**CVE-2023-24474** is a heap overflow in Honeywell Experion Server, published on 2023-07-13: a specially crafted message can cause a denial of service. It affects Experion PKS, Experion LX and PlantCruise before R520.2, which is the fix. NVD and Honeywell score it 7.5, CISA 9.8.
Vulnerability summary
CVSS base score
7.5
High severity
EPSS score (FIRST)
0.7%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2023-24474 · Source: NVD
Affected components
| Component | CPE | Version range |
|---|---|---|
| Honeywell Experion Server and Experion Station | cpe:2.3:a:honeywell:experion_server:*:*:*:*:*:*:*:* | 501.1 to 501.6 HF8, 510.1 to 510.2 HF12, 511.1 to 511.5 TCU3, 520.1 to 520.1 TCU4, 520.2 to 520.2 TCU2 (NVD CPE, CVE record; experion_station uses the same ranges) |
| Honeywell Engineering Station and Direct Station | cpe:2.3:a:honeywell:engineering_station:*:*:*:*:*:*:*:* | 510.1 to 511.5 TCU3, 520.1 to 520.1 TCU4, 520.2 to 520.2 TCU2 (NVD CPE); Honeywell's record starts Direct Station at 510.5 |
| Honeywell Experion PKS, Experion LX and PlantCruise | — | before R520.2 per CISA ICSA-23-194-06; update to R520.2 |
What does this mean for affected devices?
Honeywell, the CNA, says "Experion server may experience a DoS due to a heap overflow which could occur when handling a specially crafted message". Its record is titled "Server deserialization missing boundary checks - heap overflow in communication between server and controller", maps the flaw to CWE-122, heap-based buffer overflow, and scores it CVSS 3.1 7.5 with vector AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N. It lists Experion Server and Experion Station 501.1 to 501.6 HF8, 510.1 to 510.2 HF12, 511.1 to 511.5 TCU3, 520.1 to 520.1 TCU4, 520.2 to 520.2 TCU2, plus Engineering Station and Direct Station ranges (CVE record).
NVD's Primary score is 7.5 with vector CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H, rating availability rather than confidentiality. NVD maps it to CWE-787, out-of-bounds write, and its configuration covers experion_server, experion_station, engineering_station and direct_station with the same release ranges (NVD).
CISA's ICSA-23-194-06 of 2023-07-13 covers nine Experion CVEs reported by Armis in Experion PKS, Experion LX and PlantCruise before R520.2, and recommends R520.2 for all three, downloaded from Honeywell's support portal. It also asks users to limit access to authorised users and to keep backup files where only authorised users can reach them. Honeywell's product security page lists the advisory as Critical, covering nine CVEs in versions before R520.2. CISA's text matches Honeywell's description and is scored CVSS 3.0 9.8 (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H) with CWE-122.
The record title places the flaw in server-to-controller communication, so any host that can reach that path on the Experion network is a possible sender. Until servers run R520.2, keep that segment closed to business networks and limit which hosts can talk to the servers.
CVE-2023-24474 is not in the CISA KEV catalog as of 2026-11-23 (catalog version 2026.11.20). FIRST EPSS gives it 0.0066, percentile 52.6, in the 2026-11-22 dataset (CISA KEV, FIRST EPSS).
Our Honeywell Experion and ControlEdge guide lists all nine CVEs from ICSA-23-194-06. CVE-2023-22435 is another server denial-of-service flaw from it, and CVE-2023-24480 is a C300 stack overflow on messages from the server.
Evidence
- Honeywell CNA: heap overflow handling a crafted message; title server-controller deserialization; CWE-122; 7.5 C:H/I:N/A:N; ranges. — CVE.org record
- NVD Primary CVSS 3.1 7.5 A:H; CWE-787; CPE experion_server, experion_station, engineering_station, direct_station ranges. — NVD
- ICSA-23-194-06 (2023-07-13): Armis; heap overflow DoS; 9.8 CVSS 3.0; CWE-122; PKS, LX, PlantCruise < R520.2; fix R520.2. — CISA ICSA-23-194-06: Honeywell Experion PKS, LX and PlantCruise (CSAF)
- Notice table lists ICSA-23-194-06, Experion PKS, LX and PlantCruise before R520.2, 9 CVEs, Critical. — Honeywell product security

Related advisories
Sources
Frequently asked questions
Which products does CVE-2023-24474 affect?
Honeywell's CVE record and NVD list Experion Server, Experion Station, Engineering Station and Direct Station releases up to 520.2 TCU2. CISA lists Experion PKS, Experion LX and PlantCruise before R520.2 (per the CVE record, NVD and CISA ICSA-23-194-06).
Can CVE-2023-24474 lead to code execution?
Honeywell, NVD and CISA describe only a denial of service. CISA's 9.8 vector rates confidentiality, integrity and availability high, while NVD's 7.5 rates availability only (per the CVE record, NVD and CISA ICSA-23-194-06).
How do I fix CVE-2023-24474?
Update Experion PKS, Experion LX or PlantCruise to R520.2, downloaded from Honeywell's support portal, and limit access to the Experion network to authorised users (per CISA ICSA-23-194-06).
Is CVE-2023-24474 exploited in the wild?
It is not in the CISA KEV catalog as of 2026-11-23 (catalog version 2026.11.20). FIRST EPSS gives it 0.0066, percentile 52.6, in the 2026-11-22 dataset (per CISA KEV and FIRST EPSS).