Security Advisory

CVE-2020-10628: ControlEdge Cleartext Passwords

Last updated:
  • CVE-2020-10628

**CVE-2020-10628** is a cleartext transmission flaw (CWE-319) in Honeywell ControlEdge PLC R130.2 to R151 and ControlEdge RTU R101 to R151, published by CISA on 23 June 2020: the controllers expose unencrypted passwords on the network, so anyone who can capture the traffic can read them. NVD scores it 7.5 and CISA 5.9.

Vulnerability summary

CVSS base score

7.5

High severity

EPSS score (FIRST)

0.7%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2020-10628 · Source: NVD

Affected components

ComponentCPEVersion range
Honeywell ControlEdge PLCcpe:2.3:o:honeywell:controledge_plc_firmware:r151:*:*:*:*:*:*:*R130.2, R140, R150 and R151 per CISA ICSA-20-175-02 and NVD CPE; mitigation is the secure communication setup in Honeywell notice SN2020-04-17-01 (customer login)
Honeywell ControlEdge RTUcpe:2.3:o:honeywell:controledge_rtu_firmware:r151:*:*:*:*:*:*:*R101, R110, R140, R150 and R151 per CISA ICSA-20-175-02 and NVD CPE; mitigation is the secure communication setup in Honeywell notice SN2020-04-17-01 (customer login)

What does this mean for affected devices?

NVD describes CVE-2020-10628 as: "ControlEdge PLC (R130.2, R140, R150, and R151) and RTU (R101, R110, R140, R150, and R151) exposes unencrypted passwords on the network" (NVD, CVE.org). NVD's Primary CVSS v3.1 score is 7.5 (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N) and its CWE is CWE-319, cleartext transmission of sensitive information. CISA, the CNA, uses the same CWE but scores 5.9 because it rates attack complexity high: the attacker first needs a position on the network path to see the traffic. NVD's CPE configuration lists ControlEdge PLC firmware R130.2, R140, R150 and R151 and ControlEdge RTU firmware R101, R110, R140, R150 and R151, each paired with the hardware platform.

CISA's advisory ICSA-20-175-02 of 23 June 2020, credited to Nikolay Sklyarenko, covers ControlEdge PLC R130.2, R140, R150 and R151 and ControlEdge RTU R101, R110, R140, R150 and R151, and lists two flaws: CVE-2020-10628 (unencrypted passwords on the network) and CVE-2020-10624 (session token on the network). CISA scores both 5.9 (AV:N/AC:H/PR:N/UI:N/S:U/C:H/I:N/A:N); NVD scores both 7.5 with low attack complexity. The CSAF record gives no new firmware version as the fix. It tells users to follow the step-by-step secure communication instructions in Honeywell document SN2020-04-17-01, which needs a Honeywell Process Solutions login, and to contact Honeywell support otherwise. CISA lists Chemical, Critical Manufacturing, Energy and Water and Wastewater as the sectors and reports no known public exploits. Honeywell's public product security table lists ICSA-20-175-02 as "ControlEdge Cleartext Transmission Vulnerabilites" with both CVEs, rated Medium.

CVE-2020-10628 is not in the CISA KEV catalog as of 2026-11-22 (catalog version 2026.11.20). FIRST EPSS gives it 0.00743, percentile 55.6, in the 2026-11-21 dataset (CISA KEV, FIRST EPSS).

Until the secure communication settings are in place, treat any network path between engineering stations and ControlEdge units as able to leak credentials: keep the units on a segmented control network, do not route their engineering traffic over shared or remote links without an encrypted tunnel, and change passwords that may already have crossed the network in clear text. Our Honeywell Experion and ControlEdge guide covers ControlEdge alongside the Experion advisories.

The session token flaw from the same advisory has its own page: CVE-2020-10624.

How to fix this class of issueNo dedicated SoftWSP guide covers this weakness class; the fix is usually the vendor patch or firmware update referenced above. Our related guide explains how to plan and verify it: NIST SP 800-40 Rev. 4: enterprise patch management planning, explained.

Evidence

  • ControlEdge PLC (R130.2, R140, R150, R151) and RTU (R101, R110, R140, R150, R151) expose unencrypted passwords on the network; NVD Primary CVSS v3.1 7.5 (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N); CWE-319; CPE lists those firmware releases. — NVD
  • ICSA-20-175-02 (23 June 2020) scores CVE-2020-10628 5.9 (AV:N/AC:H/PR:N/UI:N/S:U/C:H/I:N/A:N) and gives the secure communication instructions in Honeywell document SN2020-04-17-01 (login required) as the mitigation; no known public exploits. — CISA ICSA-20-175-02
  • Honeywell lists ICSA-20-175-02, ControlEdge Cleartext Transmission, for ControlEdge PLC R130.2, R140, R150, R151 and RTU R101, R110, R140, R150, R151 with CVE-2020-10628 and CVE-2020-10624, severity Medium, dated 2020-06-23. — Honeywell product security notices
  • Not in the CISA KEV catalog as of 2026-11-22 (catalog version 2026.11.20); EPSS 0.00743, percentile 55.6, 2026-11-21 dataset. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. CVE.org record
  3. CISA ICSA-20-175-02
  4. CISA CSAF ICSA-20-175-02
  5. Honeywell product security notices
  6. CISA KEV catalog
  7. FIRST EPSS

Frequently asked questions

Which ControlEdge releases are affected by CVE-2020-10628?

ControlEdge PLC R130.2, R140, R150 and R151, and ControlEdge RTU R101, R110, R140, R150 and R151, per CISA ICSA-20-175-02 and NVD's CPE list.

Why is the NVD score 7.5 when CISA says 5.9?

Both rate high confidentiality impact only. CISA sets attack complexity to high, since the attacker must be able to capture the traffic; NVD sets it to low. That one metric moves the score from 5.9 to 7.5.

How is CVE-2020-10628 fixed?

CISA gives no new firmware release. It points to Honeywell document SN2020-04-17-01, which has step-by-step instructions to set up secure communication on ControlEdge PLC and RTU; the document needs a Honeywell Process Solutions login.

Is CVE-2020-10628 known to be exploited?

It is not in the CISA KEV catalog as of 2026-11-22 (catalog version 2026.11.20), and CISA reported no known public exploits. FIRST EPSS gives 0.00743, percentile 55.6, in the 2026-11-21 dataset.