**CVE-2023-23585** is a heap overflow in the Honeywell Experion Server and Console Station, published on 2023-07-13, triggered by a specially crafted message for a specific configuration operation and causing a denial of service. NVD scores it 7.5, while Honeywell and CISA score it 9.8. CISA recommends the Experion R520.2 release.
Vulnerability summary
CVSS base score
7.5
High severity
EPSS score (FIRST)
0.7%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2023-23585 · Source: NVD
Affected components
| Component | CPE | Version range |
|---|---|---|
| Honeywell Experion Server, Experion Station, Engineering Station, Direct Station | cpe:2.3:a:honeywell:experion_server:*:*:*:*:*:*:*:* | Experion Server and Station 501.1 to 501.6 HF8, 510.1 to 510.2 HF12, 511.1 to 511.5 TCU3, 520.1 to 520.1 TCU4, 520.2 to 520.2 TCU2; Engineering and Direct Station 510.1 to 511.5 TCU3, 520.1 to 520.1 TCU4, 520.2 to 520.2 TCU2 (CVE record; NVD CPE) |
| Honeywell Experion PKS, Experion LX and PlantCruise | — | before R520.2 per CISA ICSA-23-194-06; update to R520.2 |
What does this mean for affected devices?
Honeywell, the CNA, describes an "Experion server DoS due to heap overflow occurring during the handling of a specially crafted message for a specific configuration operation". It scores the flaw CVSS 3.1 9.8 (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H), maps it to CWE-787 and lists Experion Server and Station 501.1 to 501.6 HF8, 510.1 to 510.2 HF12, 511.1 to 511.5 TCU3, 520.1 to 520.1 TCU4, 520.2 to 520.2 TCU2; Engineering and Direct Station 510.1 to 511.5 TCU3, 520.1 to 520.1 TCU4, 520.2 to 520.2 TCU2 (CVE record).
NVD's Primary score is 7.5 with vector CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H, rating only availability. It keeps CWE-787, and its configuration lists the four Experion server and station products in the same ranges (NVD).
CISA's ICSA-23-194-06 of 2023-07-13 covers nine Experion CVEs reported by Armis in Experion PKS, Experion LX and PlantCruise before R520.2, and recommends R520.2 for all three, downloaded from Honeywell's support portal. It also asks users to limit access to authorised users and to keep backup files where only authorised users can reach them. Honeywell's product security page lists the advisory as Critical, covering nine CVEs in versions before R520.2. CISA's wording: "Experion Server or Console Station could experience a denial-of-service condition due to a heap overflow during the handling of a specially crafted message for a specific configuration operation", scored 9.8 with CWE-122, heap-based buffer overflow.
A crashed Experion server or station can cost operators their view and control of the plant, even while controllers keep running. Until servers run R520.2, limit which hosts can reach them and keep redundant server pairs in sync.
CVE-2023-23585 is not in the CISA KEV catalog as of 2026-11-22 (catalog version 2026.11.20). FIRST EPSS gives it 0.0065, percentile 52.2, in the 2026-11-21 dataset (CISA KEV, FIRST EPSS).
Our Honeywell Experion and ControlEdge guide lists all nine CVEs from this advisory. CVE-2023-25948 is a configuration-data leak from it, and CVE-2023-24480 is the matching C300 stack overflow.
Evidence
- Honeywell CNA: Experion server DoS from heap overflow on crafted message for a configuration operation; 9.8; CWE-787; server/station ranges. — CVE.org record
- NVD Primary CVSS 3.1 7.5 A:H; CWE-787; CPE experion_server, experion_station, engineering_station, direct_station. — NVD
- ICSA-23-194-06: Experion Server or Console Station heap overflow DoS; 9.8; CWE-122; fix R520.2. — CISA ICSA-23-194-06 (CSAF)
- Honeywell notice table lists ICSA-23-194-06, versions prior to R520.2, 9 CVEs, Critical. — Honeywell product security

Related advisories
Sources
Frequently asked questions
Which Experion components does CVE-2023-23585 affect?
Honeywell and NVD list Experion Server, Experion Station, Engineering Station and Direct Station; CISA names the Experion Server or Console Station (per the CVE record, NVD and CISA ICSA-23-194-06).
Why is CVE-2023-23585 scored 9.8 by CISA and 7.5 by NVD?
Honeywell and CISA rate confidentiality, integrity and availability high. NVD rates only availability high, matching the described denial of service (per NVD).
How do I fix CVE-2023-23585?
CISA recommends updating Experion PKS, Experion LX or PlantCruise to R520.2, available from the Honeywell support portal under Product Documents and Downloads (per CISA ICSA-23-194-06).
Is CVE-2023-23585 exploited in the wild?
It is not in the CISA KEV catalog as of 2026-11-22 (catalog version 2026.11.20). FIRST EPSS gives it 0.0065, percentile 52.2, in the 2026-11-21 dataset (per CISA KEV and FIRST EPSS).
Questions about this page?