Two operators at a control-room desk with a row of monitors, a laptop and keyboards

OT/ICS security

Yokogawa vulnerabilities: CENTUM VP and CS 3000, ProSafe-RS, STARDOM FCN/FCJ, Exaopc and FAST/TOOLS, fixed revisions and hardening

Last updated:

Yokogawa's CENTUM VP and CS 3000 distributed control systems, ProSafe-RS safety controllers, STARDOM FCN/FCJ controllers, Exaopc and FAST/TOOLS had no CVE in CISA's KEV catalog as of 2026-11-23, but their published flaws fall into five main families: memory corruption in control network communication, hard-coded or default credentials, missing authentication on engineering and batch functions, file and DLL tampering on Windows stations, and web server weaknesses. The newest controller-level set, Yokogawa's YSAR-26-0002 (last updated 19 June 2026), adds Vnet/IP firmware in FCS processor modules to CVE-2025-1924, which firmware R35 fixes.

The rest of this guide maps the products to their place in a plant network, explains the engineering and communication paths the advisories name, walks through the main CVEs by year with Yokogawa's fixed revisions, and ends with hardening, monitoring and a worked example. Every score below names its scorer: Yokogawa and CISA usually agree, but NVD often scores the same flaw higher.

Key takeaways

  • CISA lists critical manufacturing, energy, and food and agriculture as the deployment sectors for its 2024 and 2026 CENTUM and FAST/TOOLS advisories, with worldwide deployment and headquarters in Japan.
  • Yokogawa's YSAR-26-0002 was first published on 13 February 2026 and reached its 4th edition on 19 June 2026, after editions in April 2026 added affected products.
  • CVE-2018-8838 (YSAR-18-0001, ICSA-18-102-01): weak access control in the message management function lets a local attacker raise false alarms or block alarm displays.
  • The oldest reports matter because the products are still running in many plants and public exploit code exists.

Where do Yokogawa CENTUM, ProSafe-RS and STARDOM sit in OT networks?

CISA lists critical manufacturing, energy, and food and agriculture as the deployment sectors for its 2024 and 2026 CENTUM and FAST/TOOLS advisories, with worldwide deployment and headquarters in Japan. The product names in Yokogawa's YSAR reports and CISA's advisories fall into four groups:

Group Products named in advisories Typical place in the network
CENTUM DCS stations and servers CENTUM VP and CENTUM VP Entry Class, older CENTUM CS 3000 and CS 1000, the HIS operation and monitoring function, CAMS for HIS alarm management, the Automation Design (AD) server, B/M9000 on the same PC Supervisory level: Windows computers that run operation, engineering and alarm functions
CENTUM and ProSafe-RS controllers CENTUM VP/CS 3000 FCS controllers with CP31, CP33, CP345, CP401, CP451, CP461 and CP471 processor modules; ProSafe-RS SCS with SCP451, SCP461, S2CP471 and LICP471 Control and safety level, connected over the Vnet/IP control network
STARDOM controllers FCN-100, FCN-500, FCN-RTU and FCJ, engineered with Logic Designer and Resource Configurator Controller level, including remote sites (FCN-RTU)
Data, HMI and information servers Exaopc, FAST/TOOLS (packages RVSVRN, UNSVRN, HMIWEB, FTEES, HMIMOB), Collaborative Information Server (CI Server), PRM Between the control network and site or enterprise systems

YSAR-26-0002 describes the Vnet/IP Interface Package as the product that lets Yokogawa software on a virtualization platform communicate over Vnet/IP. That makes Vnet/IP the common thread: one flaw in its stack reaches CENTUM VP, ProSafe-RS, Exaopc, PRM and CI Server computers, plus controller firmware. ProSafe-RS appears in the Vnet/IP and 2022 reports, but its safety-function requirements belong in the IEC 61511 safety instrumented systems guide. For the zoning model behind the table, see the Purdue model guide.

How are CENTUM and STARDOM systems managed and reached?

