CVE-2023-29155 is a missing authentication flaw in the INEA ME RTU, a remote terminal unit from Slovenia used in energy, water and transportation. Firmware 3.36b and earlier does not require authentication for the root account on the device's host system, so an attacker can gain admin-level access. NVD and CISA score it 9.8; firmware 3.37 fixes it.
Vulnerability summary
CVSS base score
9.8
Critical severity
EPSS score (FIRST)
1.0%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2023-29155 · Source: NVD
Affected components
| Component | CPE | Version range |
|---|---|---|
| INEA ME RTU | cpe:2.3:o:inea:me_rtu_firmware:*:*:*:*:*:*:*:* | firmware 3.36b and earlier (CISA ICSA-23-304-02; NVD: before 3.37); fix: firmware 3.37 |
What does this mean for affected devices?
The CVE record from CISA says: "Versions of INEA ME RTU firmware 3.36b and prior do not require authentication to the "root" account on the host system of the device. This could allow an attacker to obtain admin-level access to the host system." NVD's Primary score and CISA's score are both 9.8 (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H). NVD maps it to CWE-287, improper authentication; CISA's advisory uses CWE-306, missing authentication for a critical function. NVD published the record on 2023-11-20 and its configuration covers ME RTU firmware before 3.37 (NVD, CVE record).
Which INEA RTUs are affected?
CISA's ICSA-23-304-02, released on 2023-10-31, lists the ME RTU on firmware 3.36b and earlier. CISA names the Energy, Water and Wastewater, and Transportation sectors and worldwide deployment, with INEA headquartered in Slovenia. Floris Hendriks of Radboud University reported the issues. The same advisory carries CVE-2023-35762, an OS command injection in the same firmware (CISA 9.9, NVD 9.8); CISA's summary is that exploitation could allow remote code execution.
How do you fix CVE-2023-29155?
INEA's remedy in the CISA advisory is firmware 3.37 for the ME RTU. The product page CISA linked for the download now redirects to INEA's general home page, so ask INEA support for the 3.37 image if it is not already in your engineering archive. Until every RTU runs 3.37:
- keep the RTU unreachable from the internet and from business networks, behind a firewall;
- use an up-to-date VPN when remote access to the outstation is needed, and remember the VPN is only as secure as the connected devices;
- check RTU inventories for 3.36b or older builds, since the host root account is the whole device.
Other RTU authentication flaws on this site are CVE-2023-40151 in Red Lion SixTRAK and VersaTRAK and CVE-2023-1935 in Emerson ROC800. The authentication bypass fix guide covers the firmware side, and the small manufacturers OT/ICS guide the network side.
Is CVE-2023-29155 exploited?
CVE-2023-29155 is not in the CISA KEV catalog as of 2026-11-26 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS gives it 0.00995, the 61.51th percentile, in the 2026-11-25 dataset (CISA KEV, FIRST EPSS). CISA's advisory states that no known public exploits specifically target these vulnerabilities.
Evidence
- NVD (read 2026-11-26): status Modified; published 2023-11-20; NVD Primary CVSS v3.1 9.8 CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H, ICS-CERT Secondary 9.8; CWE-287 (NVD); CPE inea me_rtu_firmware before 3.37. — NVD
- CISA ICSA-23-304-02 CSAF (released 2023-10-31, read 2026-11-26): CWE-306, CVSS 9.8; ME RTU <=3.36b; vendor fix firmware 3.37; sibling CVE-2023-35762 CWE-78 9.9; sectors Energy, Water and Wastewater, Transportation; worldwide; HQ Slovenia; reported by Floris Hendriks, Radboud University; no known public exploits. — CISA ICSA-23-304-02
- CVE record (checked 2026-11-26): state PUBLISHED, CNA ICS-CERT, published 2023-11-20, CNA CVSS v3.1 9.8; affected ME RTU <=3.36b; solution firmware 3.37. — CVE.org
- The INEA ME RTU product URL named in the CISA advisory redirected to the INEA home page when fetched on 2026-11-26. — INEA website
- Not in the CISA KEV catalog, catalog version 2026.11.25, 1,805 entries, checked 2026-11-26. — CISA KEV
- EPSS 0.00995, percentile 0.61508, dataset 2026-11-25, read 2026-11-26. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
Which firmware fixes CVE-2023-29155?
INEA ME RTU firmware 3.37. Versions 3.36b and earlier are affected (CISA ICSA-23-304-02).
What can an attacker do with this flaw?
The root account on the RTU's host system needs no authentication, so an attacker who reaches the device can get admin-level access to the host, which is full control of the outstation.
What else does ICSA-23-304-02 cover?
CVE-2023-35762, an OS command injection in the same ME RTU firmware (CISA 9.9, NVD 9.8). Firmware 3.37 is the fix for both.
Is CVE-2023-29155 in the CISA KEV catalog?
No, not as of 2026-11-26 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS rates it 0.00995 (61.51th percentile) in the 2026-11-25 dataset.