Security Advisory

CVE-2022-3192: ABB AC500 V2 Port 1200 Denial of Service

Last updated:
  • CVE-2022-3192

CVE-2022-3192 is a denial of service in ABB AC500 V2 PLCs: a crafted request that the firmware's error handling does not process correctly stops the engineering service on TCP port 1200. No login is needed. NVD and ABB both score it 5.3. ABB fixes it in AC500 V2 firmware 2.8.6, which ships with Automation Builder 2.6.0.

Vulnerability summary

CVSS base score

5.3

Medium severity

EPSS score (FIRST)

0.6%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2022-3192 · Source: NVD

Affected components

ComponentCPEVersion range
ABB AC500 V2 PLCs (all PLC types)cpe:2.3:o:abb:ac500_cpu_firmware:*:*:*:*:*:*:*:*2.0.0 up to but excluding 2.8.6; fixed in 2.8.6 (ABB 3ADR011162, NVD CPE)

What does this mean for affected devices?

NVD carries ABB's description: "Improper Input Validation vulnerability in ABB AC500 V2 PM5xx allows Client-Server Protocol Manipulation. This issue affects AC500 V2: from 2.0.0 before 2.8.6." NVD's Primary score and ABB's score are both CVSS v3.1 5.3 (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:L), and both name CWE-754, improper check for unusual or exceptional conditions. The record was published on 2023-03-31 (NVD, CVE record).

What does the crafted request do?

ABB's advisory 3ADR011162 (revision A, 2023-03-28) says: "An invalid crafted request is not properly processed by the error handling of the affected products, resulting in a denial-of-service condition on port 1200." The vector needs no login and rates the availability impact as low: the port 1200 service stops, not the whole controller. The same advisory covers eleven other CVEs, most of them from CODESYS Control V2, and ten of those need a successful login. CVE-2022-3192 does not. ABB says it had not been publicly disclosed and that no exploitation had been reported when the advisory was issued. Parul Sindhwad and Dr. Faruk Kazi of the CoE CNDS lab at VJTI, Mumbai, reported it.

Which AC500 firmware is affected and fixed?

ABB: "All AC500 V2 products with firmware version smaller than 2.8.6 are affected." NVD's CPE covers AC500 CPU firmware from 2.0.0 up to, but not including, 2.8.6. Firmware 2.8.6 is released for all AC500 V2 PLC types; it ships with Automation Builder 2.6.0, and ABB also offers a memory card image for download. AC500 V3 is not part of this advisory.

What if the update cannot be applied?

ABB states there is no workaround as such, but the flaw only affects the "ABB Tcp/Ip Level 2 AC" engineering protocol on port 1200. Switching the connection to the "Tcp/Ip" protocol moves it to port 1201, where a denial of service on port 1200 has no effect. ABB's general advice also applies: keep automation networks behind firewalls, away from office networks and the internet, and connect programming PCs only to the network they are meant for.

Firmware 2.8.6 does not fix every CVE in the advisory: the unprotected CODESYS V2 password transport CVE-2022-31805 stays open and needs network separation. Other CODESYS V2 runtime flaws, such as the stack overflow CVE-2021-30188 documented on WAGO controllers, show why the port matters. See the ABB AC500, RTU500 and Relion guide and the input handling fix guide.

CVE-2022-3192 is not in the CISA KEV catalog as of 2026-11-23 (catalog version 2026.11.20, 1,790 entries). FIRST EPSS gives it 0.00557, the 47.3rd percentile, in the 2026-11-22 dataset (CISA KEV, FIRST EPSS).

How to fix this class of issueNo dedicated SoftWSP guide covers this weakness class; the fix is usually the vendor patch or firmware update referenced above. Our related guide explains how to plan and verify it: NIST SP 800-40 Rev. 4: enterprise patch management planning, explained.

Evidence

  • NVD (read 2026-11-23): status Modified; published 2023-03-31; NVD Primary CVSS v3.1 5.3 AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:L, ABB Secondary 5.3; CWE-754 (NVD and ABB); CPE abb:ac500_cpu_firmware from 2.0.0 before 2.8.6. — NVD
  • ABB 3ADR011162 rev A 2023-03-28 (PDF read 2026-11-23): all AC500 V2 firmware < 2.8.6 affected; crafted request causes DoS on port 1200; fixed in 2.8.6 (all AC500 V2 PLC types, from Automation Builder 2.6.0, memory card image); no workaround except replacing 'ABB Tcp/Ip Level 2 AC' (port 1200) by 'Tcp/Ip' (port 1201); not publicly disclosed, no exploitation reported; credit Parul Sindhwad, Dr. Faruk Kazi (CoE CNDS lab, VJTI). — ABB 3ADR011162
  • CVE record (checked 2026-11-23): state PUBLISHED, CNA ABB, published 2023-03-31, AC500 V2 2.0.0 to before 2.8.6, CNA CVSS v3.1 5.3. — CVE.org
  • Not in the CISA KEV catalog, catalog version 2026.11.20, 1,790 entries, checked 2026-11-23. — CISA KEV
  • EPSS 0.00557, percentile 0.47319, dataset 2026-11-22, read 2026-11-23. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. ABB 3ADR011162: AC500 V2 Cyber Security Advisory
  3. CVE.org record CVE-2022-3192
  4. CISA KEV
  5. FIRST EPSS

Frequently asked questions

Which AC500 firmware fixes CVE-2022-3192?

AC500 V2 firmware 2.8.6, released for all AC500 V2 PLC types. It is available from Automation Builder 2.6.0 and as a memory card image from ABB (advisory 3ADR011162).

Does an attacker need the PLC password?

No. The CVSS vector has no privileges required. ABB's advice that a level 1 PLC password blocks exploitation applies to ten other CVEs in the same advisory, not to CVE-2022-3192.

Is there a workaround without updating?

ABB says there is none for the flaw itself, but only the 'ABB Tcp/Ip Level 2 AC' protocol on port 1200 is affected. Using the 'Tcp/Ip' protocol on port 1201 instead keeps engineering access working during a port 1200 denial of service.

Is CVE-2022-3192 in the CISA KEV catalog?

No, not as of 2026-11-23 (catalog version 2026.11.20, 1,790 entries). FIRST EPSS rates it 0.00557 (47.3rd percentile) in the 2026-11-22 dataset.