CVE-2021-32960 is an access control flaw in Rockwell Automation FactoryTalk Services Platform v6.11 and earlier with FactoryTalk Security enabled. A remote user who already has an account can bypass FactoryTalk Security policies that are based on the computer name and act with the privileges of the client machine. NVD scores it 8.8, CISA 8.5. Rockwell fixed it in FTSP v6.20.
Vulnerability summary
CVSS base score
8.8
High severity
EPSS score (FIRST)
2.4%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2021-32960 · Source: NVD

Affected components
| Component | CPE | Version range |
|---|---|---|
| Rockwell Automation FactoryTalk Services Platform (FTSP) with FactoryTalk Security enabled | cpe:2.3:a:rockwellautomation:factorytalk_services_platform:*:*:*:*:*:*:*:* | v6.11 and earlier when FactoryTalk Security is enabled and deployed (CISA ICSA-21-161-01; NVD: up to and including 6.11.00); fixed in v6.20 and later |
What does this mean for affected devices?
The CVE record reads: "Rockwell Automation FactoryTalk Services Platform v6.11 and earlier, if FactoryTalk Security is enabled and deployed contains a vulnerability that may allow a remote, authenticated attacker to bypass FactoryTalk Security policies based on the computer name. If successfully exploited, this may allow an attacker to have the same privileges as if they were logged on to the client machine." NVD's Primary score is 8.8 (CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H, CVSS 2.0 6.0) with CWE-863, incorrect authorization. CISA's record score is CVSS 3.1 8.5 (AV:N/AC:H/PR:L/UI:N/S:C/C:H/I:H/A:H) with CWE-693, protection mechanism failure: CISA rates the attack complexity high and the scope changed. NVD's configuration covers FTSP up to and including 6.11.00; the structured range in the CVE record reads "less than 6.11", but its own text, CISA and NVD all include 6.11 (NVD, CVE record).
Which FactoryTalk installations are affected?
CISA's ICSA-21-161-01 (CSAF), released on 2021-06-10, lists FactoryTalk Services Platform v6.11 and earlier "if FactoryTalk Security is enabled and deployed", used worldwide in the Chemical, Commercial Facilities, Critical Manufacturing, Energy, Government Facilities and Water and Wastewater Systems sectors. Rockwell reported the flaw to CISA itself. The flaw undermines policies tied to computer names, so any separation a site built on those rules can be bypassed by a logged-in user. Two later FTSP flaws, the weak password hash CVE-2020-14516 and the token reuse flaw CVE-2024-21917, need newer releases still.
How do you fix CVE-2021-32960?
Rockwell's fix, as CISA and the CVE record give it, is to update to FactoryTalk Services Platform v6.20 or later. Owners who cannot update are pointed to these mitigations, to be combined with Rockwell's general security guidelines:
- avoid remote desktop connections where possible;
- monitor for unusual remote desktop connections with Microsoft Event Logger or a similar logging tool;
- follow least privilege, granting user and service accounts only the rights they need on shared resources such as databases;
- keep control system networks off the internet and behind firewalls.
Since CVE-2024-21917 is fixed only in v6.40, a site still on 6.11 should move straight to a current FTSP release rather than to 6.20.
The Rockwell FactoryTalk software guide pairs this CVE with CVE-2024-21917 in its upgrade table for FTSP 6.11. Its EPSS percentile of 85 is high for a flaw that needs an account; the KEV and EPSS prioritization guide explains how to weigh that signal.
Is CVE-2021-32960 exploited?
CVE-2021-32960 is not in the CISA KEV catalog as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS gives it 0.0243, a percentile of 85.0, in the 2026-11-27 dataset (CISA KEV, FIRST EPSS).


Evidence
- NVD (read 2026-11-28): status Modified; published 2022-04-01; [email protected] Primary CVSS 3.1 8.8 AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H and CVSS 2.0 6.0 AV:N/AC:M/Au:S/C:P/I:P/A:P; CWE-863 (NVD), CWE-693 (CISA); ICS-CERT Secondary 8.5 AV:N/AC:H/PR:L/UI:N/S:C/C:H/I:H/A:H; CPE factorytalk_services_platform up to and including 6.11.00. — NVD
- CISA ICSA-21-161-01 CSAF (read 2026-11-28): released 2021-06-10; FTSP v6.11 and earlier if FactoryTalk Security is enabled and deployed; CWE-693; CVSS 3.0 8.5; reported by Rockwell Automation; fix FTSP v6.20 or later; avoid remote desktop, least privilege. — CISA ICSA-21-161-01
- CVE record (read 2026-11-28): PUBLISHED, assigner icscert, published 2022-04-01; FTSP versions lessThan 6.11 (structured), text says v6.11 and earlier; CNA CVSS 3.1 8.5; solution v6.20 or later; workarounds: avoid remote desktop, log atypical remote desktop connections with Microsoft Event Logger. — CVE.org
- Not in the CISA KEV catalog, catalog version 2026.11.27, 1,808 entries, checked 2026-11-28. — CISA KEV
- EPSS 0.02433, percentile 0.85002, dataset 2026-11-27, read 2026-11-28. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
Which FactoryTalk Services Platform versions are affected by CVE-2021-32960?
v6.11 and earlier, but only when FactoryTalk Security is enabled and deployed, per CISA ICSA-21-161-01; NVD's configuration runs up to and including 6.11.00.
Does CVE-2021-32960 need an account?
Yes. CISA and NVD describe a remote, authenticated attacker (PR:L). The flaw lets that user escape FactoryTalk Security rules tied to the computer name and act with the client machine's privileges.
How do I fix CVE-2021-32960?
Update to FactoryTalk Services Platform v6.20 or later; a current release also covers CVE-2024-21917, fixed in v6.40. Until then, avoid remote desktop connections where possible and log the ones that happen.
Is CVE-2021-32960 in the CISA KEV catalog?
No, not as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS rates it 0.0243 (percentile 85.0) in the 2026-11-27 dataset.