The engineering and communication paths that the advisories name are the attack paths:

Path Products What the sources say
Vnet/IP control network CENTUM VP, ProSafe-RS, Exaopc, PRM, CI Server, FCS and SCS firmware Crafted packets can stop communication or terminate the stack process (YSAR-26-0002)
Inter-station data link (ADL) CENTUM FCS controllers A malformed packet may stop ADL communication (CVE-2022-33939)
Batch management process BKBCopyD.exe CENTUM with Batch Management Packages, Exaopc Listens on TCP port 20111 according to YSAR-14-0003; no authentication in old revisions (CVE-2014-5208)
CAMS for HIS and CAMS Log server CENTUM VP, Exaopc Unauthenticated packets, path traversal and DLL hijacking (2020, 2022 and 2024 reports)
Logic Designer connections STARDOM FCN/FCJ No authentication up to R4.01, so commands can stop or modify the application (CVE-2016-4860)
Maintenance homepage and HTTP service STARDOM FCN/FCJ Memory exhaustion and denial of service against the web maintenance functions (CVE-2018-17898, CVE-2023-5915)
Web server FAST/TOOLS, CI Server Fourteen 2026 web flaws, from weak TLS to path traversal (ICSA-26-041-01)

The only port number in the reports used here is TCP 20111 for the batch management process, from Yokogawa's YSAR-14-0003, which asks owners to block it from outside the control network and to allow it only between CENTUM systems with Batch Management Packages. Neither Yokogawa nor CISA gives a port for Vnet/IP, CAMS or the STARDOM maintenance homepage in these advisories, so confirm those from the product security guides or from a capture. The BOD 23-02 guide on internet-exposed management interfaces shows how to test exposure from outside instead of trusting the firewall rule base.

What are the 2026 Vnet/IP and CENTUM VP vulnerabilities?

Yokogawa's YSAR-26-0002 was first published on 13 February 2026 and reached its 4th edition on 19 June 2026, after editions in April 2026 added affected products. CISA's ICSA-26-057-09 of 26 February 2026 covers only the first edition's scope, the Vnet/IP Interface Package for CENTUM VP R6 (VP6C3300) and R7 (VP7C3300) up to R1.07.00.

CVE Weakness Yokogawa CVSS v3 NVD Primary CVSS v3.1 Effect
CVE-2025-1924 Out-of-bounds write (CWE-787) 6.9 8.2 Vnet/IP communication stops, or arbitrary programs run
CVE-2025-48019 Reachable assertion 5.3 6.5 Vnet/IP software stack process terminates
CVE-2025-48020 Reachable assertion 5.3 6.5 Same
CVE-2025-48021 Integer underflow 5.3 6.5 Same
CVE-2025-48022 Improper handling of length parameter inconsistency 5.3 6.5 Same
CVE-2025-48023 Reachable assertion 5.3 6.5 Same

Yokogawa also gives CVSS v4 scores of 6.0 for all six. The fixes from YSAR-26-0002 are:

  • Vnet/IP Interface Package: patch software R1.08.00 for R1.07.00 or earlier, for the CENTUM VP R6 and R7, ProSafe-RS, Exaopc, PRM and CI Server packages.
  • Vnet/IP firmware: R35 or later for CENTUM VP FCS processor modules CP461 and CP471, the ProSafe-RS SCS modules listed in the report and the VI702 Vnet/IP interface card.
  • Wide Area Communication Router module VI461: Vnet/IP firmware R15 or later.
  • Dual-redundant Platform for Computer (PC2CKM): patch R2.04.02.

Yokogawa says Vnet/IP firmware is not affected by the five stack-termination CVEs and "may not execute arbitrary programs" through CVE-2025-1924. As of 2026-11-23, NVD's CPE configuration for CVE-2025-1924 names only CENTUM VP and the Vnet/IP Interface Package, so a CPE-based scanner will miss the controller firmware that later editions of the report added.

The second 2026 CENTUM report, YSAR-26-0003 (CISA's ICSA-26-092-02), is CVE-2025-7741: a hard-coded password for the PROG user account used in CENTUM Authentication Mode. Yokogawa scores it CVSS v3 4.0 and v4 2.1, because PROG has the low S1 permission by default and the attacker already needs access to the HIS screen. CENTUM VP R7.01.00 gets patch R7.01.10; for R5.01.00 to R5.04.20 and R6.01.00 to R6.12.00 the only countermeasure is to switch to Windows Authentication Mode, which Yokogawa says requires engineering work. NVD lists the CVE as awaiting analysis with no Primary score as of 2026-11-23.

Which CENTUM station flaws came out between 2018 and 2024?

