CVE-2023-32202 is an improper authentication flaw in the Walchem Intuition 9 water treatment controller. Before firmware 4.21 the controller stores login credentials in a form that an attacker who obtains them can replay as-is to log in. NVD scores it 8.8 and CISA, the CNA, 6.5. Walchem fixed it in firmware 4.21, and later releases keep the fix.
Vulnerability summary
CVSS base score
8.8
High severity
EPSS score (FIRST)
0.8%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2023-32202 · Source: NVD
Affected components
| Component | CPE | Version range |
|---|---|---|
| Walchem Intuition 9 water treatment controller | cpe:2.3:o:walchem:intuition_9_firmware:*:*:*:*:*:*:*:* | firmware before 4.21 (CISA ICSA-23-229-04, NVD); fix: 4.21 or later (Walchem lists 4.35 as the current Intuition-9 release as of 2026-11-26) |
What does this mean for affected devices?
The CVE record from CISA says: "Walchem Intuition 9 firmware versions prior to v4.21 are vulnerable to improper authentication. Login credentials are stored in a format that could allow an attacker to use them as-is to login and gain access to the device." CISA classifies it as CWE-287, improper authentication. NVD's Primary score is 8.8 (CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H); CISA, the CNA, scores 6.5 (CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:N/A:N), counting only the confidentiality impact. Both require a low-privileged account. NVD published the record on 2023-08-23 and its configuration covers Intuition 9 firmware before 4.21 (NVD, CVE record).
Which Walchem controllers are affected?
CISA's ICSA-23-229-04, released on 2023-08-17 (CSAF file), covers the Intuition 9 on firmware before 4.21, in the Water and Wastewater Systems sector and deployed worldwide; Walchem is a United States company. Noam Moshe of Claroty Team82 reported the flaws. The advisory has a second CVE: CVE-2023-38422, missing authentication on some API routes of the management web server that could let an attacker download and export sensitive data (NVD 7.5). CISA's summary is that exploitation could let an attacker download and export sensitive data or log in directly to a device.
Which firmware fixes CVE-2023-32202?
Walchem recommends upgrading every Intuition 9 to firmware 4.21 or later. Walchem's Intuition-9 upgrades page lists what 4.21 changed: lockout after five failed login attempts, a 240-minute maximum network timeout, strong passwords for all network users, better encryption of passwords in the browser, expiring data log download links and other security fixes. As of 2026-11-26 Walchem's software page shows 4.35 as the newest Intuition-9 release, and the upgrades page notes that an early revision can only move to the latest revision. The upgrade runs from a USB flash drive of 32 MB to 16 GB, after checking that the file matches the Product Name in Configuration Settings > Controller Details.
Keep the controller's web interface behind a firewall and off the open internet, and reset user passwords after the upgrade.
A related flaw class, a stored password hash accepted as the password, is CVE-2022-25157 in Mitsubishi MELSEC. A water and wastewater telemetry device with an authentication flaw is CVE-2017-20235 on the ProSoft ICX35-HWC. See the authentication bypass fix guide and the small manufacturers OT/ICS guide.
Is CVE-2023-32202 exploited?
CVE-2023-32202 is not in the CISA KEV catalog as of 2026-11-26 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS gives it 0.00796, the 53.07th percentile, in the 2026-11-25 dataset (CISA KEV, FIRST EPSS).
Evidence
- NVD (read 2026-11-26): status Modified; published 2023-08-23; NVD Primary CVSS v3.1 8.8 CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H; ICS-CERT Secondary 6.5 CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:N/A:N; CWE-287 from ICS-CERT; CPE walchem intuition_9_firmware before 4.21. — NVD
- CISA ICSA-23-229-04 CSAF and advisory page (page release date 2023-08-17; the CSAF initial_release_date field reads 2023-07-21; read 2026-11-26): Intuition 9 <4.21; CWE-287 6.5; sibling CVE-2023-38422 CWE-306 7.5; fix 4.21 or later from walchem.com; Water and Wastewater Systems, worldwide, HQ United States; reported by Noam Moshe, Claroty Team82. — CISA ICSA-23-229-04
- Walchem Intuition-9 upgrades page (read 2026-11-26): version 4.21 added lockout after five failed logins, 240-minute max network timeout, strong passwords for network users, improved password encryption in the browser, expiring data log links, other security improvements; early revisions update only to the latest revision; USB drive 32 MB to 16 GB; match Product Name in Controller Details. Software/Firmware page lists Intuition-9 v4.35. — Walchem
- CVE record (checked 2026-11-26): state PUBLISHED, CNA ICS-CERT, published 2023-08-23, CNA CVSS v3.1 6.5; affected Intuition 9 <4.21; solution 4.21 or later. — CVE.org
- Not in the CISA KEV catalog, catalog version 2026.11.25, 1,805 entries, checked 2026-11-26. — CISA KEV
- EPSS 0.00796, percentile 0.53068, dataset 2026-11-25, read 2026-11-26. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
Which firmware fixes CVE-2023-32202?
Intuition 9 firmware 4.21 or later. Walchem's software page lists 4.35 as the newest Intuition-9 release as of 2026-11-26, and an older controller updates directly to the latest revision.
Why is NVD's score higher than CISA's?
Both need a low-privileged account over the network. CISA rates only confidentiality impact (6.5); NVD also rates integrity and availability impact as high (8.8).
What else did firmware 4.21 change?
According to Walchem it added a lockout after five failed logins, a 240-minute network timeout, strong password rules for network users, better password encryption in the browser and expiring data log download links.
Is CVE-2023-32202 in the CISA KEV catalog?
No, not as of 2026-11-26 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS rates it 0.00796 (53.07th percentile) in the 2026-11-25 dataset.