Security Advisory

CVE-2023-1935: Emerson ROC800 and DL8000 Auth Bypass

Last updated:
  • CVE-2023-1935

CVE-2023-1935 is an authentication bypass in Emerson ROC800-Series remote terminal units and the DL8000 preset controller. An attacker can reach data or take control of the device without valid credentials, or cause a denial of service. NVD and CISA both score it 9.4. Emerson's fixes are firmware 3.91 (ROC800), 1.71 (ROC800L) and 2.60 (DL8000).

Vulnerability summary

CVSS base score

9.4

Critical severity

EPSS score (FIRST)

0.7%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2023-1935 · Source: NVD

Affected components

ComponentCPEVersion range
Emerson ROC809 and ROC827 RTU (ROC800 Series 2)cpe:2.3:o:emerson:roc809_firmware:*:*:*:*:*:*:*:*all versions before 3.91 (CISA ICSA-23-206-03 lists all versions; fix firmware 3.91 or later); Series 1 hardware: replace
Emerson ROC809L and ROC827L RTU (ROC800L Series 2)cpe:2.3:o:emerson:roc809l_firmware:*:*:*:*:*:*:*:*all versions before 1.71 (CISA ICSA-23-206-03 lists all versions; fix firmware 1.71 or later)
Emerson DL8000 preset controller (Series 2)cpe:2.3:o:emerson:dl8000_firmware:*:*:*:*:*:*:*:*all versions before 2.60 (CISA ICSA-23-206-03 lists all versions; fix firmware 2.60 or later); Series 1 hardware: replace

What does this mean for affected devices?

The CVE record from CISA says: "ROC800-Series RTU devices are vulnerable to an authentication bypass, which could allow an attacker to gain unauthorized access to data or control of the device and cause a denial-of-service condition." NVD's Primary score and CISA's score are both CVSS v3.1 9.4 (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:H/A:H). NVD maps it to CWE-287, improper authentication; CISA's advisory uses CWE-305, authentication bypass by primary weakness. The record was published on 2023-08-02 (NVD, CVE record).

Which RTUs are affected and what fixes them?

CISA's ICSA-23-206-03, released on 2023-07-25, lists all versions of the ROC809, ROC827, ROC809L and ROC827L RTUs and the DL8000 preset controller; Emerson itself reported the flaw to CISA. The fixes are firmware updates from the SupportNet portal (login required):

Product Fix
ROC800 Series 2 firmware 3.91 or later
ROC800L Series 2 firmware 1.71 or later
DL8000 Series 2 firmware 2.60 or later
ROC800 Series 1 replace with Series 2 hardware on 3.91 or later
DL8000 Series 1 replace with Series 2 hardware on 2.60 or later

Series 1 ROC800 and DL8000 hardware became obsolete in 2008, so it gets no firmware fix. Emerson asks owners to check the MD5 or SHA256 hash published on SupportNet against the image before installing it, and to follow section 1.11 "Secure Gateway" of the ROC800-Series instruction manual (D301766X012). NVD's configuration lists all firmware versions of the same five models.

How does this relate to the 2023 security update?

Emerson's Security Deployment Guide for ROC800-Series and FloBoss 107 (D301912X012, March 2023) describes the opt-in security released with ROC800 firmware 3.90 and ROC800L firmware 1.70: longer user names and passwords, and no clear-text passwords over the ROC Plus and Liquids protocols once a site opts in. The opt-in cannot be reversed, and third-party SCADA drivers must support it first. The CVE-2023-1935 fixes are the later builds 3.91 and 1.71, so a unit on 3.90 or 1.70 with the opt-in security still needs the update.

The same RTUs carry CVE-2022-30264, file read, write and delete over the ROC protocol, and the SCADA server above them carries CVE-2020-6970. See the Emerson DeltaV, Ovation and ROC guide and the authentication bypass fix guide.

CVE-2023-1935 is not in the CISA KEV catalog as of 2026-11-23 (catalog version 2026.11.20, 1,790 entries). FIRST EPSS gives it 0.00683, the 53.5th percentile, in the 2026-11-22 dataset (CISA KEV, FIRST EPSS).

How to fix this class of issueThis advisory's weakness class is Authentication bypass. Our practical guide covers how to detect, fix, verify and disclose it: How to fix authentication bypass in embedded firmware.

Evidence

  • NVD (read 2026-11-23): status Modified; published 2023-08-02; NVD Primary CVSS v3.1 9.4 CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:H/A:H, ICS-CERT Secondary 9.4; CWE-287 (NVD); CPE roc809, roc827, roc809l, roc827l, dl8000 firmware all versions. — NVD
  • CISA ICSA-23-206-03 CSAF (released 2023-07-25, read 2026-11-23): CWE-305, CVSS 9.4; affected ROC809, ROC827, ROC809L, ROC827L, DL8000 all versions; fixes ROC800 Series 2 3.91, ROC800L Series 2 1.71, DL8000 Series 2 2.60 via SupportNet; Series 1 obsolete since 2008, replace hardware; validate MD5/SHA256; manual D301766X012 section 1.11 Secure Gateway; reported by Emerson. — CISA ICSA-23-206-03
  • Emerson D301912X012 (March 2023, read 2026-11-23): opt-in security in ROC800 firmware 3.90, ROC800L 1.70, ROCLINK 800 2.71; usernames 3-30, passwords 8-32 characters; no clear-text passwords via ROC Plus and Liquids protocols after opt-in; opt-in irreversible; confirm third-party SCADA/HMI support first. — Emerson Security Deployment Guide
  • CVE record (checked 2026-11-23): state PUBLISHED, CNA ICS-CERT, published 2023-08-02, CNA CVSS v3.1 9.4. — CVE.org
  • Not in the CISA KEV catalog, catalog version 2026.11.20, 1,790 entries, checked 2026-11-23. — CISA KEV
  • EPSS 0.00683, percentile 0.53462, dataset 2026-11-22, read 2026-11-23. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. CISA ICSA-23-206-03: Emerson ROC800 Series RTU and DL8000 Preset Controller (CSAF)
  3. Emerson Security Deployment Guide for ROC800-Series and FloBoss 107 (D301912X012)
  4. CVE.org record CVE-2023-1935
  5. CISA KEV
  6. FIRST EPSS

Frequently asked questions

Which firmware fixes CVE-2023-1935?

ROC800 Series 2 firmware 3.91 or later, ROC800L Series 2 firmware 1.71 or later and DL8000 Series 2 firmware 2.60 or later, from Emerson SupportNet (CISA ICSA-23-206-03).

What about Series 1 ROC800 and DL8000 units?

They get no firmware fix. Series 1 hardware became obsolete in 2008, and Emerson's advice is to replace it with Series 2 hardware running the fixed firmware.

How do I confirm a firmware image is genuine before loading it?

Emerson publishes MD5 and SHA256 hashes on SupportNet. Compare the hash of the downloaded image with the published value before you install it on the RTU.

Is CVE-2023-1935 in the CISA KEV catalog?

No, not as of 2026-11-23 (catalog version 2026.11.20, 1,790 entries). FIRST EPSS rates it 0.00683 (53.5th percentile) in the 2026-11-22 dataset.