CVE-2024-27772 is an OS command injection in Unitronics UniStream PLC/HMI controllers that lets an attacker run code on the device over the Ethernet network. Unitronics advisory 2024-006 lists all UniStream products with UniLogic before 1.35.227 as affected and names 1.35.227 or later as the fix. NVD and INCD score it CVSS 3.1 8.8.

Vulnerability summary

CVSS base score

8.8

High severity

EPSS score (FIRST)

1.7%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2024-27772 · Source: NVD

Affected components

ComponentCPEVersion range
Unitronics UniStream PLC/HMI series, all products (Unitronics advisory 2024-006), programmed with UniLogiccpe:2.3:a:unitronics:unilogic:*:*:*:*:*:*:*:*UniLogic before 1.35.227 (NVD CPE and Unitronics advisory); fixed in UniLogic 1.35.227 or later

What does this mean for affected devices?

The CVE record for CVE-2024-27772 reads "CWE-78: 'OS Command Injection' may allow RCE" for UniLogic versions prior to 1.35.227. The Israel National Cyber Directorate (INCD) published it as CNA on 2024-03-18 and credits Noam Moshe and Vera Mens of Claroty Team82. NVD's Primary score and INCD's score agree at CVSS 3.1 8.8 (AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H): network access with a low-privileged account and full impact. NVD's CPE covers UniLogic before 1.35.227 (NVD, CVE record).

Which Unitronics products are affected?

Unitronics Cybersecurity Advisory 2024-006, titled "OS Command Injection" and dated 18 March 2024, names the component as UniStream, the product as "All Products" and the affected version as UniLogic below 1.35.227. Its description says that "an attacker can execute code from a remote location over an Ethernet network". Code running on a PLC/HMI can change the control logic and the values shown to operators, which is why a command injection on a controller is a process safety issue as well as an IT one.

How does it chain with the other UniStream flaws?

Claroty Team82 reported eight UniStream flaws together, and its write-up says some of them chain to let "an unauthorized attacker to connect to the UniStream PLC, fully control it, and execute arbitrary commands". NVD scores this flaw with low privileges required. The authentication bypass CVE-2024-27767, scored with no privileges, is the flaw that can remove that requirement. The path traversal CVE-2024-27768 and the less trusted source flaw CVE-2024-27773 are the other code execution paths in the set. Team82 counted about 480 vulnerable UniStream devices reachable from the internet.

How do you fix or mitigate it?

Unitronics' advisory gives five steps: update to UniLogic 1.35.227 or later; verify that PLCs are not directly accessible from the internet and allow access only from defined addresses or through a VPN or ZTNA; apply long complex passwords and change the default installed password; use UniCloud for two-factor access, particularly for admin access; and keep devices on the latest security updates. The advisory does not say whether the controller needs a separate update, so after updating UniLogic, check the operating system version reported by each controller against Unitronics' release notes. Our Unitronics Vision and UniStream vulnerability guide covers the full Unitronics set, and the command injection fix guide covers the weakness class.

Is it exploited?

CVE-2024-27772 is not in the CISA KEV catalog as of 2026-11-21 (catalog version 2026.11.20, 1,790 entries). The only Unitronics entry is CVE-2023-6448. FIRST EPSS gives CVE-2024-27772 0.01731, the 78.2nd percentile and the highest in the 2024 UniStream set, in the 2026-11-20 dataset (CISA KEV, FIRST EPSS).

How to fix this class of issueThis advisory's weakness class is Command injection. Our practical guide covers how to detect, fix, verify and disclose it: How to fix command injection in embedded firmware.

Evidence

  • NVD (read 2026-11-21): status Analyzed; published 2024-03-18, source [email protected]; description 'Unitronics Unistream Unilogic – Versions prior to 1.35.227 - CWE-78: OS Command Injection may allow RCE'; NVD Primary CVSS 3.1 8.8 AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H; CNA Secondary 8.8, same vector; CWE-78 (CNA); CPE cpe:2.3:a:unitronics:unilogic versions before 1.35.227. — NVD
  • Unitronics Cybersecurity Advisory 2024-006 'OS Command Injection', publication date 18 March 2024, read 2026-11-21: component UniStream, product All Products, affected UniLogic < 1.35.227; summary 'Remote code execution by an Unauthorized Actor'; 'An attacker can execute code from a remote location over an Ethernet network'; mitigations: update to UniLogic 1.35.227 or later, no direct internet access (defined addresses, VPN or ZTNA), long complex passwords and change the default, UniCloud 2FA, regular updates. — Unitronics
  • CVE record (CVE Services API, checked 2026-11-21): state PUBLISHED, CNA INCD, published 2024-03-18; affected 'Unitronics Unistream Unilogic' less than 1.35.227; CVSS 3.1 8.8; finder Noam Moshe, Vera Mens of Claroty Team82; solution 'Upgrade to version 1.35.227 or later.' — CVE.org
  • Claroty Team82 'New Critical Vulnerabilities in Unitronics UniStream Devices Uncovered', published 2024-03-18, read 2026-11-21: eight vulnerabilities that bypass UniStream authentication and authorization and can be chained to remote code execution; around 480 internet-exposed and vulnerable UniStream devices found with Shodan and Censys; devices are not preconfigured to be reachable online; disclosed to Unitronics, CISA and the Israel National Cyber Directorate; per-CVE list with CWE and CVSS v3. CVE-2024-27772 listed as CWE-78, CVSS v3 8.8. — Claroty Team82
  • Not in the CISA KEV catalog, version 2026.11.20 (1,790 entries), checked 2026-11-21; the only Unitronics entry is CVE-2023-6448 (added 2023-12-11). — CISA KEV
  • EPSS 0.01731, percentile 0.78176, dataset 2026-11-20, read 2026-11-21 (highest of CVE-2024-27767, -27768, -27769, -27772, -27773, -27774 in the same dataset). — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. Unitronics Cybersecurity Advisory 2024-006: OS Command Injection (CVE-2024-27772)
  3. Claroty Team82: New Critical Vulnerabilities in Unitronics UniStream Devices Uncovered
  4. CVE.org record (CNA: INCD, Israel National Cyber Directorate)
  5. CISA KEV
  6. FIRST EPSS

Frequently asked questions

Which version fixes CVE-2024-27772?

UniLogic 1.35.227 or later. Unitronics advisory 2024-006, the CVE record and NVD's CPE all say UniLogic versions before 1.35.227 are affected, and Unitronics lists every UniStream product.

Does an attacker need an account?

NVD and INCD score it with low privileges required (PR:L). Claroty Team82 says the UniStream flaws it found chain together to give an unauthorized attacker full control, and the set includes the authentication bypass CVE-2024-27767, so do not rely on passwords alone to protect an unpatched controller.

Why is its EPSS score higher than the others in the set?

FIRST EPSS gives CVE-2024-27772 0.01731 (78.2nd percentile) in the 2026-11-20 dataset, against 0.00355 to 0.00854 for the other five CVEs from the set covered on this site. EPSS is a model estimate of exploitation activity in the next 30 days, not a report of observed attacks, and the CVE is not in CISA KEV as of 2026-11-21.

Is this the flaw used in the 2023 water utility attacks?

No. The 2023 attacks on US water facilities used Unitronics Vision controllers and the default password weakness CVE-2023-6448, the only Unitronics entry in the CISA KEV catalog as of 2026-11-21. Claroty Team82 says that campaign prompted its research into the newer UniStream series, which found this and seven other flaws.