Security Advisory

CVE-2023-27396: OMRON FINS Plaintext, No Authentication

Last updated:
  • CVE-2023-27396

CVE-2023-27396 covers two design properties of OMRON's FINS protocol: plaintext communication and no authentication, so anyone who can reach FINS can read traffic, run any command or read system information on SYSMAC CS, CJ, CP, NJ, NX1P, NX102 and NX7 Database Connection CPU Units. NVD scores it 9.8. OMRON does not intend to revise FINS; the defence is disabling FINS (NJ/NX1P/NX102 Ver.1.49, NX7 Ver.1.29) or restricting access and enabling write protection.

Vulnerability summary

CVSS base score

9.8

Critical severity

EPSS score (FIRST)

1.4%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2023-27396 · Source: NVD

Affected components

ComponentCPEVersion range
OMRON SYSMAC CS-series (NVD CPE lists CS1W communication units such as CS1W-ETN21, CS1W-EIP21, CS1W-CLK)cpe:2.3:o:omron:cs1w-etn21_firmware:*:*:*:*:*:*:*:*All versions (JVNTA#91513661); no protocol fix as of 2026-11-19
OMRON SYSMAC CJ-series CPU Units (NVD CPE lists CJ2M and CJ2H CPUs)cpe:2.3:o:omron:cj2m-cpu35_firmware:-:*:*:*:*:*:*:*All versions (JVNTA#91513661); no protocol fix as of 2026-11-19
OMRON SYSMAC CP-series CPU Units (NVD CPE lists CP1E, CP1H, CP1L, CP2E and CP1W/CP2W option units)cpe:2.3:o:omron:cp1l-em40dr-d_firmware:-:*:*:*:*:*:*:*All versions (JVNTA#91513661); no protocol fix as of 2026-11-19
OMRON SYSMAC NJ-series CPU Unitscpe:2.3:o:omron:nj501-1300_firmware:-:*:*:*:*:*:*:*All versions (JVNTA#91513661); FINS can be disabled from Ver.1.49
OMRON SYSMAC NX1P-series and NX102-series CPU Unitscpe:2.3:o:omron:nx102-1200_firmware:-:*:*:*:*:*:*:*All versions (JVNTA#91513661); FINS can be disabled from Ver.1.49
OMRON SYSMAC NX7 Database Connection CPU Units (NX701-1620/1720)cpe:2.3:o:omron:nx701-1720_firmware:*:*:*:*:*:*:*:*Ver.1.16 or later (CVE record and NVD); all versions (JVNTA#91513661 after its 2023-09-19 update); FINS can be disabled from Ver.1.29

What does this mean for affected devices?

CVE-2023-27396 is the identifier OMRON and JPCERT/CC use for two design properties of FINS (Factory Interface Network Service), OMRON's message protocol for reading and writing controller data: (1) plaintext communication and (2) no authentication required. The CVE record states that when FINS messages are intercepted, the contents may be retrieved, and when arbitrary FINS messages are injected, "any commands may be executed on, or the system information may be retrieved from, the affected device." NVD's Primary score is CVSS v3.1 9.8 (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H) with CWE-306 (missing authentication for critical function). The record was published on 2023-06-19 (NVD, CVE record).

Why is FINS insecure by design?

JPCERT/CC's technical note JVNTA#91513661, written by Omron and JPCERT/CC, published on 2023-04-17 and updated on 2023-09-19, says FINS was designed on the assumption that the network is closed inside the device, the production line or the factory, and "does not provide any encryption, data verification, nor authentication functions." Encrypted communication is not defined, so messages can be read and alterations cannot be detected (CWE-319, CWE-345). Authentication is not defined, so attacks from malicious devices cannot be detected (CWE-290, CWE-294, CWE-306, CWE-345, CWE-400, CWE-412, CWE-799). FINS commands cover I/O memory, parameter and program area read and write, operating mode changes, access-right management, file operations and forced set/reset, so a host that can reach a controller's FINS service can do all of these.

