Security Advisory

CVE-2020-7501: Vijeo Designer Hard-Coded Credentials

Last updated:
  • CVE-2020-7501

CVE-2020-7501 is a hard-coded credentials flaw (CWE-798) in Schneider Electric's Vijeo Designer and Vijeo Designer Basic, the tools that configure Harmony/Magelis HMIs. It could allow unauthorized read and write when projects or firmware are transferred to or from a panel. NVD scores it 8.8 and Schneider 8.6. Vijeo Designer V6.2 SP10 and Basic V1.1 HotFix 17 fix it.

Vulnerability summary

CVSS base score

8.8

High severity

EPSS score (FIRST)

1.1%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2020-7501 · Source: NVD

CVSS v3.1 severity rating scale: None 0.0, Low 0.1 to 3.9, Medium 4.0 to 6.9, High 7.0 to 8.9, Critical 9.0 to 10.0
How a CVSS v3.1 base score maps to a severity rating. Source: FIRST CVSS v3.1 specification, section 5.

Affected components

ComponentCPEVersion range
Schneider Electric Vijeo Designercpe:2.3:a:schneider-electric:vijeo_designer:*:*:*:*:-:*:*:*V6.2 SP9 and prior per Schneider (NVD CPE: up to and including 6.2, plus 6.9 and 6.9 SP9 entries); fixed in V6.2 SP10 (July 2020)
Schneider Electric Vijeo Designer Basiccpe:2.3:a:schneider-electric:vijeo_designer:*:*:*:*:basic:*:*:*V1.1 HotFix 16 and prior per Schneider (NVD CPE: up to 1.0, 1.1 and 1.1 HotFix 15); fixed in V1.1 HotFix 17 from Schneider customer support

What does this mean for affected devices?

Schneider Electric's notice SEVD-2020-133-02, first released on 12 May 2020 and updated to version 1.1 in August 2020, describes "a CWE-798: Use of Hard-coded Credentials vulnerability" "which could cause unauthorized read and write when downloading and uploading project or firmware into Vijeo Designer Basic and Vijeo Designer". Vijeo Designer builds the applications that run on Magelis and Harmony HMI panels and smart iPCs, so the transfer path is the link between the engineering workstation and the panel.

How severe is CVE-2020-7501?

NVD's Primary score is CVSS v3.1 8.8, AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H, plus CVSS v2 6.5 (NVD). Schneider scores it CVSS v3.0 8.6, AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:L/A:H: no privileges needed, but lower confidentiality and integrity impact. NVD and Schneider both map it to CWE-798 (CVE.org record). Jie Chen of NSFOCUS reported it.

Which versions are affected and what is the fix?

Schneider lists Vijeo Designer Basic V1.1 HotFix 16 and prior and Vijeo Designer V6.2 SP9 and prior. The fixes are Vijeo Designer Basic V1.1 HotFix 17, available from Schneider customer support, and Vijeo Designer V6.2 SP10, released in July 2020. Users of Vijeo Designer V6.2 or later receive SP10 through the Schneider Electric Software Update (SESU) client; users of V6.1 or earlier get it from customer support. NVD's CPE list differs in detail: it includes Basic only up to HotFix 15 and lists Vijeo Designer 6.9 and 6.9 SP9 entries next to versions up to 6.2.

Until updated, Schneider's workarounds are to enable "Download security", which overrides the hard-coded password (online help section 4.8.2.2, Protecting Targets from Unauthorized Project Downloads), and to segment the network and block all unauthorized access to TCP port 6001, which Schneider describes as a non-standard FTP port.

The Schneider EcoStruxure HMI and SCADA software guide pairs this flaw with the FTP path traversal CVE-2021-22704 on the same port. Other fixed logins in Schneider gear include CVE-2015-7921 in Pro-face GP-Pro EX and CVE-2014-9198 in the ETG3000 gateway. The hard-coded credentials fix guide explains the root cause.

Is CVE-2020-7501 exploited?

It is not in the CISA KEV catalog as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS gives it 0.01118, the 65.8th percentile, in the 2026-11-27 dataset (CISA KEV, FIRST EPSS).

Three signals on every advisory: CVSS says how severe the flaw is, EPSS gives the probability of exploitation in the wild in the next 30 days, and a CISA KEV listing means the flaw has been exploited in the wild
CVSS rates severity, EPSS estimates the likelihood of exploitation, and CISA KEV records exploitation seen in the wild. Source: FIRST EPSS; CISA KEV catalog.
How to fix this class of issueThis advisory's weakness class is Hard-coded credentials. Our practical guide covers how to detect, fix, verify and disclose it: How to fix hard-coded credentials in embedded firmware.
From advisory to verified fix in four steps: read the advisory, find the affected component in the firmware SBOM, apply the fixed version or vendor mitigation, then re-scan the image to confirm the vulnerable version is gone
Read the advisory, find the component in your firmware SBOM, apply the fix, then re-scan to confirm it.

Evidence

  • NVD (read 2026-11-28): published 2020-06-16, status Modified; NVD Primary CVSS v3.1 8.8 AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H; NVD Primary CVSS v2 6.5; CWE-798 (NVD and Schneider); CPE vijeo_designer basic up to 1.0, 1.1, 1.1 hotfix_15; vijeo_designer up to 6.2, 6.9, 6.9 sp9. — NVD
  • Schneider SEVD-2020-133-02 V1.1 (12 May 2020, updated August 2020, read 2026-11-28): affected Vijeo Designer Basic V1.1 HotFix 16 and prior, Vijeo Designer V6.2 SP9 and prior; CVSS v3.0 8.6 AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:L/A:H; fixes Basic V1.1 HotFix 17 (customer support) and Vijeo Designer V6.2 SP10 (July 2020, SESU for V6.2+); workarounds Download security and block TCP/6001; credited to Jie Chen (NSFOCUS). — Schneider Electric
  • CVE.org record (read 2026-11-28): assigner Schneider Electric, CWE-798, no CVSS metric in the CNA container. — CVE.org
  • Not in the CISA KEV catalog, catalog version 2026.11.27, 1,808 entries, checked 2026-11-28. — CISA KEV
  • EPSS 0.01118, percentile 0.65828, dataset 2026-11-27, read 2026-11-28. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. Schneider Electric SEVD-2020-133-02 V1.1: Vijeo Designer and Vijeo Designer Basic
  3. CVE.org record (JSON)
  4. CISA KEV
  5. FIRST EPSS

Frequently asked questions

Which versions fix CVE-2020-7501?

Vijeo Designer V6.2 SP10, released in July 2020 and delivered through SESU to V6.2 users, and Vijeo Designer Basic V1.1 HotFix 17, available from Schneider customer support, per SEVD-2020-133-02.

How can I reduce the risk before updating?

Schneider's workarounds are to enable "Download security", which overrides the hard-coded password, and to block all unauthorized access to TCP port 6001, the non-standard FTP port used for project and firmware transfer.

Why do NVD and Schneider scores differ?

NVD's CVSS v3.1 8.8 assumes low privileges and high confidentiality and integrity impact. Schneider's CVSS v3.0 8.6 assumes no privileges but low confidentiality and integrity impact with high availability impact.

Is CVE-2020-7501 in the CISA KEV catalog?

No, not as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS rates it 0.01118, the 65.8th percentile, in the 2026-11-27 dataset.