The station-side reports cluster around CAMS (alarm management), default credentials and file tampering on the Windows computers:

  • CVE-2018-8838 (YSAR-18-0001, ICSA-18-102-01): weak access control in the message management function lets a local attacker raise false alarms or block alarm displays. CISA and NVD score it 6.5. CENTUM VP R5.04.B2 or R6.04.00 and Exaopc R3.76.00 fix it; CENTUM CS 1000 and CS 3000 get no update.
  • CVE-2020-5608 and CVE-2020-5609 (YSAR-20-0001, ICSA-20-224-01): improper authentication and path traversal in CAMS for HIS, which let an unauthenticated attacker on the network send tampered packets or create and overwrite files and run commands. CISA scores both 8.1 (adjacent network); NVD's Primary score is 9.8. Fixes are patch R5.04.D1 for CENTUM VP R5, patch R6.07.11 for R6.01.00 to R6.07.00, and Exaopc R3.78.10.
  • CVE-2022-21194 and CVE-2022-23402 (YSAR-22-0001, ICSA-22-083-01): a default password on the OS account created at installation, and hard-coded credentials in the CAMS server application that let a malformed packet suppress alarms. Yokogawa and CISA score them 7.1 and 7.8; NVD says 9.8 for both. CENTUM VP R6.09.00 and Exaopc R3.80.00 fix them, and Yokogawa also asks owners to change the initial passwords of predefined user accounts, using the same password across the system.
  • CVE-2022-27188 and CVE-2022-26034 (YSAR-22-0004, ICSA-22-123-01): tampered Graphic Builder files can run programs on an HIS (CISA 6.1), and the Automation Design server protocol lacks proper authentication (CISA 6.4, NVD 9.1). CENTUM VP R6.09.00 with patch R6.09.04 and ProSafe-RS R4.07.02 or later are the fixes.
  • CVE-2024-5650 (YSAR-24-0002, ICSA-24-172-01): DLL hijacking in the CENTUM CAMS Log server lets someone who can reach a shared folder replace a DLL and run programs as SYSTEM. Yokogawa scores it 8.5. CENTUM VP R6.11.12 or later fixes it; CS 3000 and CENTUM VP R4 and R5 get no patch. NVD has deferred it with no Primary score as of 2026-11-23.

Several of these need a foothold on a station or file share first, which is why Yokogawa's countermeasures pair patches with account and share hygiene. The hard-coded credentials fix guide explains why a default password that the installer is told to change still ends up as a CVE.

What did the 2014 and 2015 CENTUM CS 3000 advisories fix?

The oldest reports matter because the products are still running in many plants and public exploit code exists. YSAR-14-0001 covers four buffer overflows in CENTUM CS 3000 R3.09.50 and earlier, with matching CISA advisory ICSA-14-070-01A:

CVE Process NVD Primary CVSS v2
CVE-2014-0781 Operation logging process BKCLogSvr.exe (heap overflow via UDP) 9.3
CVE-2014-0783 Project equalization process BKHOdeq.exe 9.0
CVE-2014-0784 Batch management process BKBCopyD.exe 8.3
CVE-2014-0782 Simulator management process BKESimmgr.exe in the Expanded Test Functions 8.3

Patch R3.09.79 for CS 3000 R3.09.50, R4.03.55 for CENTUM VP R4.03.00 and R5.03.51 for R5.03.20 fix all four and the YSAR-14-0002 flaw. That flaw, CVE-2014-3888 (NVD 8.3), is a stack overflow in BKFSim_vhfd.exe when the Expanded Test Functions are in use. CVE-2014-5208 (YSAR-14-0003, NVD 7.5) is the missing authentication in BKBCopyD.exe on TCP 20111 that lets an attacker read and write files. CVE-2015-5626 (YSAR-15-0003, ICSA-15-253-01) is a stack overflow in the control network communication process of CENTUM, ProSafe-RS, Exaopc, STARDOM VDS, FAST/TOOLS and other products; NVD's Primary CVSS v3.1 score is 9.8. YSAR-15-0003 lists CENTUM VP up to R6.02.00 as affected where CISA's CSAF says R5.04.20, so use the Yokogawa report for scoping. Memory-safety fixes like these are covered in the memory corruption fix guide.

Which STARDOM FCN/FCJ vulnerabilities still matter?