How severe is it, and who scored it?

NVD and CISA's ADP container both give 9.8 with the same vector: network attack, low complexity, no privileges, no user interaction, high impact on confidentiality, integrity and availability. The CNA is JPCERT/CC; its record carries the problem type "Insecure Design" and no CVSS score. CISA's SSVC entry (2024-12-24) reads exploitation none, automatable yes, technical impact total. CVE-2023-27396 is not in the CISA KEV catalog as of 2026-11-19 (catalog version 2026.11.18, 1,786 entries), and that catalog holds no OMRON entry at all. FIRST EPSS gives it 0.01374, the 72.6th percentile, in the 2026-11-18 dataset (CISA KEV, FIRST EPSS).

Which OMRON products are affected?

JVNTA#91513661 lists SYSMAC CS-series, CJ-series, CP-series, NJ-series, NX1P-series and NX102-series CPU Units, all versions, and SYSMAC NX7 Database Connection CPU Units. The JVN note says "all versions" for the NX7 Database Connection CPU Units after its 2023-09-19 update; the CVE record and NVD say Ver.1.16 or later. NVD's CPE configuration names individual models: CJ2M and CJ2H CPUs, CP1E, CP1H, CP1L and CP2E CPUs, NJ101, NJ301, NJ501 and NJ-PA/PD controllers, NX1P2 and NX102 CPUs, NX701-1620/1720 from 1.16, plus CS1W communication units (for example CS1W-ETN21 and CS1W-EIP21) and CP1W/CP2W option and expansion units.

Is there a firmware fix?

No firmware adds authentication or encryption to FINS. According to JVNTA#91513661, OMRON does not intend to revise the FINS protocol and asks users to run FINS products in an appropriately protected environment. What firmware does add is the option to switch FINS off: NJ, NX1P and NX102 CPU Units from Ver.1.49 and NX7 Database Connection CPU Units from Ver.1.29. For CS, CJ and CP controllers, the note lists access-source IP restriction, FINS write protection, a PLC protection password and the hardware DIP switch that prohibits program changes, plus firewalling FINS port 9600 off from IT networks, VPN for remote access and regular backups. CISA's ICSA-22-179-02, which JVN references, gives the same password, write protection and DIP switch advice for SYSMAC CS/CJ/CP.

How do these controls fit together on a plant network?

Treat every host that can send to port 9600 as able to control the PLC. Disable FINS on NJ/NX units that do not use it, restrict the rest to the HMIs and the engineering workstation, and enable write protection so that memory and program writes are refused. Our OMRON FINS protocol security guide lists the FINS command codes worth alerting on, and the authentication bypass fix guide covers the class. Specific OMRON CVEs that use the same unauthenticated path are CVE-2022-31207 (unsigned logic download on CS/CJ/CP), CVE-2022-31204 (cleartext PLC password), CVE-2019-18259 (FINS spoofing on CS/CJ) and, for NJ/NX, CVE-2022-33208 and CVE-2022-34151.

How to fix this class of issueThis advisory's weakness class is Authentication bypass. Our practical guide covers how to detect, fix, verify and disclose it: How to fix authentication bypass in embedded firmware.

