**CVE-2020-10624** is a cleartext transmission flaw (CWE-319) in Honeywell ControlEdge PLC R130.2 to R151 and ControlEdge RTU R101 to R151, published by CISA on 23 June 2020: the controllers expose a session token on the network, which someone capturing the traffic could reuse. NVD scores it 7.5 and CISA 5.9.
Vulnerability summary
CVSS base score
7.5
High severity
EPSS score (FIRST)
0.7%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2020-10624 · Source: NVD
Affected components
| Component | CPE | Version range |
|---|---|---|
| Honeywell ControlEdge PLC | cpe:2.3:o:honeywell:controledge_plc_firmware:r151:*:*:*:*:*:*:* | R130.2, R140, R150 and R151 per CISA ICSA-20-175-02 and NVD CPE; mitigation is the secure communication setup in Honeywell notice SN2020-04-17-01 (customer login) |
| Honeywell ControlEdge RTU | cpe:2.3:o:honeywell:controledge_rtu_firmware:r151:*:*:*:*:*:*:* | R101, R110, R140, R150 and R151 per CISA ICSA-20-175-02 and NVD CPE; mitigation is the secure communication setup in Honeywell notice SN2020-04-17-01 (customer login) |
What does this mean for affected devices?
NVD describes CVE-2020-10624 as: "ControlEdge PLC (R130.2, R140, R150, and R151) and RTU (R101, R110, R140, R150, and R151) exposes a session token on the network" (NVD, CVE.org). NVD's Primary CVSS v3.1 score is 7.5 (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N) and its CWE is CWE-319. CISA, the CNA, uses the same CWE and scores 5.9 with high attack complexity. NVD's CPE configuration lists the same ControlEdge PLC and RTU firmware releases as for CVE-2020-10628. A captured session token matters because it can stand in for the password: the advisory pairs it with the cleartext password flaw, and both are closed by the same secure communication setup.
CISA's advisory ICSA-20-175-02 of 23 June 2020, credited to Nikolay Sklyarenko, covers ControlEdge PLC R130.2, R140, R150 and R151 and ControlEdge RTU R101, R110, R140, R150 and R151, and lists two flaws: CVE-2020-10628 (unencrypted passwords on the network) and CVE-2020-10624 (session token on the network). CISA scores both 5.9 (AV:N/AC:H/PR:N/UI:N/S:U/C:H/I:N/A:N); NVD scores both 7.5 with low attack complexity. The CSAF record gives no new firmware version as the fix. It tells users to follow the step-by-step secure communication instructions in Honeywell document SN2020-04-17-01, which needs a Honeywell Process Solutions login, and to contact Honeywell support otherwise. CISA lists Chemical, Critical Manufacturing, Energy and Water and Wastewater as the sectors and reports no known public exploits. Honeywell's public product security table lists ICSA-20-175-02 as "ControlEdge Cleartext Transmission Vulnerabilites" with both CVEs, rated Medium.
CVE-2020-10624 is not in the CISA KEV catalog as of 2026-11-22 (catalog version 2026.11.20). FIRST EPSS gives it 0.00743, percentile 55.6, in the 2026-11-21 dataset (CISA KEV, FIRST EPSS).
Until the secure communication settings are in place, treat any network path between engineering stations and ControlEdge units as able to leak credentials: keep the units on a segmented control network, do not route their engineering traffic over shared or remote links without an encrypted tunnel, and change passwords that may already have crossed the network in clear text. Our Honeywell Experion and ControlEdge guide covers ControlEdge alongside the Experion advisories.
The cleartext password flaw from the same advisory has its own page: CVE-2020-10628.
Evidence
- ControlEdge PLC (R130.2, R140, R150, R151) and RTU (R101, R110, R140, R150, R151) expose a session token on the network; NVD Primary CVSS v3.1 7.5; CWE-319; CPE lists those firmware releases. — NVD
- ICSA-20-175-02 (23 June 2020) scores CVE-2020-10624 5.9 (AV:N/AC:H/PR:N/UI:N/S:U/C:H/I:N/A:N) and gives the secure communication instructions in Honeywell document SN2020-04-17-01 (login required) as the mitigation; no known public exploits. — CISA ICSA-20-175-02
- Honeywell lists ICSA-20-175-02, ControlEdge Cleartext Transmission, for ControlEdge PLC R130.2, R140, R150, R151 and RTU R101, R110, R140, R150, R151 with CVE-2020-10628 and CVE-2020-10624, severity Medium, dated 2020-06-23. — Honeywell product security notices
- Not in the CISA KEV catalog as of 2026-11-22 (catalog version 2026.11.20); EPSS 0.00743, percentile 55.6, 2026-11-21 dataset. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
What does CVE-2020-10624 expose?
Per NVD and CISA, affected ControlEdge PLC and RTU units expose a session token on the network. Anyone who can capture that traffic can read the token.
Which ControlEdge versions are affected by CVE-2020-10624?
ControlEdge PLC R130.2, R140, R150 and R151, and ControlEdge RTU R101, R110, R140, R150 and R151, per CISA ICSA-20-175-02 and NVD.
What is the remediation for CVE-2020-10624?
Follow the secure communication instructions in Honeywell document SN2020-04-17-01 (Honeywell Process Solutions login required), per CISA. The advisory names no new firmware release, so the fix is a configuration change.
Is CVE-2020-10624 on the CISA KEV list?
No, not as of 2026-11-22 (catalog version 2026.11.20). FIRST EPSS gives 0.00743, percentile 55.6, in the 2026-11-21 dataset.
Questions about this page?