STARDOM advisories run from 2016 to 2023, and several have no firmware fix, only the controller's packet filter:

CVE Report Weakness Score (scorer) Yokogawa countermeasure
CVE-2016-4860 YSAR-16-0002 No authentication for Logic Designer connections, R1.01 to R4.01 7.3 (CISA, NVD) R4.02
CVE-2018-10592 YSAR-18-0004 Hard-coded account and password, R4.02 and earlier 9.8 (CISA, NVD) R4.10 or later
CVE-2018-17900 YSAR-18-0007 Credential management lets an attacker obtain remote-access credentials 9.4 (Yokogawa, CISA); NVD 9.8 Packet filter, protect traffic from capture
CVE-2018-17902 YSAR-18-0007 Session handling causes denial of service to remote management 5.3 (Yokogawa, CISA, NVD) Packet filter
CVE-2018-17896 YSAR-18-0007 Hard-coded credential in the maintenance function, usable only during maintenance work 8.3 (Yokogawa, CISA); NVD 8.1 Packet filter
CVE-2018-17898 YSAR-18-0007 Memory exhaustion through the HTTP service 5.3 (Yokogawa, CISA); NVD 7.5 R4.20 or later
CVE-2022-29519 YSAR-22-0007 Cleartext transmission, R1.01 to R4.31 4.8 (Yokogawa, CISA); NVD 7.5 Packet filter, protect traffic from capture
CVE-2022-30997 YSAR-22-0007 Hard-coded credentials on dual-redundant CPU modules, R4.10 to R4.31 6.3 (Yokogawa, CISA); NVD 7.2 Packet filter, protect traffic from capture
CVE-2023-5915 YSAR-23-0003 Crafted packet blocks the maintenance homepage, R1.01 to R4.31 5.3 (Yokogawa, CISA, NVD) Packet filter; Yokogawa provides no patch

The packet filter function needs FCN/FCJ basic software R4.20 or later, according to YSAR-22-0007 and YSAR-23-0003. The 2022 STARDOM pair came out of Forescout's OT:ICEFALL research, which JVNVU#95452299 from JPCERT/CC links. A separate report, YSAR-22-0009, points to CISA's ICSA-22-172-04 on Phoenix Contact ProConOS and MULTIPROG for a flaw in a module used in STARDOM FCN/FCJ R1.01 to R4.31 and asks owners to enable both the packet filter and Resource Configurator's Project Protection (R4.02 or later), which blocks project downloads from Logic Designer.

YSAR-23-0003 notes that during the CVE-2023-5915 attack the controller keeps running its control application; only the maintenance functions are unavailable. That distinction matters for incident triage but not for exposure: every STARDOM entry above is reachable by anyone who can send packets to the controller.

What about CENTUM FCS controllers and FAST/TOOLS?

CVE-2022-33939 (YSAR-22-0008, ICSA-22-228-01, JVNVU#94343729) is a denial of service in CENTUM VP/CS 3000 FCS controllers: a malformed packet may stop ADL communication between stations. Yokogawa and CISA score it 6.5; NVD says 7.5. For CP401 and CP451 processor modules, CENTUM VP R5.04.20 with patch R5.04.78 or R6.03.10 or later fixes it. CP31, CP33 and CP345 modules in CENTUM CS 3000 and CENTUM VP R4 get no patch because those products are past end of support.

FAST/TOOLS R9.01 to R10.04 has fourteen web server CVEs in YSAR-26-0001 and CISA's ICSA-26-041-01. The two most serious are CVE-2025-66597, support for weak cryptographic algorithms that could let an attacker decrypt web traffic (Yokogawa CVSS v3 8.2, NVD 7.5), and CVE-2025-66608, insufficient URL validation that lets crafted requests read files from the web server (Yokogawa 7.5, NVD 7.5). The rest cover CSRF, missing HSTS, verbose error pages, path disclosure and similar web hardening issues. Yokogawa's fix is to move to R10.04, apply R10.04 SP3 and then patch CS_e12787; the 2nd edition of 23 June 2026 adds CI Server R1.01 to R1.04, fixed in R1.05. CISA's text lists the SP3 and CS_e12787 steps in the opposite order, so follow the Yokogawa report.

Are Yokogawa vulnerabilities exploited in the wild?

No Yokogawa CVE is in the CISA KEV catalog as of 2026-11-23 (catalog version 2026.11.20, 1,790 entries, no Yokogawa vendor entry). CISA's 2018, 2020 and 2022 STARDOM and CENTUM advisories say no known public exploits specifically target the vulnerabilities, and CISA's 2026 CENTUM VP advisories (ICSA-26-057-09 and ICSA-26-092-02) record an SSVC exploitation value of "none".

