; do not use a Station node to browse the internet. — CISA CSAF ICSA-12-150-01
- Honeywell lists ICSA-12-150-01 HMIWeb Browser Buffer Overflow Vulnerability, CVE-2012-0254, severity Medium, published 2012-03-09 (read 2026-11-23). — Honeywell product security notices
- Not in the CISA KEV catalog, version 2026.11.20 (1,790 entries), checked 2026-11-23. — CISA KEV
- EPSS 0.04083, percentile 0.90969, dataset 2026-11-22, read 2026-11-23. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
Which Honeywell products does CVE-2012-0254 affect?
Experion R2xx, R30x, R31x and R400.x, Enterprise Building Manager R400 and R410.1, and SymmetrE R410.1, all through the HMIWeb Browser HSCDSPRenderDLL ActiveX control, per CISA ICSA-12-150-01 and NVD.
How do you fix CVE-2012-0254?
Experion sites apply the fixes linked from Honeywell notice SN 2012 03 09 01A; Enterprise Building Manager sites contact their Honeywell account manager; SymmetrE sites install the HMIWeb Browser update on the server and workstation clients, per CISA.
Why does CVE-2012-0254 have no CVSS v3 score?
It was scored in 2012, before CVSS v3 existed, and NVD has not added a v3 metric. Its only Primary score is CVSS v2 7.5, which matches CISA's advisory.
Is CVE-2012-0254 exploited in the wild?
It is not in the CISA KEV catalog as of 2026-11-23 (catalog version 2026.11.20). FIRST EPSS gives 0.04083, percentile 91.0, in the 2026-11-22 dataset.