Security Advisory

CVE-2022-38138: Triangle MicroWorks 61850/ICCP DoS

Last updated:
  • CVE-2022-38138

CVE-2022-38138 is a denial-of-service flaw in Triangle MicroWorks' IEC 61850 and IEC 60870-6 (ICCP/TASE.2) protocol libraries, which other vendors build into their own clients and servers. A remote attacker can make a client or server built on them access uninitialized pointers (CWE-824) and crash. NVD and CISA score it 7.5.

Vulnerability summary

CVSS base score

7.5

High severity

EPSS score (FIRST)

1.0%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2022-38138 · Source: NVD

Affected components

ComponentCPEVersion range
Triangle MicroWorks IEC 61850 Library (C)cpe:2.3:a:trianglemicroworks:iec_61850_software_library:-:*:*:*:*:*:*:*11.2.0 or earlier (CISA ICSA-22-249-01); no fixed version named by CISA
Triangle MicroWorks IEC 61850 Library (C++, C#, Java)cpe:2.3:a:trianglemicroworks:iec_61850_software_library:-:*:*:*:*:*:*:*5.0.1 or earlier (CISA ICSA-22-249-01); no fixed version named by CISA
Triangle MicroWorks IEC 60870-6 (ICCP/TASE.2) Library (C++)cpe:2.3:a:trianglemicroworks:iec_60870-6_software_library:-:*:*:*:*:*:*:*4.4.3 or earlier (CISA ICSA-22-249-01); no fixed version named by CISA

What does this mean for affected devices?

The CVE record, issued by CISA ICS, says the Triangle MicroWorks IEC 61850 Library and 60870-6 (ICCP/TASE.2) Library "are vulnerable to access given to a small number of uninitialized pointers within their code. This could allow an attacker to target any client or server using the affected libraries to cause a denial-of-service condition." CISA published advisory ICSA-22-249-01 on 2022-09-06; the CVE record followed on 2022-10-11 (NVD, CVE record).

How severe is CVE-2022-38138?

NVD and CISA agree: CVSS v3.1 7.5 (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H), network-reachable, no privileges, availability impact only. The weakness is CWE-824 (access of uninitialized pointer). The CISA ADP SSVC entry of 2025-04-16 records exploitation "none", automatable "yes" and technical impact "partial". The ICSA-22-249-01 CSAF names the energy and water and wastewater sectors, credits Vera Mens of Claroty Research, and states that no known public exploits specifically target this vulnerability.

Which libraries and versions are affected?

Library (CISA wording) Affected
TMW IEC 61850 Library, C language 11.2.0 or earlier, any client or server using it
TMW IEC 61850 Library, C++, C# or Java language 5.0.1 or earlier, any client or server using it
TMW IEC 60870-6 (ICCP/TASE.2) Library, C++ language 4.4.3 or earlier, any client or server using it

NVD's CPEs (iec_61850_software_library and iec_60870-6_software_library) carry no version limit, so they match every version. Use the CISA ranges above instead.

Why is this a device problem?

These are protocol libraries, not finished products: the flaw sits in whatever IEC 61850 or ICCP client or server a vendor built on top of them. CISA's wording, "any client or server using the affected libraries", is the reason a single library flaw can reach many product lines, and IEC 61850 and ICCP are the protocols of substations and of links between control centres. CISA names no downstream products, and this page names none either. If you build on these libraries, check the library version in your build. If you operate such equipment, ask each vendor whether their IEC 61850 or ICCP stack is from Triangle MicroWorks and which version it is.

How do you fix or mitigate CVE-2022-38138?

CISA's advisory names no fixed version. Its only vendor remediation is that Triangle MicroWorks "encourages those using the affected library to contact Triangle MicroWorks Support for mitigation guidance and strategies." Library users should get that guidance and move to a version later than those listed above; device owners should get an updated firmware or software release from their product vendor. Meanwhile CISA's general advice applies: keep control system devices off the internet, put them behind firewalls and use secure remote access. For ICCP, allow only the bilateral peers you have an agreement with. Our ICCP/TASE.2 security guide and IEC 61850 security guide cover these protocols, and the memory corruption fix guide covers uninitialized pointer bugs. Related stack flaws: CVE-2020-6996 in the Triangle MicroWorks DNP3 outstation library, CVE-2022-2277 in the Hitachi Energy SYS600 ICCP stack, and CVE-2015-6574 in SISCO MMS-EASE.

Is CVE-2022-38138 exploited?

It is not in the CISA KEV catalog as of 2026-11-20 (catalog version 2026.11.18, 1,786 entries). FIRST EPSS gives it 0.01003, the 63.6th percentile, in the 2026-11-19 dataset (CISA KEV, FIRST EPSS).

How to fix this class of issueThis advisory's weakness class is Memory corruption. Our practical guide covers how to detect, fix, verify and disclose it: How to fix memory corruption in embedded firmware.

Evidence

  • NVD (read 2026-11-20): status Modified; published 2022-10-11; NVD Primary CVSS v3.1 7.5 CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H; CISA ICS Secondary 7.5; CWE-824; CPE trianglemicroworks iec_60870-6_software_library and iec_61850_software_library without version; reference ICSA-22-249-01. — NVD
  • CISA ICSA-22-249-01 CSAF (2022-09-06), read 2026-11-20: TMW IEC 61850 library C 11.2.0 and earlier and C++/C#/Java 5.0.1 and earlier, TMW IEC 60870-6 (ICCP/TASE.2) C++ library 4.4.3 and earlier; CWE-824, CVSS v3.0 7.5; remediation: contact Triangle MicroWorks Support for mitigation guidance; sectors Energy, Water and Wastewater; no known public exploits; credits Vera Mens of Claroty Research. — CISA CSAF ICSA-22-249-01
  • CVE record (checked 2026-11-20): state PUBLISHED, CNA icscert, published 2022-10-11; affected versions as in ICSA-22-249-01; CNA CVSS v3.1 7.5, CWE-824; CISA ADP SSVC (2025-04-16) exploitation none, automatable yes, technical impact partial. — CVE.org
  • Not in the CISA KEV catalog, version 2026.11.18 (1,786 entries), checked 2026-11-20. — CISA KEV
  • EPSS 0.01003, percentile 0.63613, dataset 2026-11-19, read 2026-11-20. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. CISA CSAF: ICSA-22-249-01 Triangle MicroWorks Libraries (machine-readable advisory)
  3. CVE.org record CVE-2022-38138 (CNA: CISA ICS)
  4. CISA KEV
  5. FIRST EPSS

Frequently asked questions

Which Triangle MicroWorks library versions are affected by CVE-2022-38138?

The IEC 61850 C library 11.2.0 and earlier, the IEC 61850 C++, C# and Java libraries 5.0.1 and earlier, and the IEC 60870-6 (ICCP/TASE.2) C++ library 4.4.3 and earlier (per CISA ICSA-22-249-01). NVD's CPEs have no version limit.

Is there a fixed version?

CISA's advisory does not name one. It says Triangle MicroWorks encourages users of the affected library to contact Triangle MicroWorks Support for mitigation guidance. Device owners should ask their product vendor for a firmware or software release built on a newer library.

Can CVE-2022-38138 be exploited without credentials?

Yes. NVD and CISA both score it CVSS 7.5 with network access, no privileges and no user interaction. The impact is availability only: the attacker can crash a client or server built on the library.

Which products contain these libraries?

CISA names none; it says any client or server using the affected libraries is at risk. The flaw travels with the library into other vendors' products, so ask the maker of each IEC 61850 or ICCP device or application whether it uses them and at which version.