Public exploit code does exist for the 2014 set. The Rapid7 Metasploit Framework has exploit modules for CVE-2014-0782, CVE-2014-0783, CVE-2014-0784 and CVE-2014-3888, such as the BKHOdeq.exe module, and an auxiliary client for CVE-2014-5208. That fits the FIRST EPSS scores dated 2026-11-22, the latest as of 2026-11-23:

CVE Product EPSS Percentile
CVE-2014-0783 CENTUM CS 3000 BKHOdeq.exe 0.67618 0.993
CVE-2014-3888 CENTUM BKFSim_vhfd.exe 0.62312 0.992
CVE-2014-0782 CENTUM BKESimmgr.exe 0.56688 0.991
CVE-2014-0784 CENTUM CS 3000 BKBCopyD.exe 0.35900 0.985
CVE-2014-0781 CENTUM CS 3000 BKCLogSvr.exe 0.26299 0.980
CVE-2014-5208 CENTUM and Exaopc BKBCopyD.exe 0.22543 0.978
CVE-2018-10592 STARDOM FCN/FCJ 0.06852 0.942
CVE-2015-5626 CENTUM and other products 0.04173 0.912
CVE-2016-4860 STARDOM FCN/FCJ 0.02649 0.860
CVE-2020-5609 CAMS for HIS 0.02065 0.819
CVE-2025-1924 Vnet/IP 0.00202 0.101

High EPSS on the 2014 flaws reflects ready-made exploit modules, and CS 3000 R3.09.50 is the last revision those patches apply to. The 2025 Vnet/IP flaws score low, but EPSS predicts exploitation activity across the internet, not how reachable a controller is once someone is on the control network. The KEV and EPSS prioritization guide explains how to rank by reachability first.

How should CENTUM, ProSafe-RS and STARDOM systems be hardened?

The steps below come from Yokogawa's countermeasures and CISA's recommended practices:

  1. Apply the Vnet/IP fixes everywhere the code runsInstall Vnet/IP Interface Package R1.08.00 on virtualized CENTUM VP, ProSafe-RS, Exaopc, PRM and CI Server, and update Vnet/IP firmware in CP461 and CP471 FCS modules, ProSafe-RS SCS modules and VI702 cards to R35 or later.
  2. Bring CENTUM VP to a current revisionR6.11.12 or later covers the 2024 CAMS Log server fix and is later than the R6.09.00 and R6.09.04 fix levels for the 2022 reports; R7.01.00 needs patch R7.01.10 for CVE-2025-7741.
  3. Switch to Windows Authentication Modewhere CENTUM Authentication Mode is still in use on R5 or R6, as YSAR-26-0003 asks for CVE-2025-7741.
  4. Change every default passwordYokogawa's 2022 report asks owners to change the OS account password set at installation and the initial passwords of predefined CENTUM VP and Exaopc user accounts.
  5. Turn on the STARDOM packet filterMove FCN/FCJ basic software to R4.20 or later, allow only trusted hosts, and enable Resource Configurator Project Protection.
  6. Update FAST/TOOLS to R10.04 SP3 with CS_e12787, and CI Server to R1.05.
  7. Retire CENTUM CS 3000 and CENTUM VP R4Yokogawa's reports from 2020 to 2024 give no patch for them and recommend upgrading to the latest CENTUM VP.
  8. Firewall the control networkYokogawa asks for a firewall between the external network and the control system network and for preventing unapproved devices from connecting. CISA asks owners to keep control system devices off the internet, isolate them from business networks and use VPNs for remote access.

Plan these updates through a change process such as the one in the IEC 62443-2-3 patch management guide, since Yokogawa notes that work its service personnel do to apply patches or upgrade revisions is charged to the customer.

How do you check which revision a Yokogawa system runs?

Yokogawa fixes arrive as revisions, patch software numbers and firmware levels, so record each one:

  1. Record CENTUM VP revision and patches per station"R6" alone does not show whether R6.07.11, R6.09.04 or R6.11.12 is installed, and those decide which reports apply.
  2. Record controller processor modules and Vnet/IP firmwareCP401 and CP451 have different fixes from CP461 and CP471, and YSAR-26-0002 tracks firmware revisions such as R33 or R35, not the CENTUM release.
  3. Record STARDOM basic software and CPU configurationCVE-2022-30997 only applies to dual-redundant CPU modules, and the packet filter needs R4.20.
  4. Record which optional packages are installedBatch Management Packages, the Expanded Test Functions, CAMS for HIS and the Graphic Builder each pulled in a separate report.
  5. Do not rely on CPE matching aloneAs of 2026-11-23, NVD has no CPE configuration for CVE-2024-5650 or CVE-2025-7741, and its CVE-2025-1924 configuration misses the controller firmware. Read the YSAR tables.

