Security Advisory

CVE-2023-48364: SIMATIC WinCC RPC Server Denial of Service

Last updated:
  • CVE-2023-48364

CVE-2023-48364 is a denial-of-service flaw in the RPC server of Siemens SIMATIC WinCC, PCS 7 V9.1 and WinCC Runtime Professional. Certain malformed RPC messages from an attacker on the adjacent network trigger a NULL pointer dereference. NVD scores it CVSS v3.1 6.5. Siemens fixed it in WinCC V7.5 SP2 Update 15 and V8.0 Update 4, and says Encrypted Communication completely mitigates it.

Vulnerability summary

CVSS base score

6.5

Medium severity

EPSS score (FIRST)

0.4%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2023-48364 · Source: NVD

CVSS v3.1 severity rating scale: None 0.0, Low 0.1 to 3.9, Medium 4.0 to 6.9, High 7.0 to 8.9, Critical 9.0 to 10.0
How a CVSS v3.1 base score maps to a severity rating. Source: FIRST CVSS v3.1 specification, section 5.

Affected components

ComponentCPEVersion range
Siemens SIMATIC WinCC V7.4, V7.5 and V8.0cpe:2.3:a:siemens:simatic_wincc:*:*:*:*:*:*:*:*V7.4: all versions, no fix; V7.5 before V7.5 SP2 Update 15; V8.0 before V8.0 Update 4 (Siemens SSA-753746). NVD CPEs list WinCC 7.4, 7.5 and 8.0 without update levels
Siemens SIMATIC WinCC Runtime Professional V18 and V19cpe:2.3:a:siemens:simatic_wincc_runtime_professional:*:*:*:*:*:*:*:*V18 before V18 Update 4; V19 before V19 Update 2
Siemens SIMATIC PCS 7 V9.1 with OpenPCS 7, BATCH and Route Control V9.1cpe:2.3:a:siemens:simatic_pcs_7:*:*:*:*:*:*:*:*All versions before V9.1 SP2 UC05; OpenPCS 7, BATCH and Route Control V9.1 follow the PCS 7 V9.1 remediation. NVD CPEs: up to and including 9.1

What does this mean for affected devices?

NVD's description, from Siemens, says the RPC (Remote Procedure Call) implementation in the affected products does "not properly handle certain malformed RPC messages. An attacker could use this vulnerability to cause a denial of service condition in the RPC server." It names OpenPCS 7, SIMATIC BATCH, PCS 7 and Route Control V9.1, WinCC Runtime Professional V18 and V19, and WinCC V7.4, V7.5 and V8.0 (NVD, CVE record).

Which score applies?

NVD's Primary score is CVSS v3.1 6.5 (CVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H): an attacker on the adjacent network, needing no privileges or user interaction, can take down availability. Siemens, the CNA, gives the same CVSS v3.1 6.5 and adds CVSS v4.0 7.1 (CVSS:4.0/AV:A/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N). Siemens classifies the flaw as CWE-476 (NULL pointer dereference); NVD lists no weakness of its own.

What does Siemens say?

Siemens advisory SSA-753746 ("Denial of Service Vulnerabilities in SIMATIC WinCC Affecting Other SIMATIC Software Products", first published 2024-02-13, current version 5 of 2024-09-10) covers CVE-2023-48364, which concerns "malformed" RPC messages, and CVE-2023-48363, which concerns "unorganized" ones, with identical products, scores and fixes. Its summary says the two NULL pointer dereferences "could allow an attacker to cause a persistent denial of service condition in the RPC Server of these products".

The fixes, each "or later version", are WinCC V7.5 SP2 Update 15 and V8.0 Update 4; WinCC Runtime Professional V18 Update 4 and V19 Update 2; and PCS 7 V9.1 SP2 UC05, which also covers OpenPCS 7, BATCH and Route Control V9.1. Version 3 corrected the WinCC V8.0 fix from "SP4" to "Update 4". WinCC V7.4 has no fix. The workaround, added in version 2, applies to every affected product: make WinCC, WinCC Runtime Professional and PCS 7 stations communicate over encrypted channels by activating "Encrypted Communication", which Siemens says "completely mitigates the vulnerability".

What does CISA say?

CISA advisory ICSA-24-046-12 (CSAF), "Siemens SIMATIC WinCC, OpenPCS", republishes Siemens' scores, CWE-476 and the same product and fix list, with five revisions matching the Siemens versions. In the CVE record, CISA's ADP assessment rates exploitation "none", automatable "no" and technical impact "partial".

What should a WinCC or PCS 7 owner do?

