CVE-2020-12017 is a missing-authentication flaw in the web interface of GE Reason RT430, RT431 and RT434 GPS/GNSS precision clocks. Without logging in, an attacker can run commands, change the configuration password or reboot the clock. NVD scores it 9.8, CISA 9.6. Firmware 08A05 and later fix it.
Vulnerability summary
CVSS base score
9.8
Critical severity
EPSS score (FIRST)
2.3%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2020-12017 · Source: NVD

Affected components
| Component | CPE | Version range |
|---|---|---|
| GE Grid Solutions Reason RT430 | cpe:2.3:o:ge:rt430_firmware:*:*:*:*:*:*:*:* | All firmware before 08A05 (CVE record, NVD, CISA ICSA-20-154-05); update to 08A05 or later (GE Vernova lists 08A07 and 08A08 as of 2026-11-27) |
| GE Grid Solutions Reason RT431 | cpe:2.3:o:ge:rt431_firmware:*:*:*:*:*:*:*:* | All firmware before 08A05 (CVE record, NVD, CISA); update to 08A05 or later |
| GE Grid Solutions Reason RT434 | cpe:2.3:o:ge:rt434_firmware:*:*:*:*:*:*:*:* | All firmware before 08A05 (CVE record, NVD, CISA); update to 08A05 or later |
What does this mean for affected devices?
The CVE record from CISA says that GE Grid Solutions Reason RT Clocks RT430, RT431 and RT434, "all firmware versions prior to 08A05", have a web application flaw that "could allow multiple unauthenticated attacks": an attacker may "execute arbitrary commands and send a request to a specific URL that could cause the device to become unresponsive", may change the password of the 'configuration' user account and then modify the device configuration through the web interface, and may bypass the authentication required to configure the device and reboot it. NVD's Primary score is 9.8 (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H, CVSS 2.0 9.0), and NVD and CISA agree on CWE-306, missing authentication for a critical function. CISA's own score is 9.6 (CVSS:3.0/AV:A/AC:L/PR:N/UI:N/S:C/C:L/I:H/A:H): it rates the attack as adjacent-network rather than network (NVD, CVE record).
Which GE clocks are affected?
CISA advisory ICSA-20-154-05, released on 2020-06-02, lists the RT430, RT431 and RT434 at all firmware versions before 08A05, deployed worldwide in the Chemical, Critical Manufacturing, Energy, Food and Agriculture and Water and Wastewater sectors. CISA's risk summary is access to sensitive information, arbitrary code execution and an unresponsive device. Ehab Hussein of IOActive reported the flaw to GE.
How do you fix CVE-2020-12017?
GE recommends updating the clocks to firmware 08A05 or later. GE Vernova's RT430 software page lists RT43x firmware 08A08 (2025-12-12) and 08A07 (2022-08-31), plus end-of-manufacturing notices for firmware 05, 06 and 07, as of 2026-11-27. Until the update, GE's mitigations as CISA records them are:
- strong network and physical security so an attacker cannot reach the local network where the clocks are installed;
- block TCP ports 80 and 443 to the clock's web interface, using an access control list on the Ethernet port the clock is connected to, so other HTTP/HTTPS applications are not affected;
- keep control system devices off the internet and analyse security events for unexpected traffic.
GE notes that these steps do not ensure complete security and are meant only until the clock is upgraded. Other GE Grid Solutions devices on this site include the Reason DR60 recorder (CVE-2021-27440) and the UR relays (CVE-2021-27428). For device makers, the authentication bypass fix guide covers protecting every configuration endpoint, and the time synchronisation guide covers flaws in the time-synchronisation software of embedded devices.
Is CVE-2020-12017 exploited?
CVE-2020-12017 is not in the CISA KEV catalog as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS gives it 0.02331, the 84.27th percentile, in the 2026-11-26 dataset (CISA KEV, FIRST EPSS). CISA reported no known public exploits specifically targeting this vulnerability.


Evidence
- NVD (read 2026-11-27): status Modified; published 2020-06-02; [email protected] Primary CVSS 3.1 9.8 AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H, CVSS 2.0 9.0; CWE-306 (NVD and ICS-CERT); CPEs ge rt430_firmware, rt431_firmware, rt434_firmware before 08a05. — NVD
- CISA ICSA-20-154-05 (CSAF, 2020-06-02): RT430, RT431, RT434 < 08A05; CWE-306 CVSS 3.0 9.6 AV:A/AC:L/PR:N/UI:N/S:C/C:L/I:H/A:H; sectors Chemical, Critical Manufacturing, Energy, Food and Agriculture, Water and Wastewater; GE: update to 08A05 or greater; mitigations: network/physical security, block TCP 80/443 via ACL on the clock's Ethernet port, minimize exposure, analyse security events; mitigations not complete security; reported by Ehab Hussein (IOActive); no known public exploits. — CISA CSAF
- GE Vernova RT430 software page (read 2026-11-27): RT43x Firmware 08A08 (2025-12-12), RT430 Firmware FW 08A07 (2022-08-31), GER-4795 end-of-manufacturing notice firmware 05 and 06, GER-4820 firmware 07. — GE Vernova
- CVE record (CNA icscert, published 2020-06-02): GE Grid Solutions Reason RT Clocks RT430, RT431, RT434, all firmware prior to 08A05; no CNA CVSS. — CVE.org
- CISA KEV catalog version 2026.11.25, 1,805 entries: CVE-2020-12017 not listed; checked 2026-11-27. — CISA KEV
- EPSS 0.02331, percentile 0.84269, dataset 2026-11-26, read 2026-11-27. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
Which GE Reason clock firmware is affected by CVE-2020-12017?
All RT430, RT431 and RT434 firmware versions before 08A05, per the CVE record, NVD and CISA ICSA-20-154-05.
Which firmware fixes CVE-2020-12017?
GE recommends firmware 08A05 or later. GE Vernova's download page lists RT43x firmware 08A07 and 08A08 as of 2026-11-27.
What can I do if I cannot update the clock yet?
GE advises blocking TCP ports 80 and 443 to the clock's web interface with an access control list on its Ethernet port, keeping the clock's network physically and logically protected, and watching for unexpected traffic. GE says this does not ensure complete security.
Is CVE-2020-12017 in the CISA KEV catalog?
No, not as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS rates it 0.02331, the 84.27th percentile, in the 2026-11-26 dataset.