**CVE-2023-22435** is a denial-of-service flaw in Honeywell Experion Server, published on 2023-07-13: a specially crafted message can crash the server. It affects Experion PKS, Experion LX and PlantCruise before R520.2, which is the fix. NVD scores it 7.5, Honeywell 7.5 with a different vector, and CISA 9.8.
Vulnerability summary
CVSS base score
7.5
High severity
EPSS score (FIRST)
0.6%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2023-22435 · Source: NVD
Affected components
| Component | CPE | Version range |
|---|---|---|
| Honeywell Experion Server and Experion Station | cpe:2.3:a:honeywell:experion_server:*:*:*:*:*:*:*:* | 501.1 to 501.6 HF8, 510.1 to 510.2 HF12, 511.1 to 511.5 TCU3, 520.1 to 520.1 TCU4, 520.2 to 520.2 TCU2 (NVD CPE, CVE record; experion_station uses the same ranges) |
| Honeywell Engineering Station and Direct Station | cpe:2.3:a:honeywell:engineering_station:*:*:*:*:*:*:*:* | 510.1 to 511.5 TCU3, 520.1 to 520.1 TCU4, 520.2 to 520.2 TCU2 (NVD CPE); Honeywell's record starts Direct Station at 510.5 |
| Honeywell Experion PKS, Experion LX and PlantCruise | — | before R520.2 per CISA ICSA-23-194-06; update to R520.2 |
What does this mean for affected devices?
Honeywell, the CNA, says "Experion server may experience a DoS due to a stack overflow when handling a specially crafted message". Its record is titled "Server bad parsing implementation - stack overflow in server::get_db_path_for_driver", maps the flaw to CWE-697, incorrect comparison, and scores it CVSS 3.1 7.5 with vector AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N. It lists Experion Server and Experion Station 501.1 to 501.6 HF8, 510.1 to 510.2 HF12, 511.1 to 511.5 TCU3, 520.1 to 520.1 TCU4, 520.2 to 520.2 TCU2, plus Engineering Station and Direct Station ranges (CVE record).
NVD's Primary score is also 7.5, but with vector CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H: availability rather than confidentiality, which matches the denial of service in the description. NVD maps it to CWE-787, out-of-bounds write, and its configuration covers experion_server, experion_station, engineering_station and direct_station with the same release ranges (NVD).
CISA's ICSA-23-194-06 of 2023-07-13 covers nine Experion CVEs reported by Armis in Experion PKS, Experion LX and PlantCruise before R520.2, and recommends R520.2 for all three, downloaded from Honeywell's support portal. It also asks users to limit access to authorised users and to keep backup files where only authorised users can reach them. Honeywell's product security page lists the advisory as Critical, covering nine CVEs in versions before R520.2. CISA's text reads "Experion Server may experience a denial-of-service condition due to an incorrect comparison when handling a specially crafted message", scored CVSS 3.0 9.8 (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H) with CWE-697.
An Experion server that stops answering takes operator views, alarms and history with it while controllers keep running their last strategy. Until servers run R520.2, keep the Experion network segment closed to business networks and limit which hosts can send messages to the servers.
CVE-2023-22435 is not in the CISA KEV catalog as of 2026-11-23 (catalog version 2026.11.20). FIRST EPSS gives it 0.0060, percentile 49.7, in the 2026-11-22 dataset (CISA KEV, FIRST EPSS).
Our Honeywell Experion and ControlEdge guide lists all nine CVEs from ICSA-23-194-06. CVE-2023-24474 is a heap overflow in the same server, and CVE-2023-23585 is a server overflow in a configuration operation.
Evidence
- Honeywell CNA: stack overflow when handling a crafted message; title get_db_path_for_driver; CWE-697; 7.5 C:H/I:N/A:N; Server/Station ranges 501.1-520.2 TCU2. — CVE.org record
- NVD Primary CVSS 3.1 7.5 A:H; CWE-787; CPE experion_server, experion_station, engineering_station, direct_station ranges. — NVD
- ICSA-23-194-06 (2023-07-13): Armis; incorrect comparison DoS; 9.8 CVSS 3.0; CWE-697; affected PKS, LX, PlantCruise < R520.2; fix R520.2; backup file access. — CISA ICSA-23-194-06: Honeywell Experion PKS, LX and PlantCruise (CSAF)
- Notice table lists ICSA-23-194-06, Experion PKS, LX and PlantCruise before R520.2, 9 CVEs, Critical. — Honeywell product security

Related advisories
Sources
Frequently asked questions
Which products does CVE-2023-22435 affect?
Honeywell's CVE record and NVD list Experion Server, Experion Station, Engineering Station and Direct Station releases up to 520.2 TCU2. CISA lists Experion PKS, Experion LX and PlantCruise before R520.2 (per the CVE record, NVD and CISA ICSA-23-194-06).
Why do the scores for CVE-2023-22435 differ?
NVD rates it 7.5 for availability only. Honeywell also gives 7.5 but rates confidentiality instead of availability, and CISA gives 9.8 with confidentiality, integrity and availability all high (per NVD, the CVE record and CISA ICSA-23-194-06).
How do I fix CVE-2023-22435?
Update Experion PKS, Experion LX or PlantCruise to R520.2, downloaded from Honeywell's support portal, and keep Experion backup files where only authorised users can reach them (per CISA ICSA-23-194-06).
Is CVE-2023-22435 exploited in the wild?
It is not in the CISA KEV catalog as of 2026-11-23 (catalog version 2026.11.20). FIRST EPSS gives it 0.0060, percentile 49.7, in the 2026-11-22 dataset (per CISA KEV and FIRST EPSS).