Security Advisory

CVE-2019-19282: WinCC and PCS 7 Encrypted Comms DoS

Last updated:
  • CVE-2019-19282

CVE-2019-19282 is a denial-of-service flaw in Siemens SIMATIC WinCC, PCS 7 and SIMATIC NET PC Software that works when encrypted communication is enabled. Crafted messages from an attacker with network access, needing no privileges, make the system unavailable. NVD's Primary score is CVSS v2 7.1; Siemens scores CVSS v3.1 7.5. Fixes include WinCC V7.4 SP1 Update 14, V7.5 SP1 Update 1 and PCS 7 V9.0 SP3.

Vulnerability summary

CVSS base score

7.1

High severity

EPSS score (FIRST)

1.3%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2019-19282 · Source: NVD

CVSS v3.1 severity rating scale: None 0.0, Low 0.1 to 3.9, Medium 4.0 to 6.9, High 7.0 to 8.9, Critical 9.0 to 10.0
How a CVSS v3.1 base score maps to a severity rating. Source: FIRST CVSS v3.1 specification, section 5.

Affected components

ComponentCPEVersion range
Siemens SIMATIC WinCC V7.3 to V7.5cpe:2.3:a:siemens:simatic_wincc:*:*:*:*:*:*:*:*V7.3: all versions, no fix; V7.4 before V7.4 SP1 Update 14; V7.5 before V7.5 SP1 Update 1 (Siemens SSA-270778)
Siemens SIMATIC WinCC (TIA Portal) V13 to V16cpe:2.3:a:siemens:simatic_wincc:*:*:*:*:*:*:*:*V13 before V13 SP2; V14 before V14 SP1 Update 10; V15.1 before V15.1 Update 5; V16 before V16 Update 1
Siemens SIMATIC PCS 7 with OpenPCS 7, BATCH and Route Controlcpe:2.3:a:siemens:simatic_pcs_7:*:*:*:*:*:*:*:*PCS 7 V8.1 and its add-ons: no fix; PCS 7 V8.2: update to V8.2 SP1, then WinCC V7.4 SP1 Update 14; BATCH V8.2 before Update 12; PCS 7, OpenPCS 7, BATCH and Route Control V9.0 before PCS 7 V9.0 SP3
Siemens SIMATIC NET PC Softwarecpe:2.3:a:siemens:simatic_net_pc:*:*:*:*:*:*:*:*V14 before V14 SP1 Update 14; V15: all versions, no fix; V16 before V16 Update 1

What does this mean for affected devices?

NVD's description, from Siemens, says: "Through specially crafted messages, when encrypted communication is enabled, an attacker with network access could use the vulnerability to compromise the availability of the system by causing a Denial-of-Service condition. Successful exploitation requires no system privileges and no user interaction." It names OpenPCS 7, SIMATIC BATCH, SIMATIC NET PC Software, PCS 7, Route Control and WinCC, including WinCC in TIA Portal V13 to V16 (NVD, CVE record).

Which score applies?

NVD's only Primary metric is CVSS v2 7.1 (AV:N/AC:M/Au:N/C:N/I:N/A:C), so this page uses 7.1 as the headline score. NVD also shows its own CVSS v3.1 7.5 (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H), but labels that metric Secondary. Siemens, the CNA, scores CVSS v3.1 7.5 with the same base vector plus E:P/RL:O/RC:C. Siemens classifies the flaw as CWE-131 (incorrect calculation of buffer size); NVD's own weakness entry is NVD-CWE-noinfo.

What does Siemens say?

Siemens advisory SSA-270778 ("Denial-of-Service Vulnerability in SIMATIC PCS 7, SIMATIC WinCC and SIMATIC NET PC Software", first published 2020-02-11, current version 9 of 2023-04-11) lists these fixes, each "or later version": WinCC V7.4 SP1 Update 14 and V7.5 SP1 Update 1; WinCC (TIA Portal) V13 SP2, V14 SP1 Update 10, V15.1 Update 5 and V16 Update 1; SIMATIC NET PC Software V14 SP1 Update 14 and V16 Update 1; PCS 7 V9.0 SP3, which also covers OpenPCS 7, BATCH and Route Control V9.0; PCS 7 V8.2 SP1 followed by WinCC V7.4 SP1 Update 14; and BATCH V8.2 Update 12. For OpenPCS 7 and Route Control V8.2, the flaw is fixed when WinCC V7.4 SP1 Update 14 or later is installed on the same system.

Siemens lists no fix for WinCC V7.3, PCS 7 V8.1, OpenPCS 7 V8.1, BATCH V8.1, Route Control V8.1 and SIMATIC NET PC Software V15. For every affected product its mitigation is to "use VPN for protecting network communication between cells". The version history shows the fixes arriving over three years, from SIMATIC NET PC Software in March 2020 to BATCH V8.2 in April 2023.

What does CISA say?

CISA advisory ICSA-20-042-06 (CSAF), "Siemens SIMATIC PCS 7, SIMATIC WinCC, and SIMATIC NET PC (Update G)", republishes Siemens' CVSS v3.1 7.5, CWE-131 and the same product and fix list, with nine revisions matching the Siemens versions.

