Security Advisory

CVE-2020-9307: Hirschmann HiOS HSR Ring Port DoS

Last updated:
  • CVE-2020-9307

CVE-2020-9307 is a denial of service in Hirschmann HiOS on RSP, RSPE and OS2 switches: an attacker on one link of an HSR ring sends a forged packet that loops the other HSR port and breaks ring redundancy. NVD scores it 6.5. Hirschmann's HiOS issue list names releases 07.1.01 and 08.4.01 as fixed; NVD gives 08.3.00.

Vulnerability summary

CVSS base score

6.5

Medium severity

EPSS score (FIRST)

0.6%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2020-9307 · Source: NVD

Affected components

ComponentCPEVersion range
Hirschmann HiOS (RSP, RSPE, OS2)cpe:2.3:o:belden:hirschmann_hios:*:*:*:*:*:*:*:*07.0.04 to before 07.1.00 and 08.0.00 to before 08.3.00 (NVD); HiOS issue list 45543: since 07.0.04, fixed in 08.3.00, correction text 08.4.01 and 07.1.01
Hitachi ABB Power Grids AFS660-SR—7.0.07 (CISA ICSA-21-075-03; no NVD CPE)
Hitachi ABB Power Grids AFS665-SR—7.0.07 (CISA ICSA-21-075-03; no NVD CPE)

What does this mean for affected devices?

NVD's description: "Hirschmann OS2, RSP, and RSPE devices before HiOS 08.3.00 allow a denial of service. An unauthenticated, adjacent attacker can cause an infinite loop on one of the HSR ring ports of the device. This effectively breaks the redundancy of the HSR ring." If the attacker repeats it on a second device, the ring splits into two parts that cannot talk to each other. NVD's Primary score is CVSS v3.1 6.5 (CVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H), v2 6.1, with CWE-835 (loop with unreachable exit condition). The CNA, MITRE, published the record on 2021-02-11 without its own score. NVD's CPE covers Hirschmann HiOS 07.0.04 to before 07.1.00 and 08.0.00 to before 08.3.00 (NVD, CVE record).

What happens to the HSR ring?

High-availability Seamless Redundancy (HSR) sends every frame both ways round a ring, so one broken link costs nothing. Hirschmann's HiOS issue list (2026-06-25 edition) describes the flaw as issue 45543: "By forging a specific packet, an attacker that is placed on one of the two redundant links of an HSR network can cause a denial of service on the other link." The attacker needs a foothold on the ring itself, which is why the score uses an adjacent attack vector. The plant keeps running on one path, but the redundancy is gone, and a second attacked node cuts the ring.

Which HiOS versions are affected and what fixes it?

The issue list names the RSP, RSPE and OS2 variants, gives 07.0.04 as the first affected release and 08.3.00 in its "Fixed in" column, and its correction text reads "Fixed in release 08.4.01 and 07.1.01." NVD's CPE ends the 07 line before 07.1.00, while the issue list names 07.1.01 as the 07 line fix, so treat 07.1.00 as unconfirmed and update to 07.1.01 or 08.4.01 or later. The flaw sits in the HSR ring port handling, so it matters on switches that run HSR.

Which other switches carry it?

CISA advisory ICSA-21-075-03 (2021-03-16) lists Hitachi ABB Power Grids AFS660-SR and AFS665-SR version 7.0.07 as affected by CVE-2020-9307, with the same CVSS v3 6.5 score. It says a crafted HSR frame can cause a denial of service on one of the ports in an HSR ring, that the update removes the flaw by changing how the switch processes HSR frames, and that it is not exploitable remotely (CISA CSAF ICSA-21-075-03).

The Hirschmann and Belden switch vulnerability guide lists the HSR row with the other HiOS flaws. CVE-2016-2509 also needs an attacker on the local network, and CVE-2018-5469 is a Hirschmann Classic switch flaw from a CISA ICS advisory.

CVE-2020-9307 is not in the CISA KEV catalog as of 2026-11-23 (catalog version 2026.11.20, 1,790 entries). FIRST EPSS gives it 0.00593, the 49.3rd percentile, in the 2026-11-22 dataset (CISA KEV, FIRST EPSS).

How to fix this class of issueNo dedicated SoftWSP guide covers this weakness class; the fix is usually the vendor patch or firmware update referenced above. Our related guide explains how to plan and verify it: NIST SP 800-40 Rev. 4: enterprise patch management planning, explained.

Evidence

  • NVD (read 2026-11-23): status Modified; published 2021-02-11; NVD Primary CVSS v3.1 6.5 CVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H, v2 6.1 AV:A/AC:L/Au:N/C:N/I:N/A:C; CWE-835; CPE belden hirschmann_hios 07.0.04 to before 07.1.00 and 08.0.00 to before 08.3.00. — NVD
  • Hirschmann HiOS issue list 2026-06-25, read 2026-11-23: ID 45543 (old ID 332), since 07.0.04, Fixed in 08.3.00, variants RSP, RSPE, OS2; forged packet on one of two redundant HSR links causes denial of service on the other link (CVE-2020-9307); correction: Fixed in release 08.4.01 and 07.1.01. — Hirschmann (Belden)
  • CISA ICSA-21-075-03 CSAF (2021-03-16), read 2026-11-23: Hitachi ABB Power Grids AFS660-SR and AFS665-SR 7.0.07 affected; CWE-835; CVSS v3 6.5 AV:A/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H; crafted HSR frame causes DoS on one port of an HSR ring; update changes how the switch processes HSR frames; not exploitable remotely; sector Energy. — CISA ICS advisory (CSAF)
  • CVE record (checked 2026-11-23): state PUBLISHED, CNA MITRE, published 2021-02-11; no CNA CVSS metric. — CVE.org
  • Not in the CISA KEV catalog, catalog version 2026.11.20, 1,790 entries, checked 2026-11-23. — CISA KEV
  • EPSS 0.00593, percentile 0.49285, dataset 2026-11-22, read 2026-11-23. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. Hirschmann: List of issues HiOS (2026-06-25)
  3. CISA ICSA-21-075-03: Hitachi ABB Power Grids AFS Series, CSAF
  4. CVE.org record CVE-2020-9307
  5. CISA KEV
  6. FIRST EPSS

Frequently asked questions

Which HiOS release fixes CVE-2020-9307?

Hirschmann's HiOS issue list (issue 45543) says fixed in releases 08.4.01 and 07.1.01, with 08.3.00 in its Fixed in column; NVD treats 08.3.00 as the first fixed 08 release.

Can the attack come from the internet?

No. The attacker must sit on one of the two redundant links of the HSR ring, which is why NVD scores an adjacent attack vector, and CISA says the flaw is not exploitable remotely.

Are other vendors' switches affected?

Yes. CISA advisory ICSA-21-075-03 lists Hitachi ABB Power Grids AFS660-SR and AFS665-SR version 7.0.07, with the same 6.5 score.

Is CVE-2020-9307 in the CISA KEV catalog?

No, not as of 2026-11-23 (catalog version 2026.11.20, 1,790 entries). FIRST EPSS rates it 0.00593 (49.3rd percentile) in the 2026-11-22 dataset.