Security Advisory

CVE-2021-20594: MELSEC Safety CPU User Name Leak

Last updated:
  • CVE-2021-20594

CVE-2021-20594 is an information exposure (CWE-200) in Mitsubishi Electric MELSEC iQ-R Safety CPUs (firmware 26 and prior) and SIL2 Process CPUs (firmware 11 and prior): a remote attacker without credentials can brute-force the CPU's user names. A login still needs the password. NVD scores it 7.5 and Mitsubishi 5.9; fixed firmware ships only in new units.

Vulnerability summary

CVSS base score

7.5

High severity

EPSS score (FIRST)

2.4%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2021-20594 · Source: NVD

Affected components

ComponentCPEVersion range
MELSEC iQ-R R08/16/32/120SFCPU (Safety CPU)cpe:2.3:o:mitsubishielectric:r08sfcpu_firmware:*:*:*:*:*:*:*:*firmware 26 and prior per Mitsubishi (NVD CPE: all versions); fixed in production firmware 27; installed units cannot be updated
MELSEC iQ-R R08/16/32/120PSFCPU (SIL2 Process CPU)cpe:2.3:o:mitsubishielectric:r08psfcpu_firmware:*:*:*:*:*:*:*:*firmware 11 and prior per Mitsubishi (NVD CPE: all versions); fixed in production firmware 12; installed units cannot be updated

What does this mean for affected devices?

NVD's description: the flaw "allows a remote unauthenticated attacker to acquire legitimate user names registered in the module via brute-force attack on user names." NVD's Primary score is CVSS v3.1 7.5 (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N) with CWE-200 (Exposure of Sensitive Information to an Unauthorized Actor). Mitsubishi Electric and CISA give 5.9 (AV:N/AC:H/PR:N/UI:N/S:U/C:H/I:N/A:N), rating the attack complexity high. NVD's CPE configuration lists the eight SFCPU and PSFCPU firmware entries with no version bound. The record was published on 2021-08-06 (NVD).

Which CPUs are affected, and can they be fixed?

Mitsubishi Electric's advisory 2021-008 (released 5 August 2021, last updated 18 April 2024) gives these versions:

CPU Affected Fixed in production Field update
iQ-R Safety CPU R08/16/32/120SFCPU Firmware 26 and prior 27 Not available
iQ-R SIL2 Process CPU R08/16/32/120PSFCPU Firmware 11 and prior 12 Not available

Mitsubishi says: "We have released the fixed version as shown below, but updating the product to the fixed version is not available." Units already installed stay on their firmware, and the fixed firmware ships only in newer production. The advisory notes the limit of the attack: "it is only possible to log-in to the unit, providing that the attacker can aquire the password." Ivan Speziale of Nozomi Networks Labs reported it.

CISA's ICSA-21-250-01 (2021-09-07, revised 2024-04-18) groups it with credential sniffing in CVE-2021-20597 and the lockout abuse CVE-2021-20598 (CISA CSAF). A valid user name makes the password the only remaining secret, and on these CPUs CVE-2021-20599 allows login with credentials other than the password, sent in cleartext.

How do you mitigate it?

Mitsubishi recommends a firewall or VPN where Internet access is required, using the CPU within a LAN with untrusted networks and hosts blocked, and the IP filter function to restrict which addresses can reach it. On a safety controller, treat the user names as known and make the passwords long and unique. Our Mitsubishi MELSEC SLMP protocol security guide covers IP filters, remote passwords and the MELSOFT ports these CPUs share with the standard iQ-R.

CVE-2021-20594 is not in the CISA KEV catalog as of 2026-11-18 (catalog version 2026.11.17), which has no Mitsubishi Electric entry. FIRST EPSS gives it 0.0237, the 84th percentile, in the 2026-11-17 dataset (CISA KEV, FIRST EPSS).

How to fix this class of issueNo dedicated SoftWSP guide covers this weakness class; the fix is usually the vendor patch or firmware update referenced above. Our related guide explains how to plan and verify it: NIST SP 800-40 Rev. 4: enterprise patch management planning, explained.

Evidence

  • NVD: R08/16/32/120SFCPU firmware 26 and prior and R08/16/32/120PSFCPU firmware 11 and prior; remote unauthenticated attacker acquires user names via brute force; NVD Primary CVSS v3.1 7.5 AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N; CWE-200; 8 CPEs, no version bound; published 2021-08-06. — NVD
  • Mitsubishi Electric advisory 2021-008 (released 2021-08-05, updated 2024-04-18): CVSS v3.1 5.9 AV:N/AC:H; affected SFCPU 26 and prior, PSFCPU 11 and prior; fixed 27 and 12; updating to the fixed version is not available; login still requires the password; mitigations firewall/VPN, LAN, IP filter; reported by Ivan Speziale (Nozomi Networks Labs). — Mitsubishi Electric PSIRT
  • ICSA-21-250-01 (initial 2021-09-07, current 2024-04-18): CVE-2021-20594 CWE-200 5.9, CVE-2021-20597 CWE-522 7.4, CVE-2021-20598 CWE-645 3.7; fixed SFCPU 27, PSFCPU 12. — CISA CSAF ICSA-21-250-01
  • Not in the CISA KEV catalog, version 2026.11.17 (1,782 entries, no Mitsubishi Electric vendor entry), checked 2026-11-18. — CISA KEV
  • EPSS 0.0237, percentile 0.84115, dataset 2026-11-17. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. Mitsubishi Electric advisory 2021-008: information disclosure vulnerability in MELSEC iQ-R series CPU module
  3. CISA ICS Advisory ICSA-21-250-01: Mitsubishi Electric MELSEC iQ-R Series
  4. CISA CSAF: ICSA-21-250-01 (machine-readable advisory)
  5. JPCERT/CC JVNVU#98578731 (Japanese)
  6. CISA KEV
  7. FIRST EPSS

Frequently asked questions

Can an attacker log in to a MELSEC Safety CPU with CVE-2021-20594 alone?

No. It reveals registered user names; Mitsubishi Electric says logging in is only possible if the attacker also obtains the password. Combined with credential flaws such as CVE-2021-20597 or CVE-2021-20599 on the same CPUs, a known user name lowers the bar (per Mitsubishi advisory 2021-008 and CISA ICSA-21-250-01).

Can I update an installed R08SFCPU to fix CVE-2021-20594?

No. Firmware 27 (Safety CPU) and 12 (SIL2 Process CPU) contain the fix, but Mitsubishi states that updating the product to the fixed version is not available, so installed units rely on mitigations: firewalls, a VPN, a LAN with untrusted hosts blocked and the IP filter (per Mitsubishi advisory 2021-008).

Why do NVD and Mitsubishi score CVE-2021-20594 differently?

Both rate it as a network attack with high confidentiality impact and no integrity or availability impact. Mitsubishi and CISA rate the attack complexity high (5.9); NVD rates it low (7.5) (per NVD and Mitsubishi advisory 2021-008).

Is CVE-2021-20594 in the CISA KEV catalog?

No, not as of 2026-11-18 (catalog version 2026.11.17). FIRST EPSS gives it 0.0237, the 84th percentile, in the 2026-11-17 dataset (per CISA KEV and FIRST EPSS).