CVE-2020-27251 is a heap overflow in Rockwell Automation FactoryTalk Linx 6.11 and earlier: a remote attacker without credentials can send malicious port ranges and may run code on the host. NVD and CISA both score it 9.8. Rockwell fixes it with a patch for versions 6.10 and 6.11 or with an upgrade to 6.20.
Vulnerability summary
CVSS base score
9.8
Critical severity
EPSS score (FIRST)
6.8%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2020-27251 · Source: NVD

Affected components
| Component | CPE | Version range |
|---|---|---|
| Rockwell Automation FactoryTalk Linx | cpe:2.3:a:rockwellautomation:factorytalk_linx:*:*:*:*:*:*:*:* | 6.11 and earlier (NVD: up to and including 6.11; CISA ICSA-20-329-01); fixed by the Rockwell patch for 6.10/6.11 (Patch Answer ID 1126433) or by 6.20 |
What does this mean for affected devices?
The CVE record from CISA says: "A heap overflow vulnerability exists within FactoryTalk Linx Version 6.11 and prior. This vulnerability could allow a remote, unauthenticated attacker to send malicious port ranges, which could result in remote code execution." NVD's Primary score is 9.8 (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H, CVSS 2.0 7.5), the same 9.8 that CISA calculated. The weakness is CWE-122, heap-based buffer overflow, as mapped by CISA; NVD lists no CWE of its own. NVD's configuration covers FactoryTalk Linx up to and including 6.11 (NVD, CVE record).
Which FactoryTalk Linx versions are affected?
CISA's ICSA-20-329-01, released on 2020-11-24, lists FactoryTalk Linx 6.11 and prior, deployed worldwide in the Critical Manufacturing, Energy and Water and Wastewater Systems sectors. Sharon Brizinov of Claroty reported the flaws to Rockwell Automation's PSIRT. The advisory has two sibling CVEs in the same software: CVE-2020-27253, an input validation flaw in the ingress/egress checks that lets a crafted packet cause a denial of service (CISA 8.6), and CVE-2020-27255, a second heap overflow through set attribute requests that can leak memory useful for bypassing ASLR (CISA 5.3). CISA summarises the impact of the three as denial of service, remote code execution or an information leak.
How do you fix CVE-2020-27251?
Rockwell's remedy, as CISA records it in the CSAF advisory, is to install the patch for FactoryTalk Linx 6.10 and 6.11 (Rockwell Patch Answer ID 1126433) or to move to version 6.20; both are on Rockwell's download site, which needs a login, and Rockwell's own Industrial Security Advisory 1128684 is also behind a login. Rockwell and CISA add general controls:
- keep control system networks and devices off the internet and behind firewalls, isolated from the business network;
- run the software as a normal user, not as administrator, and apply application allow-listing such as AppLocker;
- follow least privilege for user and service accounts;
- use a current VPN when remote access is needed.
The memory corruption fix guide covers how vendors remove this class of bug, and the Rockwell Logix guide collects other Rockwell advisories, including the Logix key bypass CVE-2021-22681 and the hidden code change CVE-2022-1161.
Is CVE-2020-27251 exploited?
CVE-2020-27251 is not in the CISA KEV catalog as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS gives it 0.06815, the 94.78th percentile, in the 2026-11-26 dataset (CISA KEV, FIRST EPSS). CISA reported no known public exploits specifically targeting these vulnerabilities when it published the advisory.


Evidence
- NVD (read 2026-11-27): status Modified; published 2020-11-26; [email protected] Primary CVSS 3.1 9.8 AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H, CVSS 2.0 7.5; CWE-122 from ICS-CERT (Secondary) only; CPE rockwellautomation factorytalk_linx up to and including 6.11. — NVD
- CISA ICSA-20-329-01 (2020-11-24): FactoryTalk Linx <= 6.11; CVE-2020-27251 CWE-122 CVSS 3.0 9.8; siblings CVE-2020-27253 (CWE-20, 8.6) and CVE-2020-27255 (CWE-122, 5.3); fix: patch for 6.10/6.11 (Patch Answer ID 1126433) or move to 6.20 (PCDC, login); Rockwell advisory ID 1128684 (login); reported by Sharon Brizinov (Claroty); sectors Critical Manufacturing, Energy, Water and Wastewater; no known public exploits. — CISA CSAF
- CVE.org record (CNA icscert): published 2020-11-26; FactoryTalk Linx Version 6.11 and prior; CWE-122; no CVSS in the record. — CVE.org
- CISA KEV catalog version 2026.11.25, 1,805 entries: CVE-2020-27251 not listed; checked 2026-11-27. — CISA KEV
- EPSS 0.06815, percentile 0.94778, dataset 2026-11-26, read 2026-11-27. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
Which FactoryTalk Linx versions are affected by CVE-2020-27251?
FactoryTalk Linx 6.11 and earlier, per CISA ICSA-20-329-01 and the NVD configuration, which covers versions up to and including 6.11.
How do I fix CVE-2020-27251?
Install Rockwell's patch for FactoryTalk Linx 6.10 or 6.11 (Patch Answer ID 1126433) or upgrade to 6.20. Both downloads need a Rockwell login. Until then, keep the host off the internet, behind a firewall and separate from the business network.
What other CVEs were published with CVE-2020-27251?
CVE-2020-27253, a crafted-packet denial of service (CISA 8.6), and CVE-2020-27255, a heap overflow that can leak memory to bypass ASLR (CISA 5.3). The same patch or upgrade covers all three (CISA ICSA-20-329-01).
Is CVE-2020-27251 in the CISA KEV catalog?
No, not as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS rates it 0.06815, the 94.78th percentile, in the 2026-11-26 dataset.
Questions about this page?