  1. Turn on Encrypted Communication on every WinCC, Runtime Professional and PCS 7 station, and check projects upgraded from older versions where it may be off.
  2. Install WinCC V7.5 SP2 Update 15, V8.0 Update 4, Runtime Professional V18 Update 4 or V19 Update 2, or PCS 7 V9.1 SP2 UC05.
  3. Move stations off WinCC V7.4, which has no fix, and keep the RPC traffic inside the control network cell.

The Siemens WinCC and PCS 7 guide explains the role of Encrypted Communication across WinCC advisories. CVE-2023-48363 is the second RPC flaw from the same advisory, CVE-2019-10922 is the code execution flaw the same setting closes, and CVE-2019-19282 is an older WinCC denial of service. The guide to fixing memory corruption in embedded firmware covers NULL pointer dereferences.

CVE-2023-48364 is not in the CISA KEV catalog as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS gives it 0.00403, a percentile of 26.1, in the 2026-11-27 dataset (CISA KEV, FIRST EPSS).

Three signals on every advisory: CVSS says how severe the flaw is, EPSS gives the probability of exploitation in the wild in the next 30 days, and a CISA KEV listing means the flaw has been exploited in the wild
CVSS rates severity, EPSS estimates the likelihood of exploitation, and CISA KEV records exploitation seen in the wild. Source: FIRST EPSS; CISA KEV catalog.
How to fix this class of issueThis advisory's weakness class is Memory corruption. Our practical guide covers how to detect, fix, verify and disclose it: How to fix memory corruption in embedded firmware.
From advisory to verified fix in four steps: read the advisory, find the affected component in the firmware SBOM, apply the fixed version or vendor mitigation, then re-scan the image to confirm the vulnerable version is gone
Read the advisory, find the component in your firmware SBOM, apply the fix, then re-scan to confirm it.

Evidence

  • NVD (read 2026-11-28): status Modified; published 2024-02-13; NVD Primary CVSS v3.1 6.5 CVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H; no NVD CWE (Siemens CWE-476 only); CPEs openpcs_7, simatic_batch, simatic_pcs_7 and simatic_route_control up to and including 9.1, simatic_wincc 7.4, 7.5, 8.0, simatic_wincc_runtime_professional up to 18 and 19. — NVD
  • Siemens SSA-753746 CSAF V5, 2024-09-10 (read 2026-11-28): CVSS v3.1 6.5, CVSS v4.0 7.1, CWE-476; per-product fixes; no fix for WinCC V7.4; Encrypted Communication workaround completely mitigates; V8.0 fix corrected from SP4 to Update 4 in V3. — Siemens ProductCERT SSA-753746
  • CISA ICSA-24-046-12 CSAF (read 2026-11-28): CVSS v3.1 6.5, CWE-476, same products and fixes, five revisions to 2024-09-10. — CISA ICSA-24-046-12
  • CVE record (read 2026-11-28): state PUBLISHED, assigner siemens, CNA CVSS v3.1 6.5 and v4.0 7.1, CWE-476; CISA-ADP SSVC exploitation none, automatable no, technical impact partial. — CVE.org
  • Not in the CISA KEV catalog, catalog version 2026.11.27, 1,808 entries, checked 2026-11-28. — CISA KEV
  • EPSS 0.00403, percentile 0.26116, dataset 2026-11-27, read 2026-11-28. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. Siemens SSA-753746: Denial of Service Vulnerabilities in SIMATIC WinCC Affecting Other SIMATIC Software Products
  3. CISA ICSA-24-046-12: Siemens SIMATIC WinCC, OpenPCS
  4. CISA ICSA-24-046-12 CSAF (machine-readable advisory)
  5. CVE record CVE-2023-48364 (CVE Services JSON)
  6. CISA KEV
  7. FIRST EPSS

Frequently asked questions

Which versions fix CVE-2023-48364?

Siemens SSA-753746 lists WinCC V7.5 SP2 Update 15 and V8.0 Update 4, WinCC Runtime Professional V18 Update 4 and V19 Update 2, and PCS 7 V9.1 SP2 UC05 for PCS 7, OpenPCS 7, BATCH and Route Control V9.1, each or later.

Does Encrypted Communication stop it?

Yes. Siemens says activating Encrypted Communication in WinCC and PCS 7 completely mitigates the vulnerability, and lists it as the workaround for every affected product, including WinCC V7.4, which has no fix.

How does CVE-2023-48364 differ from CVE-2023-48363?

Both are NULL pointer dereferences in the same RPC server with the same scores, products and fixes in SSA-753746. Siemens describes CVE-2023-48364 as triggered by malformed RPC messages, and CVE-2023-48363 by unorganized ones.

Is CVE-2023-48364 in the CISA KEV catalog?

No, not as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS rates it 0.00403 (percentile 26.1) in the 2026-11-27 dataset.