How do you monitor Yokogawa control networks?

Start with a baseline of which hosts talk to each station and controller, and on which ports, then alert on changes:

  • New hosts on the Vnet/IP or control network segment, since every Vnet/IP CVE needs crafted packets from an adjacent host.
  • Connections to TCP 20111 from anything other than CENTUM stations with Batch Management Packages, which fits CVE-2014-5208 and the YSAR-14-0003 firewall rule.
  • Logic Designer or web connections to STARDOM controllers from outside the engineering subnet, which fits CVE-2016-4860, CVE-2018-17900 and CVE-2023-5915.
  • File-share access to HIS and CAMS computers from unexpected hosts, which fits CVE-2024-5650 and CVE-2022-27188.
  • Web access to FAST/TOOLS from outside the operations network, which fits the ICSA-26-041-01 web flaws.

Flow records show who connected to which port and when, not which Vnet/IP message was sent. Map alerts to MITRE ATT&CK for ICS techniques such as remote services and program download.

Worked example: what does a review of a refinery unit find?

Synthetic example, not a real site. A refinery unit runs CENTUM VP R6.08 with CP451 controllers, a virtualized Exaopc server, four STARDOM FCN-RTU controllers at a tank farm and FAST/TOOLS R10.04 SP2 for the site overview.

Observation Why it matters Action
CENTUM VP stations on R6.08.00 Before R6.09.00, so the 2022 CAMS and default-password reports (CVE-2022-21194, CVE-2022-23402) apply, as do CVE-2024-5650 and CVE-2025-7741 Update to R6.11.12 or later; switch to Windows Authentication Mode
Exaopc on a virtualization host with Vnet/IP Interface Package R1.07.00 In scope of CVE-2025-1924 and CVE-2025-48019 to 48023 Apply R1.08.00
STARDOM FCN-RTU on R4.10, dual-redundant CPUs, packet filter off Hard-coded credential CVE-2022-30997 and the 2018 credential flaws are open Move to R4.20 or later, enable the packet filter, enable Project Protection
TCP 20111 open from the business network to the batch station The YSAR-14-0003 firewall rule is not in place Block it at the boundary; allow only between batch stations
FAST/TOOLS on R10.04 SP2 Below the CS_e12787 fix for the 2026 web flaws Apply SP3, then CS_e12787
One CENTUM CS 3000 engineering PC kept for an old unit End of support; no patch for 2018 to 2024 reports, high EPSS 2014 flaws if below R3.09.79 Plan migration to CENTUM VP and isolate it meanwhile

Where does passive monitoring fit in a Yokogawa review?

A passive capture shows who talks to stations and controllers without logging in to anything. SoftWSP's OT Snapshot reads Zeek and ICSNPP logs from a mirror-port recording and builds a host-by-port inventory at connection level, including hosts using TCP 20111, web ports and file sharing, and lists remote-access sessions that cross from outside the private address range. It does not decode Vnet/IP, CAMS or STARDOM engineering messages or read CENTUM revisions from traffic, so those come from the asset list. For that list, Device & Firmware Security identifies components and versions and matches them against NVD, CISA KEV, FIRST EPSS and CISA ICS advisories. An engineer reviews every AI-drafted, cited report before it is sent.

What are the common pitfalls?

  • Patching CENTUM VP stations but not the Vnet/IP firmware in FCS and SCS processor modules, which YSAR-26-0002 added in later editions.
  • Reading CISA's first-edition advisory as the full scope, when Yokogawa's YSAR has been updated since.
  • Treating the STARDOM packet filter as optional, when it is the only countermeasure for six of the STARDOM CVEs above.
  • Assuming one score: NVD rates CVE-2020-5608 and CVE-2022-21194 at 9.8 where Yokogawa and CISA say 8.1 and 7.1.
  • Keeping CENTUM CS 3000 on the network because it still runs, when the 2014 flaws have public exploit modules.
  • Leaving CENTUM Authentication Mode or default OS account passwords in place after an upgrade.

