CVE-2024-27773 is a flaw in Unitronics UniStream PLC/HMI controllers where the device trusts data from a less trusted source, which may let an attacker run code over the network. Unitronics advisory 2024-007 lists all UniStream products with UniLogic before 1.35.227 as affected and names 1.35.227 or later as the fix. NVD and INCD score it 8.8.
Vulnerability summary
CVSS base score
8.8
High severity
EPSS score (FIRST)
0.4%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2024-27773 · Source: NVD
Affected components
| Component | CPE | Version range |
|---|---|---|
| Unitronics UniStream PLC/HMI series, all products (Unitronics advisory 2024-007), programmed with UniLogic | cpe:2.3:a:unitronics:unilogic:*:*:*:*:*:*:*:* | UniLogic before 1.35.227 (NVD CPE and Unitronics advisory); fixed in UniLogic 1.35.227 or later |
What does this mean for affected devices?
The CVE record for CVE-2024-27773 reads "CWE-348: Use of Less Trusted Source may allow RCE" for UniLogic versions prior to 1.35.227. The Israel National Cyber Directorate (INCD) published it as CNA on 2024-03-18 and credits Noam Moshe and Vera Mens of Claroty Team82. NVD's Primary score and INCD's score agree at CVSS 3.1 8.8 (AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H). NVD's CPE covers UniLogic before 1.35.227 (NVD, CVE record).
Which weakness is it?
The sources disagree on the CWE. INCD gives CWE-348 (Use of Less Trusted Source), NVD maps it to CWE-345 (Insufficient Verification of Data Authenticity), and Claroty Team82's per-CVE list on its write-up labels it CWE-78, OS command injection. All three agree on the result, remote code execution, and none gives technical details of the input involved. This page follows the CNA's description.
Which Unitronics products are affected?
Unitronics Cybersecurity Advisory 2024-007, titled "Use of Less Trusted Source" and dated 18 March 2024, names the component as UniStream, the product as "All Products" and the affected version as UniLogic below 1.35.227. Its description says that "an attacker can execute code from a remote location over an Ethernet network".
How does it fit with the other UniStream flaws?
Claroty Team82 reported eight UniStream flaws and says some of them chain to give "an unauthorized attacker" full control of the PLC and command execution. NVD scores this one with low privileges required. The authentication bypass CVE-2024-27767 needs none, and the OS command injection CVE-2024-27772 is the other low-privilege code execution path. Team82 counted about 480 vulnerable UniStream devices reachable from the internet.
How do you fix or mitigate it?
Unitronics' advisory gives five steps: update to UniLogic 1.35.227 or later; verify that PLCs are not directly accessible from the internet and allow access only from defined addresses or through a VPN or ZTNA; apply long complex passwords and change the default installed password; use UniCloud for two-factor access, particularly for admin access; and keep devices on the latest security updates. The advisory does not say whether the controller needs a separate update, so after updating UniLogic, check the operating system version reported by each controller against Unitronics' release notes. Our Unitronics Vision and UniStream vulnerability guide covers the full Unitronics set, and the input handling fix guide covers validating data before a device acts on it.
Is it exploited?
CVE-2024-27773 is not in the CISA KEV catalog as of 2026-11-21 (catalog version 2026.11.20, 1,790 entries). The only Unitronics entry is CVE-2023-6448. FIRST EPSS gives CVE-2024-27773 0.00355, the 30.0th percentile, in the 2026-11-20 dataset (CISA KEV, FIRST EPSS).
Evidence
- NVD (read 2026-11-21): status Analyzed; published 2024-03-18, source [email protected]; description 'Unitronics Unistream Unilogic – Versions prior to 1.35.227 - CWE-348: Use of Less Trusted Source may allow RCE'; NVD Primary CVSS 3.1 8.8 AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H; CNA Secondary 8.8, same vector; CWE-348 (CNA), CWE-345 (NVD); CPE cpe:2.3:a:unitronics:unilogic versions before 1.35.227. — NVD
- Unitronics Cybersecurity Advisory 2024-007 'Use of Less Trusted Source', publication date 18 March 2024, read 2026-11-21: component UniStream, product All Products, affected UniLogic < 1.35.227; summary 'Remote code execution by an Unauthorized Actor'; 'An attacker can execute code from a remote location over an Ethernet network'; mitigations: update to UniLogic 1.35.227 or later, no direct internet access (defined addresses, VPN or ZTNA), long complex passwords and change the default, UniCloud 2FA, regular updates. — Unitronics
- CVE record (CVE Services API, checked 2026-11-21): state PUBLISHED, CNA INCD, published 2024-03-18; affected 'Unitronics Unistream Unilogic' less than 1.35.227; CVSS 3.1 8.8; finder Noam Moshe, Vera Mens of Claroty Team82; solution 'Upgrade to version 1.35.227 or later.' — CVE.org
- Claroty Team82 'New Critical Vulnerabilities in Unitronics UniStream Devices Uncovered', published 2024-03-18, read 2026-11-21: eight vulnerabilities that bypass UniStream authentication and authorization and can be chained to remote code execution; around 480 internet-exposed and vulnerable UniStream devices found with Shodan and Censys; devices are not preconfigured to be reachable online; disclosed to Unitronics, CISA and the Israel National Cyber Directorate; per-CVE list with CWE and CVSS v3. CVE-2024-27773 listed as CWE-78 'OS Command Injection', CVSS v3 8.8. — Claroty Team82
- Not in the CISA KEV catalog, version 2026.11.20 (1,790 entries), checked 2026-11-21; the only Unitronics entry is CVE-2023-6448 (added 2023-12-11). — CISA KEV
- EPSS 0.00355, percentile 0.29994, dataset 2026-11-20, read 2026-11-21. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
Which version fixes CVE-2024-27773?
UniLogic 1.35.227 or later. Unitronics advisory 2024-007, the CVE record and NVD's CPE all say UniLogic versions before 1.35.227 are affected, and Unitronics lists every UniStream product.
Why do the CWE labels differ?
INCD, the CNA, uses CWE-348 (Use of Less Trusted Source); NVD maps it to CWE-345 (Insufficient Verification of Data Authenticity); Claroty's vulnerability list shows CWE-78 (OS Command Injection). The CVE, affected versions, score and fix are the same in every source.
What should I do before I can update?
Unitronics recommends keeping PLCs off direct internet access and allowing only defined addresses or a VPN/ZTNA path, replacing the default password with a long complex one, and using UniCloud two-factor access for admin connections.
Is this the flaw used in the 2023 water utility attacks?
No. The 2023 attacks on US water facilities used Unitronics Vision controllers and the default password weakness CVE-2023-6448, the only Unitronics entry in the CISA KEV catalog as of 2026-11-21. Claroty Team82 says that campaign prompted its research into the newer UniStream series, which found this and seven other flaws.
Questions about this page?