Evidence

  • NVD (record read 2026-11-19): status Modified; published 2023-06-19T05:15:09.187; NVD Primary CVSS v3.1 9.8 CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H; CISA-ADP Secondary 9.8 same vector; CWE-306 (NVD Primary and CISA-ADP); CPE configuration lists CS1W communication units, CJ2M/CJ2H, CP1E/CP1H/CP1L/CP2E CPUs, CP1W/CP2W units, NJ101/NJ301/NJ501/NJ-PA/NJ-PD, NX1P2, NX102, and NX701-1620/1720 from 1.16; description lists NX7 Database Connection CPU Units Ver.1.16 or later. — NVD
  • JPCERT/CC JVNTA#91513661 (published 2023-04-17, updated 2023-09-19), read 2026-11-19: written by Omron and JPCERT/CC; FINS designed for closed networks with no encryption, data verification or authentication; issue 1 plaintext communication (CWE-319, CWE-345), issue 2 no authentication required (CWE-290, CWE-294, CWE-306, CWE-345, CWE-400, CWE-412, CWE-799); affected CS, CJ, CP, NJ, NX1P, NX102 and NX7 Database Connection CPU Units, all versions; the developer does not intend to revise FINS; FINS can be disabled on NJ/NX1P/NX102 Ver.1.49 or later and NX7 Database Connection Ver.1.29 or later; mitigations: source IP restriction, FINS write protection, PLC protection password, hardware DIP switch, firewall FINS port 9600, VPN, backups; issues treated as CVE-2023-27396. — JPCERT/CC JVNTA#91513661
  • CISA ICSA-22-179-02 CSAF (released 2022-06-28), read 2026-11-19: for SYSMAC CS/CJ/CP Series, Omron recommends the PLC protection password, protection against unauthorized write access, and the hardware DIP switch that prevents unauthorized program changes; referenced by JVNTA#91513661 and the CVE record. It does not list CVE-2023-27396 itself. — CISA CSAF ICSA-22-179-02
  • CVE record (checked 2026-11-19): state PUBLISHED, CNA JPCERT/CC, published 2023-06-19; CNA problem type 'Insecure Design', no CNA CVSS; CISA-ADP CVSS v3.1 9.8, CWE-306, SSVC (2024-12-24) exploitation none, automatable yes, technical impact total; references JVNTA#91513661, OMRON OMSR-2023-003, ICSA-19-346-02, ICSA-20-063-03, ICSA-22-179-02. — CVE.org
  • Not in the CISA KEV catalog, version 2026.11.18 (1,786 entries), checked 2026-11-19; the catalog has no OMRON entry. — CISA KEV
  • EPSS 0.01374, percentile 0.72553, dataset 2026-11-18, read 2026-11-19. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. JPCERT/CC JVNTA#91513661: Security Issues in FINS protocol (written by Omron and JPCERT/CC)
  3. CISA CSAF: ICSA-22-179-02 Omron SYSMAC CS/CJ/CP Series and NJ/NX Series (machine-readable advisory)
  4. CVE.org record CVE-2023-27396 (CNA: JPCERT/CC)
  5. CISA KEV
  6. FIRST EPSS

Frequently asked questions

Is there a firmware update that fixes CVE-2023-27396?

No firmware adds encryption or authentication to FINS, because OMRON does not intend to revise the protocol. NJ, NX1P and NX102 CPU Units from Ver.1.49 and NX7 Database Connection CPU Units from Ver.1.29 can disable FINS where it is unused (per JPCERT/CC JVNTA#91513661).

What can an attacker do over FINS?

Intercepted FINS messages can be read, and injected messages can execute any command on the controller or read its system information. FINS commands include memory and program area read and write, operating mode changes, file operations and forced set/reset (per JVNTA#91513661 and the CVE record).

How do I protect CS, CJ and CP controllers that still need FINS?

Restrict which source IP addresses can reach the controller, block FINS port 9600 at the firewall between IT and control networks, enable FINS write protection, set the PLC protection password and use the hardware DIP switch that prohibits program changes (per JVNTA#91513661 and CISA ICSA-22-179-02).

Why is it scored 9.8 if it is a design property?

An attacker needs only network access to FINS: no privileges, no user interaction and low complexity, with high impact on confidentiality, integrity and availability. NVD and CISA's ADP both score CVSS v3.1 9.8; CISA's SSVC rates it automatable with total technical impact (per NVD and the CVE record).

Is CVE-2023-27396 known to be exploited?

It is not in the CISA KEV catalog as of 2026-11-19 (catalog version 2026.11.18, 1,786 entries), and CISA's SSVC entry reads exploitation none. FIRST EPSS gives it 0.01374, the 72.6th percentile, in the 2026-11-18 dataset (per CISA KEV, the CVE record and FIRST EPSS).