This guide draws on Yokogawa Security Advisory Reports YSAR-14-0001 to YSAR-26-0003, CISA ICS advisories ICSA-14-070-01A, ICSA-15-253-01, ICSA-16-259-01, ICSA-18-102-01, ICSA-18-151-03, ICSA-20-224-01, ICSA-22-083-01, ICSA-22-123-01, ICSA-22-174-01, ICSA-22-228-01, ICSA-23-334-02, ICSA-24-172-01, ICSA-26-041-01, ICSA-26-057-09 and ICSA-26-092-02 and their CSAF records, JPCERT/CC JVN entries, NVD and CVE.org records, CISA KEV and FIRST EPSS, all checked as of 2026-11-23.

Put this guide to work

Frequently asked questions

What are the 2026 Vnet/IP vulnerabilities in CENTUM VP?

Yokogawa's YSAR-26-0002, first published on 13 February 2026 and last updated on 19 June 2026, covers six CVEs found by Dmitry Sklyar and Demid Uzenkov of Positive Technologies. CVE-2025-1924 is an out-of-bounds write that can stop Vnet/IP communication or run arbitrary programs, scored CVSS v3 6.9 by Yokogawa and 8.2 by NVD. CVE-2025-48019 to CVE-2025-48023 are reachable assertion, integer underflow and length-handling flaws that can terminate the Vnet/IP software stack process, scored 5.3 by Yokogawa and 6.5 by NVD. CISA published the first edition as ICSA-26-057-09 for the Vnet/IP Interface Package for CENTUM VP R6 and R7. Later editions of the Yokogawa report add the Vnet/IP firmware in CENTUM VP FCS processor modules CP461 and CP471, ProSafe-RS SCS processor modules, the VI702 Vnet/IP interface card and the Wide Area Communication Router module.

Which fix does Yokogawa give for the Vnet/IP flaws?

YSAR-26-0002 lists Vnet/IP Interface Package R1.08.00 (patch software for R1.07.00 or earlier), Vnet/IP firmware R35 or later for FCS and SCS processor modules and the VI702 card, R15 or later for the Wide Area Communication Router module (VI461), and patch R2.04.02 for the Dual-redundant Platform for Computer. Yokogawa says Vnet/IP firmware is not affected by the five stack-termination CVEs, only by CVE-2025-1924.

Are STARDOM FCN/FCJ controllers still exposed to hard-coded credentials?

Partly, and that depends on configuration. YSAR-18-0004 says upgrading the FCN/FCJ basic software to R4.10 or later corrects the hard-coded password in CVE-2018-10592. For CVE-2022-30997, a hard-coded credential that works only on dual-redundant CPU modules running R4.10 to R4.31, YSAR-22-0007 gives no fixed revision; Yokogawa asks owners to use the controller's packet filter function (R4.20 or later) to allow only trusted hosts and to keep traffic from being captured. The same packet filter advice covers the 2018 maintenance-function credential CVE-2018-17896.

Are any Yokogawa CENTUM or STARDOM vulnerabilities in the CISA KEV catalog?

No. As of 2026-11-23, CISA's Known Exploited Vulnerabilities catalog (version 2026.11.20, 1,790 entries) has no Yokogawa entry. The 2014 CENTUM CS 3000 flaws still carry the highest FIRST EPSS scores of the CVEs in this guide, led by CVE-2014-0783 at 0.676, and public Metasploit modules exist for CVE-2014-0782, CVE-2014-0783, CVE-2014-0784, CVE-2014-3888 and CVE-2014-5208.

Where does Yokogawa publish its security advisories?

Yokogawa publishes Yokogawa Security Advisory Reports (YSAR) as PDFs, listed by year on its security advisory report list page. Each report names affected revisions, fixed revisions or patch numbers, CVSS scores and a support contact. JPCERT/CC publishes Japanese JVN entries for many of them, and CISA republishes a subset as ICS advisories with CSAF files on GitHub.

