Security Advisory

CVE-2020-14516: FactoryTalk Services Platform Weak Hash

Last updated:
  • CVE-2020-14516

CVE-2020-14516 is a password hashing flaw (CWE-916) in Rockwell Automation FactoryTalk Services Platform 6.10.00 and 6.11.00, which other FactoryTalk software connects to. User passwords are not hashed properly, so CISA says a remote attacker could add users and change connected FactoryTalk data. NVD and CISA score it 10.0; Rockwell released a new version.

Vulnerability summary

CVSS base score

10

Critical severity

EPSS score (FIRST)

4.2%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2020-14516 · Source: NVD

CVSS v3.1 severity rating scale: None 0.0, Low 0.1 to 3.9, Medium 4.0 to 6.9, High 7.0 to 8.9, Critical 9.0 to 10.0
How a CVSS v3.1 base score maps to a severity rating. Source: FIRST CVSS v3.1 specification, section 5.

Affected components

ComponentCPEVersion range
Rockwell Automation FactoryTalk Services Platformcpe:2.3:a:rockwellautomation:factorytalk_services_platform:6.10.00:*:*:*:*:*:*:*6.10.00 and 6.11.00 (NVD CPE and CISA ICSA-21-054-01); fix: the new FactoryTalk Services Platform release Rockwell published for this issue (Rockwell knowledge base, login required)

What does this mean for affected devices?

The CVE record from CISA says: "In Rockwell Automation FactoryTalk Services Platform Versions 6.10.00 and 6.11.00, there is an issue with the implementation of the SHA-256 hashing algorithm with FactoryTalk Services Platform that prevents the user password from being hashed properly." NVD's Primary score is CVSS v3.1 10.0 (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H), with a CVSS v2 score of 7.5, and CISA's advisory gives the same 10.0 under CVSS v3.0. CISA classifies it as CWE-916, use of password hash with insufficient computational effort. NVD published the record on 2021-03-18 and lists exactly the two versions 6.10.00 and 6.11.00 (NVD, CVE record).

What can an attacker do with CVE-2020-14516?

CISA's ICSA-21-054-01, released on 2021-02-23, says successful exploitation "could allow a remote, unauthenticated attacker to create new users in the FactoryTalk Services Platform administration console". Those users could then modify or delete configuration and application data in other FactoryTalk software connected to the platform. CISA lists the Chemical, Commercial Facilities, Critical Manufacturing, Energy, Government Facilities and Water and Wastewater sectors, worldwide deployment, and notes that Rockwell Automation reported the flaw itself. The advisory states that no known public exploits specifically target it.

How do you fix CVE-2020-14516?

Rockwell Automation has released a new version of FactoryTalk Services Platform and published its own security advisory; both are in Rockwell's knowledge base, which needs a login, and CISA's advisory does not name the fixed version number. In practice:

  • move every system on 6.10.00 or 6.11.00 to the new FactoryTalk Services Platform release, on every server and engineering workstation that runs it;
  • review the user list in the FactoryTalk administration console for accounts nobody created, and reset passwords once the update is in place;
  • keep FactoryTalk servers and engineering stations off the internet and behind firewalls, and use an up-to-date VPN for remote access, as CISA recommends.

Rockwell's controller-side issues are covered in CVE-2021-22681 (Logix controller key bypass) and CVE-2022-1161 (Logix hidden code change), and the Rockwell Logix controller vulnerabilities guide groups the Rockwell advisories. Rolling a vendor update through plants is the subject of the patch management guide, and the weak cryptography fix guide explains how products should store password hashes.

Is CVE-2020-14516 exploited?

CVE-2020-14516 is not in the CISA KEV catalog as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS gives it 0.0424, the 91.80th percentile, in the 2026-11-26 dataset (CISA KEV, FIRST EPSS).

Three signals on every advisory: CVSS says how severe the flaw is, EPSS gives the probability of exploitation in the wild in the next 30 days, and a CISA KEV listing means the flaw has been exploited in the wild
CVSS rates severity, EPSS estimates the likelihood of exploitation, and CISA KEV records exploitation seen in the wild. Source: FIRST EPSS; CISA KEV catalog.
How to fix this class of issueNo dedicated SoftWSP guide covers this weakness class; the fix is usually the vendor patch or firmware update referenced above. Our related guide explains how to plan and verify it: NIST SP 800-40 Rev. 4: enterprise patch management planning, explained.
From advisory to verified fix in four steps: read the advisory, find the affected component in the firmware SBOM, apply the fixed version or vendor mitigation, then re-scan the image to confirm the vulnerable version is gone
Read the advisory, find the component in your firmware SBOM, apply the fix, then re-scan to confirm it.

Evidence

  • NVD (read 2026-11-27): status Modified; published 2021-03-18; NVD Primary CVSS v3.1 10.0 CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H; NVD Primary CVSS v2 7.5; CWE-916 from ICS-CERT; CPE rockwellautomation factorytalk_services_platform 6.10.00 and 6.11.00. — NVD
  • CISA ICSA-21-054-01 CSAF (released 2021-02-23, read 2026-11-27): FactoryTalk Services Platform 6.10.00 and 6.11.00; CWE-916; CVSS v3.0 10.0 AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H; remote unauthenticated attacker could create new users in the administration console, then modify or delete configuration and application data in connected FactoryTalk software; Rockwell released a new version (login required) and a security advisory (login required); sectors Chemical, Commercial Facilities, Critical Manufacturing, Energy, Government Facilities, Water and Wastewater; worldwide; HQ United States; reported by Rockwell Automation; no known public exploits. — CISA ICSA-21-054-01
  • CVE record (checked 2026-11-27): state PUBLISHED, CNA ICS-CERT, published 2021-03-18; the record carries no CNA CVSS metric; affected product Rockwell Automation FactoryTalk Services Platform; reference is the CISA advisory. — CVE.org
  • Not in the CISA KEV catalog, catalog version 2026.11.25, 1,805 entries, checked 2026-11-27. — CISA KEV
  • EPSS 0.0424, percentile 0.91796, dataset 2026-11-26, read 2026-11-27. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. CISA ICSA-21-054-01: Rockwell Automation FactoryTalk Services Platform (CSAF)
  3. CISA ICSA-21-054-01 advisory page
  4. CVE.org record CVE-2020-14516
  5. CISA KEV
  6. FIRST EPSS

Frequently asked questions

Which versions are affected by CVE-2020-14516?

FactoryTalk Services Platform 6.10.00 and 6.11.00, per NVD and CISA ICSA-21-054-01. Other versions are not listed.

Which version fixes CVE-2020-14516?

Rockwell Automation released a new version of FactoryTalk Services Platform; the download and Rockwell's own advisory are in its knowledge base, which needs a login. CISA's advisory does not give the version number.

Why is CVE-2020-14516 scored 10.0?

The attack works over the network without credentials, and the scope is changed: an attacker who adds users to the FactoryTalk platform can alter configuration and application data in other connected FactoryTalk software. NVD and CISA both score it 10.0.

Is CVE-2020-14516 in the CISA KEV catalog?

No, not as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS rates it 0.0424 (91.80th percentile) in the 2026-11-26 dataset, and CISA reported no known public exploits.