CVE-2023-1049 is a code injection flaw (CWE-94) in Schneider Electric EcoStruxure Operator Terminal Expert and Pro-face BLUE. When a user loads a crafted project file from the local filesystem, malicious code could run on the engineering workstation. NVD, Schneider and CISA all score it 7.8. Version 3.4 of both products fixes it.
Vulnerability summary
CVSS base score
7.8
High severity
EPSS score (FIRST)
0.4%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2023-1049 · Source: NVD

Affected components
| Component | CPE | Version range |
|---|---|---|
| Schneider Electric EcoStruxure Operator Terminal Expert | cpe:2.3:a:schneider-electric:ecostruxure_operator_terminal_expert:*:*:*:*:*:*:*:* | 3.3 SP1 and prior; fixed in v3.4 |
| Pro-face BLUE | cpe:2.3:a:schneider-electric:pro-face_blue:*:*:*:*:*:*:*:* | 3.3 SP1 and prior; fixed in v3.4 |
What does this mean for affected devices?
Schneider's notice SEVD-2023-164-01 of 13 June 2023 describes "a CWE-94: Improper Control of Generation of Code ('Code Injection') vulnerability" "that could cause execution of malicious code when an unsuspicious user loads a project file from the local filesystem into the HMI." The notice puts the loss of availability, confidentiality and integrity on the workstation where Operator Terminal Expert or the Pro-face BLUE runtime is installed. Schneider credits Daan Keuper and Thijs Alkemade, working with Trend Micro's Zero Day Initiative. CISA republished it as ICSA-23-180-02 on 29 June 2023.
How severe is CVE-2023-1049?
NVD's Primary score is CVSS v3.1 7.8, AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H (NVD). Schneider and CISA reach the same 7.8 with AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H: they model an unprivileged attacker who needs the user to open the file, while NVD models a local user with low privileges. NVD and Schneider agree on CWE-94.
Which versions are affected and what is the fix?
Affected are Operator Terminal Expert 3.3 SP1 and prior and Pro-face BLUE 3.3 SP1 and prior; CISA's advisory names Operator Terminal Expert only. Version 3.4 of each product fixes the flaw. Until then, Schneider's mitigations are to protect project files with the "Set up Password" feature, encrypt stored project files and restrict access to trusted users, exchange files over secure protocols, only open project files from trusted sources and share them only with the encryption feature on, and use the software on a trusted, hardened workstation in a secure network environment.
The Schneider EcoStruxure HMI and SCADA software guide lists every Operator Terminal Expert fix. The earlier project-file flaw CVE-2020-7493 and the DLL-loading flaw CVE-2022-41666 need the same workstation controls. The OT security guide for small manufacturers covers handling project files from contractors.
Is CVE-2023-1049 exploited?
It is not in the CISA KEV catalog as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS gives it 0.0040, the 25th percentile, in the 2026-11-27 dataset (CISA KEV, FIRST EPSS).


Evidence
- NVD (read 2026-11-28): published 2023-06-14, status Modified; NVD Primary CVSS v3.1 7.8 AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H; Schneider Secondary CVSS v3.1 7.8 AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H; CWE-94 (NVD Primary and Schneider); CPE ecostruxure_operator_terminal_expert and pro-face_blue before 3.3, 3.3 and 3.3 sp1. — NVD
- Schneider SEVD-2023-164-01 V1.0 (13 June 2023, PDF and Schneider CSAF read 2026-11-28): affected Operator Terminal Expert 3.3 SP1 and prior and Pro-face BLUE 3.3 SP1 and prior; CVSS v3.1 7.8 PR:N/UI:R; fix v3.4 of each product; mitigations (Set up Password, encrypt project files, secure protocols, trusted sources with encryption feature, secure network, trusted and hardened workstation); credit Daan Keuper and Thijs Alkemade (ZDI). — Schneider Electric
- CISA ICSA-23-180-02 CSAF (2023-06-29): CWE-94, CVSS v3 7.8 AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H; affected Operator Terminal Expert <= 3.3 SP1; vendor fix v3.4. — CISA
- CVE.org record (read 2026-11-28): assigner Schneider Electric, CWE-94, CVSS v3.1 7.8 AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H; affected Operator Terminal Expert and Pro-face BLUE 3.3 SP1 and prior. — CVE.org
- Not in the CISA KEV catalog, catalog version 2026.11.27, 1,808 entries, checked 2026-11-28. — CISA KEV
- EPSS 0.00396, percentile 0.25378, dataset 2026-11-27, read 2026-11-28. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
Which version fixes CVE-2023-1049?
Version 3.4 of EcoStruxure Operator Terminal Expert and of Pro-face BLUE, per Schneider's SEVD-2023-164-01. Versions 3.3 SP1 and earlier are affected.
Is Pro-face BLUE affected even though CISA does not name it?
Yes. CISA's ICSA-23-180-02 lists Operator Terminal Expert only, but Schneider's own notice, NVD's configuration and the CVE.org record all include Pro-face BLUE 3.3 SP1 and prior.
How do I protect project files until I update?
Schneider asks owners to set a project password, encrypt stored project files, limit access to trusted users, use secure protocols for transfer, and open or share project files only from trusted sources with encryption turned on.
Is CVE-2023-1049 in the CISA KEV catalog?
No, not as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS rates it 0.0040, the 25th percentile, in the 2026-11-27 dataset.
Questions about this page?