Sources

  1. Yokogawa: Security Advisory Report list (YSAR)
  2. Yokogawa YSAR-26-0002: Vulnerabilities in Vnet/IP related products
  3. Yokogawa YSAR-26-0003: Hardcoded Password Vulnerability in CENTUM
  4. Yokogawa YSAR-26-0001: Vulnerabilities in FAST/TOOLS and CI Server
  5. Yokogawa YSAR-24-0002: DLL Hijacking Vulnerability in CENTUM CAMS Log server
  6. Yokogawa YSAR-23-0003: Denial-of-Service Vulnerability in STARDOM
  7. Yokogawa YSAR-22-0009: Vulnerability in STARDOM controller
  8. Yokogawa YSAR-22-0008: DoS vulnerability in CENTUM controller FCS
  9. Yokogawa YSAR-22-0007: Vulnerabilities in STARDOM
  10. Yokogawa YSAR-22-0004: Vulnerabilities in CENTUM and ProSafe-RS
  11. Yokogawa YSAR-22-0001: Vulnerabilities in CENTUM and Exaopc
  12. Yokogawa YSAR-20-0001: Vulnerabilities in CAMS for HIS
  13. Yokogawa YSAR-18-0007: Vulnerabilities in STARDOM controllers
  14. Yokogawa YSAR-18-0004: Vulnerability of hardcoded password in STARDOM controllers
  15. Yokogawa YSAR-18-0001: Faked and blocked alarms vulnerability in CENTUM and Exaopc
  16. Yokogawa YSAR-16-0002: Arbitrary command execution vulnerability in STARDOM
  17. Yokogawa YSAR-15-0003: Vulnerabilities of communication functions in CENTUM and other products
  18. Yokogawa YSAR-14-0003: Arbitrary File Read/Write Vulnerability in CENTUM series and Exaopc
  19. Yokogawa YSAR-14-0002: Buffer Overflow Vulnerability in CENTUM systems and Exaopc
  20. Yokogawa YSAR-14-0001: Vulnerabilities in CENTUM and other Yokogawa products
  21. CISA CSAF: ICSA-26-057-09 Yokogawa CENTUM VP R6, R7
  22. CISA CSAF: ICSA-26-092-02 Yokogawa CENTUM VP
  23. CISA CSAF: ICSA-26-041-01 Yokogawa FAST/TOOLS
  24. CISA CSAF: ICSA-24-172-01 Yokogawa CENTUM
  25. CISA CSAF: ICSA-23-334-02 Yokogawa STARDOM
  26. CISA CSAF: ICSA-22-228-01 Yokogawa CENTUM Controller FCS
  27. CISA CSAF: ICSA-22-174-01 Yokogawa STARDOM
  28. CISA CSAF: ICSA-22-123-01 Yokogawa CENTUM and ProSafe-RS
  29. CISA CSAF: ICSA-22-083-01 Yokogawa CENTUM and Exaopc
  30. CISA CSAF: ICSA-20-224-01 Yokogawa CENTUM (Update A)
  31. CISA CSAF: ICSA-18-151-03 Yokogawa STARDOM Controllers (Update A)
  32. CISA CSAF: ICSA-18-102-01 Yokogawa CENTUM and Exaopc
  33. CISA CSAF: ICSA-16-259-01 Yokogawa STARDOM Authentication Bypass
  34. CISA CSAF: ICSA-15-253-01 Yokogawa Multiple Products Buffer Overflow
  35. CISA CSAF: ICSA-14-070-01A Yokogawa CENTUM CS 3000 (Update A)
  36. JPCERT/CC JVNVU#95452299: YOKOGAWA STARDOM controller vulnerabilities (Japanese)
  37. JPCERT/CC JVNVU#94343729: CENTUM controller FCS DoS (Japanese)
  38. NVD: CVE-2025-1924 (Vnet/IP out-of-bounds write)
  39. NVD: CVE-2025-66597 (FAST/TOOLS weak cryptographic algorithms)
  40. NVD: CVE-2022-21194 (CENTUM and Exaopc default OS account password)
  41. NVD: CVE-2020-5608 (CAMS for HIS improper authentication)
  42. NVD: CVE-2018-10592 (STARDOM hard-coded password)
  43. NVD: CVE-2014-0783 (CENTUM CS 3000 BKHOdeq.exe stack overflow)
  44. Rapid7 Metasploit Framework: Yokogawa CENTUM CS 3000 BKHOdeq.exe module
  45. CISA Known Exploited Vulnerabilities catalog
  46. FIRST: Exploit Prediction Scoring System (EPSS)
Was this guide helpful?

In this cluster

Yokogawa vulnerabilities: CENTUM VP and CS 3000, ProSafe-RS, STARDOM FCN/FCJ, Exaopc and FAST/TOOLS, fixed revisions and hardening