What should a WinCC or PCS 7 owner do?

  1. List every WinCC, PCS 7, BATCH, Route Control, OpenPCS 7 and SIMATIC NET PC installation with its exact Update level.
  2. Install the fixed update for each line; schedule the move off WinCC V7.3, PCS 7 V8.1 and NET PC V15, which have no fix.
  3. Keep Encrypted Communication on (it closes other WinCC flaws), and protect the traffic between cells with a VPN as Siemens advises.

The Siemens WinCC and PCS 7 guide explains why Encrypted Communication is both a fix and, here, the precondition for a denial of service. CVE-2019-10922 is the flaw that setting closes, CVE-2018-4832 is an earlier WinCC and PCS 7 denial of service, and CVE-2023-48363 is a later RPC denial of service. The guide to fixing memory corruption in embedded firmware covers buffer size errors like CWE-131.

CVE-2019-19282 is not in the CISA KEV catalog as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS gives it 0.01344, a percentile of 71.5, in the 2026-11-27 dataset (CISA KEV, FIRST EPSS).

Three signals on every advisory: CVSS says how severe the flaw is, EPSS gives the probability of exploitation in the wild in the next 30 days, and a CISA KEV listing means the flaw has been exploited in the wild
CVSS rates severity, EPSS estimates the likelihood of exploitation, and CISA KEV records exploitation seen in the wild. Source: FIRST EPSS; CISA KEV catalog.
How to fix this class of issueThis advisory's weakness class is Memory corruption. Our practical guide covers how to detect, fix, verify and disclose it: How to fix memory corruption in embedded firmware.
From advisory to verified fix in four steps: read the advisory, find the affected component in the firmware SBOM, apply the fixed version or vendor mitigation, then re-scan the image to confirm the vulnerable version is gone
Read the advisory, find the component in your firmware SBOM, apply the fix, then re-scan to confirm it.

Evidence

  • NVD (read 2026-11-28): status Modified; published 2020-03-10; NVD Primary CVSS v2 7.1 AV:N/AC:M/Au:N/C:N/I:N/A:C; NVD CVSS v3.1 7.5 labelled Secondary; NVD weakness NVD-CWE-noinfo (Secondary); 44 CPE entries for openpcs_7, simatic_batch, simatic_net_pc, simatic_pcs_7, simatic_route_control and simatic_wincc. — NVD
  • Siemens SSA-270778 CSAF V9, 2023-04-11 (read 2026-11-28): CVSS v3.1 7.5 AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H/E:P/RL:O/RC:C, CWE-131; per-product fixes, products with no fix, VPN mitigation for all products. — Siemens ProductCERT SSA-270778
  • CISA ICSA-20-042-06 CSAF (read 2026-11-28): Update G, CVSS v3.1 7.5, CWE-131, same products and fixes, nine revisions to 2023-04-11. — CISA ICSA-20-042-06
  • CVE record (read 2026-11-28): state PUBLISHED, assigner siemens, CNA CVSS v3.1 7.5, CWE-131. — CVE.org
  • Not in the CISA KEV catalog, catalog version 2026.11.27, 1,808 entries, checked 2026-11-28. — CISA KEV
  • EPSS 0.01344, percentile 0.7154, dataset 2026-11-27, read 2026-11-28. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. Siemens SSA-270778: Denial-of-Service Vulnerability in SIMATIC PCS 7, SIMATIC WinCC and SIMATIC NET PC Software
  3. CISA ICSA-20-042-06: Siemens SIMATIC PCS 7, SIMATIC WinCC, and SIMATIC NET PC
  4. CISA ICSA-20-042-06 CSAF (machine-readable advisory)
  5. CVE record CVE-2019-19282 (CVE Services JSON)
  6. CISA KEV
  7. FIRST EPSS

Frequently asked questions

Which WinCC versions fix CVE-2019-19282?

Siemens SSA-270778 lists WinCC V7.4 SP1 Update 14 and V7.5 SP1 Update 1, and for WinCC in TIA Portal V13 SP2, V14 SP1 Update 10, V15.1 Update 5 and V16 Update 1, each or later.

Should I switch off Encrypted Communication to avoid it?

No. Siemens does not suggest that, and the setting is the fix or mitigation for other WinCC flaws such as CVE-2019-10922. Siemens' mitigation is to protect communication between cells with a VPN and to install the updates.

Which products have no fix?

WinCC V7.3, PCS 7 V8.1 with OpenPCS 7, BATCH and Route Control V8.1, and SIMATIC NET PC Software V15. Siemens marks them as having no fix, so moving to a supported line is the remedy.

Why does this page show 7.1 when Siemens says 7.5?

NVD's only Primary metric is CVSS v2 7.1. NVD's v3.1 7.5 is labelled Secondary, and 7.5 is also Siemens' CNA score, so both numbers are shown with their source.

Is CVE-2019-19282 in the CISA KEV catalog?

No, not as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS rates it 0.01344 (percentile 71.5) in the 2026-11-27 dataset.