CVE-2025-7972 is an access control flaw in the Network Browser of Rockwell Automation FactoryTalk Linx before 6.50, the communication software between FactoryTalk HMIs and Logix controllers. Switching the browser to development mode turns off FactoryTalk Services Platform token validation, so an attacker can create, change or delete Linx drivers. NVD scores it 9.1. The fix is FactoryTalk Linx 6.50.
Vulnerability summary
CVSS base score
9.1
Critical severity
EPSS score (FIRST)
0.8%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2025-7972 · Source: NVD

Affected components
| Component | CPE | Version range |
|---|---|---|
| Rockwell Automation FactoryTalk Linx (Network Browser) | cpe:2.3:a:rockwellautomation:factorytalk_linx:*:*:*:*:*:*:*:* | All versions before 6.50 (NVD: before 6.50; CISA ICSA-25-226-24 and Rockwell's record); fixed in FactoryTalk Linx 6.50 and later |
What does this mean for affected devices?
Rockwell Automation, the CNA, says: "A security issue exists within the FactoryTalk Linx Network Browser. By modifying the process.env.NODE_ENV to 'development', the attacker can disable FTSP token validation. This bypass allows access to create, update, and delete FTLinx drivers." FTSP is the FactoryTalk Services Platform, which provides FactoryTalk Security for the suite. NVD's Primary score is 9.1 (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:H). CISA scores a local attack vector with changed scope, CVSS 3.1 9.0 (AV:L/AC:L/PR:N/UI:N/S:C/C:N/I:H/A:H), and Rockwell gives CVSS v4.0 8.4, also local. CISA maps CWE-284, improper access control; Rockwell's record maps CWE-286, incorrect user management; NVD adds no CWE of its own. NVD's configuration covers FactoryTalk Linx before 6.50 (NVD, CVE record).
Which FactoryTalk Linx versions are affected?
CISA's ICSA-25-226-24 (CSAF), released on 2025-08-14, lists FactoryTalk Linx before 6.50, deployed worldwide in the Critical Manufacturing sector; Rockwell reported it to CISA and published its own advisory as SD1735. Linx drivers define how HMI servers, historians and engineering tools reach the controllers, so an attacker who can change or delete them can cut or redirect plant communications. FactoryTalk Linx also ships inside other Rockwell software: CISA's 2020 advisory ICSA-20-163-02 listed products such as Studio 5000 Launcher, Studio 5000 Logix Designer, FactoryTalk AssetCentre and ControlFLASH alongside FactoryTalk Linx, so check engineering workstations as well as communication servers.
How do you fix CVE-2025-7972?
Update FactoryTalk Linx to 6.50 or later, as Rockwell and CISA recommend. Where the upgrade has to wait, apply Rockwell's security best practices and CISA's standard controls: keep control system hosts off the internet and behind firewalls, isolate them from the business network, limit who can log on to Linx hosts, and use an up-to-date VPN for remote access. CISA reported no known public exploitation when it published the advisory.
The Rockwell FactoryTalk software guide lists the other FactoryTalk Linx flaws, including the 2020 heap overflow CVE-2020-27251, and the FTSP token flaw CVE-2024-21917 shows a related weakness in the platform underneath. The authentication bypass fix guide covers how to detect, fix and verify this family of authentication flaws.
Is CVE-2025-7972 exploited?
CVE-2025-7972 is not in the CISA KEV catalog as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS gives it 0.0085, a percentile of 55.6, in the 2026-11-27 dataset (CISA KEV, FIRST EPSS).


Evidence
- NVD (read 2026-11-28): status Analyzed; published 2025-08-14; [email protected] Primary CVSS 3.1 9.1 AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:H; Rockwell Secondary CVSS 4.0 8.4 (AV:L); CWE-286 (Rockwell Secondary) only; CPE factorytalk_linx before 6.50. — NVD
- CISA ICSA-25-226-24 CSAF (read 2026-11-28): released 2025-08-14; FactoryTalk Linx < 6.50; CWE-284; CVSS 3.1 9.0 AV:L/AC:L/PR:N/UI:N/S:C/C:N/I:H/A:H; fix update to v6.50; reported by Rockwell Automation; no known public exploitation; sector Critical Manufacturing. — CISA ICSA-25-226-24
- CVE record (read 2026-11-28): PUBLISHED, assigner Rockwell, published 2025-08-14; all prior to 6.50; CWE-286; CNA CVSS 4.0 8.4; solution upgrade to 6.50 or later; reference Rockwell advisory SD1735. — CVE.org
- CISA ICSA-20-163-02 CSAF (read 2026-11-28): product tree lists FactoryTalk Linx 6.00/6.10/6.11 together with FactoryTalk Linx CommDTM, Studio 5000 Launcher, FactoryTalk AssetCentre, Studio 5000 Logix Designer, Connected Components Workbench, ControlFLASH Plus and ControlFLASH. — CISA ICSA-20-163-02
- Not in the CISA KEV catalog, catalog version 2026.11.27, 1,808 entries, checked 2026-11-28. — CISA KEV
- EPSS 0.00849, percentile 0.55612, dataset 2026-11-27, read 2026-11-28. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
Which FactoryTalk Linx versions are affected by CVE-2025-7972?
All FactoryTalk Linx versions before 6.50, per CISA ICSA-25-226-24, Rockwell's CVE record and NVD's configuration.
How do I fix CVE-2025-7972?
Upgrade FactoryTalk Linx to 6.50 or later on every host where it is installed, including engineering workstations that received Linx with other Rockwell software. Until then, restrict logons to those hosts and keep them behind the plant firewall.
Why do NVD, CISA and Rockwell give different scores?
NVD scored a network attack vector (9.1, CVSS 3.1). CISA scored a local attack with changed scope (9.0, CVSS 3.1), and Rockwell a local attack in CVSS v4.0 (8.4). All three rate the integrity and availability impact high.
Is CVE-2025-7972 in the CISA KEV catalog?
No, not as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS rates it 0.0085 (percentile 55.6) in the 2026-11-27 dataset.
Questions about this page?