Security Advisory

CVE-2024-21917: FactoryTalk Services Platform Token Reuse

Last updated:
  • CVE-2024-21917

CVE-2024-21917 is a signature verification flaw in Rockwell Automation FactoryTalk Services Platform before v6.40, the security and directory layer under FactoryTalk View, Linx and AssetCentre. The FTSP service token is not digitally bound to its directory, so a malicious user who obtains it can use it on another FTSP directory. NVD scores it 9.1 and CISA 9.8. FTSP v6.40 fixes it.

Vulnerability summary

CVSS base score

9.1

Critical severity

EPSS score (FIRST)

0.7%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2024-21917 · Source: NVD

CVSS v3.1 severity rating scale: None 0.0, Low 0.1 to 3.9, Medium 4.0 to 6.9, High 7.0 to 8.9, Critical 9.0 to 10.0
How a CVSS v3.1 base score maps to a severity rating. Source: FIRST CVSS v3.1 specification, section 5.

Affected components

ComponentCPEVersion range
Rockwell Automation FactoryTalk Services Platform (FTSP)cpe:2.3:a:rockwellautomation:factorytalk_services_platform:*:*:*:*:*:*:*:*Before v6.40 (CISA ICSA-24-030-06: < v6.4; Rockwell's record: <= v6.31; NVD: up to and including 6.31.00); fixed in v6.40 and later

What does this mean for affected devices?

Rockwell Automation, the CNA, describes the flaw: it "allows a malicious user to obtain the service token and use it for authentication on another FTSP directory. This is due to the lack of digital signing between the FTSP service token and directory. If exploited, a malicious user could potentially retrieve user information and modify settings without any authentication." NVD's Primary score is 9.1 (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:N); Rockwell and CISA score it 9.8 (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H), rating availability high as well. NVD, Rockwell and CISA all map CWE-347, improper verification of cryptographic signature. NVD's configuration covers FTSP up to and including 6.31.00 (NVD, CVE record).

Which FactoryTalk Services Platform versions are affected?

CISA's ICSA-24-030-06 (CSAF), released on 2024-01-30, lists FactoryTalk Services Platform before v6.4, deployed worldwide in the Critical Manufacturing sector; Rockwell's record says v6.31 and earlier, and its own advisory is SD1660. FTSP holds the FactoryTalk Directory and FactoryTalk Security, so it runs on every node with FactoryTalk software: HMI servers, clients, engineering workstations and AssetCentre servers. Settings changed through a reused token apply to the products that rely on that directory.

How do you fix CVE-2024-21917?

Rockwell's guidance, from its CVE record and CISA's advisory:

  • update FactoryTalk Services Platform to v6.40 or later;
  • set the DCOM authentication level to 6, following Rockwell's article on mitigating the Microsoft DCOM hardening patch (CVE-2021-26414) for affected Rockwell products;
  • where v6.40 cannot be installed yet, enable verification of the publisher information (digital signature) of any executable that tries to use the FactoryTalk Services APIs, so a malicious program cannot call the API to receive the service token. The setting is in the Application Authorization node under System Policies in the FactoryTalk Administration Console.

Apply Rockwell's security best practices as well, and keep FactoryTalk nodes behind the plant firewall. CISA reported no known public exploitation when it published the advisory.

The Rockwell FactoryTalk software guide lists the other FTSP flaws, including the 2021 password hashing flaw CVE-2020-14516; the FactoryTalk Linx token check bypass CVE-2025-7972 is a later flaw around the same tokens. The authentication bypass fix guide covers how to detect, fix and verify this family of authentication flaws.

Is CVE-2024-21917 exploited?

CVE-2024-21917 is not in the CISA KEV catalog as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS gives it 0.0071, a percentile of 49.2, in the 2026-11-27 dataset (CISA KEV, FIRST EPSS).

Three signals on every advisory: CVSS says how severe the flaw is, EPSS gives the probability of exploitation in the wild in the next 30 days, and a CISA KEV listing means the flaw has been exploited in the wild
CVSS rates severity, EPSS estimates the likelihood of exploitation, and CISA KEV records exploitation seen in the wild. Source: FIRST EPSS; CISA KEV catalog.
How to fix this class of issueNo dedicated SoftWSP guide covers this weakness class; the fix is usually the vendor patch or firmware update referenced above. Our related guide explains how to plan and verify it: NIST SP 800-40 Rev. 4: enterprise patch management planning, explained.
From advisory to verified fix in four steps: read the advisory, find the affected component in the firmware SBOM, apply the fixed version or vendor mitigation, then re-scan the image to confirm the vulnerable version is gone
Read the advisory, find the component in your firmware SBOM, apply the fix, then re-scan to confirm it.

Evidence

  • NVD (read 2026-11-28): status Modified; published 2024-01-31; [email protected] Primary CVSS 3.1 9.1 AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:N; Rockwell Secondary 9.8 AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H; CWE-347 (NVD Primary and Rockwell); CPE factorytalk_services_platform up to and including 6.31.00. — NVD
  • CISA ICSA-24-030-06 CSAF (read 2026-11-28): released 2024-01-30; FactoryTalk Service Platform < v6.4; CWE-347; CVSS 3.1 9.8; mitigation: when v6.40 is not possible, enable publisher verification via Application Authorization node in System Policies (FactoryTalk Administration Console); reported by Rockwell Automation; sector Critical Manufacturing. — CISA ICSA-24-030-06
  • CVE record (read 2026-11-28): PUBLISHED, assigner Rockwell, published 2024-01-31; FactoryTalk Service Platform <= v6.31; CWE-347; CNA CVSS 3.1 9.8; solutions: update to v6.40 or later, set DCOM authentication level to 6 (Rockwell article on the Microsoft DCOM hardening patch CVE-2021-26414), publisher verification; reference Rockwell advisory SD1660. — CVE.org
  • Not in the CISA KEV catalog, catalog version 2026.11.27, 1,808 entries, checked 2026-11-28. — CISA KEV
  • EPSS 0.00708, percentile 0.49178, dataset 2026-11-27, read 2026-11-28. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. CISA ICSA-24-030-06: Rockwell Automation FactoryTalk Service Platform
  3. CISA ICSA-24-030-06 CSAF (machine-readable advisory)
  4. CVE record CVE-2024-21917 (CVE Services JSON)
  5. CISA KEV
  6. FIRST EPSS

Frequently asked questions

Which FactoryTalk Services Platform versions are affected by CVE-2024-21917?

Versions before v6.40. CISA lists FTSP before v6.4, Rockwell's record says v6.31 and earlier, and NVD's configuration covers up to and including 6.31.00.

How do I fix CVE-2024-21917?

Update FactoryTalk Services Platform to v6.40 or later on every FactoryTalk node. Rockwell also asks owners to set the DCOM authentication level to 6. Until the update, enable publisher verification for executables that call the FactoryTalk Services APIs in the FactoryTalk Administration Console.

Why does NVD say 9.1 when Rockwell and CISA say 9.8?

NVD rated the availability impact as none (A:N), while Rockwell and CISA rated it high (A:H). Both agree on a network attack with no privileges and high confidentiality and integrity impact.

Is CVE-2024-21917 in the CISA KEV catalog?

No, not as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS rates it 0.0071 (percentile 49.2) in the 2026-11-27 dataset.