CVE-2019-5080 is a missing-authentication flaw in the I/O-Check service (iocheckd, TCP port 6626) of WAGO controllers. One unauthenticated packet stops the device and restores its documented default credentials. NVD scores it 9.1. WAGO's 2025 advisory VDE-2025-080 lists every firmware version as affected and gives one measure: disable port 6626.
Vulnerability summary
CVSS base score
9.1
Critical severity
EPSS score (FIRST)
1.9%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2019-5080 · Source: NVD
Affected components
| Component | CPE | Version range |
|---|---|---|
| WAGO PFC200 G1 (750-820x) and G2 (750-821x) | cpe:2.3:o:wago:pfc_200_firmware:03.01.07\(13\):*:*:*:*:*:*:* | All firmware versions; no fixed version, disable port 6626 (CERT@VDE VDE-2025-080). NVD lists firmware 03.00.39(12) and 03.01.07(13) |
| WAGO PFC100 G1 (750-810x) and G2 (750-811x) | cpe:2.3:o:wago:pfc_100_firmware:03.00.39\(12\):*:*:*:*:*:*:* | All firmware versions; no fixed version, disable port 6626 (CERT@VDE VDE-2025-080). NVD lists firmware 03.00.39(12) |
| WAGO CC100 (751-9x01), Edge Controller (752-8303/8000-0002), Touch Panel 600 (762-4x0x, 762-5x0x, 762-6x0x), Basic Controller 100 (750-800x) | — | All firmware versions; no fixed version, disable port 6626 (CERT@VDE VDE-2025-080). No NVD CPE |
| WAGO controllers 750-823, 750-829, 750-842, 750-843, 750-862 and discontinued 750-831, 750-852, 750-860, 750-863, 750-870/871/872, 750-880/881; fieldbus couplers 750-331, 750-340/341/342, 750-352, 750-362/363, 750-370, 750-375, 750-377 | — | All firmware versions; no fixed version (CERT@VDE VDE-2025-080). No NVD CPE |
What does this mean for affected devices?
NVD carries the Cisco Talos description: "A single packet can cause a denial of service and weaken credentials resulting in the default documented credentials being applied to the device. An attacker can send an unauthenticated packet to trigger this vulnerability." NVD's Primary score is CVSS v3.1 9.1 (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:H) with CWE-306; the record was published on 2019-12-18 (NVD, CVE record).
What happens when the packet arrives?
TALOS-2019-0872 explains that the unauthenticated iocheckd message makes the controller restore its factory settings. "Part of the factory restore procedure is to restore the well-known and documented default passwords for linux users and lighthttpd users used for authentication with the web server provided by the device. The CODESYS runtime is also stopped as a result of this message which will stop the industrial application." So the attack both halts the process and leaves the web-based management open to anyone who knows the manual's default passwords. Talos scores it 10.0 (CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:C/C:N/I:H/A:H); CISA's ICSA-20-065-01 uses the same 10.0.
Is there a fixed firmware?
No. In March 2020 CISA's ICSA-20-065-01 listed CVE-2019-5080 with the other I/O-Check flaws and the advice to update to FW15 or above. WAGO's own 2019 advisory, VDE-2019-022, did not include CVE-2019-5080 in its FW15 fix list. On 2025-09-09 WAGO published VDE-2025-080 for this CVE alone. Its CSAF file marks every listed product as affected in all firmware versions and records no fix: CC100 (751-9x01), PFC100 G1 and G2, PFC200 G1 and G2, Basic Controller 100, six Touch Panel 600 lines, the Edge Controller, controllers such as 750-823, 750-862 and 750-881, and fieldbus couplers from 750-331 to 750-377. It scores the flaw 9.1, matching NVD.
How do you protect a WAGO controller?
WAGO's mitigation reads: "The I/O-Check service protocol is only needed during installation and commissioning, not during normal operations. It is highly recommended to disable the IP-port 6626 after commissioning." Talos also says the service can be disabled through the web-based management. Check every controller for an open 6626 after commissioning, block the port at the cell boundary, and change the default passwords so that a reset to defaults is visible as a change. The same port carries the FW15-fixed overflows CVE-2019-5074 and CVE-2019-5082. See the WAGO PFC controller guide and the authentication bypass fix guide.
CVE-2019-5080 is not in the CISA KEV catalog as of 2026-11-21 (catalog version 2026.11.20, 1,790 entries). FIRST EPSS gives it 0.01866, the 79.8th percentile, in the 2026-11-20 dataset (CISA KEV, FIRST EPSS).
Evidence
- NVD (read 2026-11-21): status Modified; published 2019-12-18; NVD Primary CVSS v3.1 9.1 CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:H, v2 6.4; CWE-306 (NVD); CPE pfc_200_firmware 03.00.39(12), 03.01.07(13), pfc_100_firmware 03.00.39(12); reference TALOS-2019-0872. — NVD
- TALOS-2019-0872 (read 2026-11-21): unauthenticated iocheckd packet restores factory settings, including documented default passwords for Linux and lighttpd users, and stops the CODESYS runtime; CVSS v3.0 10.0; CWE-306; mitigation: disable I/O-Check via web-based management; disclosed 2019-07-30, public 2019-12-16. — Cisco Talos
- CERT@VDE VDE-2025-080 (initial release 2025-09-09), HTML and CSAF read 2026-11-21: CVE-2019-5080 CVSS v3.1 9.1, CWE-306; all firmware versions of CC100, PFC100 G1/G2, PFC200 G1/G2, Basic Controller 100, TP600 lines, Edge Controller, listed 750 controllers and fieldbus couplers known affected; remediation category no fix; mitigation disable IP port 6626 after commissioning. — CERT@VDE VDE-2025-080
- CISA ICSA-20-065-01 CSAF (2020-03-05), read 2026-11-21: CVE-2019-5080 CVSS v3.0 10.0, CWE-306; WAGO recommends FW15 or above and disabling port 6626. CERT@VDE VDE-2019-022 (2019-12-16) lists CVE-2019-5073, 5074, 5075, 5078, 5079, 5081, 5082 but not 5080. — CISA CSAF ICSA-20-065-01
- CVE record (checked 2026-11-21): state PUBLISHED, CNA Talos, published 2019-12-18. — CVE.org
- Not in the CISA KEV catalog, catalog version 2026.11.20, 1,790 entries, checked 2026-11-21. — CISA KEV
- EPSS 0.01866, percentile 0.79817, dataset 2026-11-20, read 2026-11-21. — FIRST EPSS

Related advisories
Sources
- NVD
- CERT@VDE VDE-2025-080: WAGO multiple vulnerabilities in I/O-Check service
- CERT@VDE VDE-2025-080 CSAF (machine-readable advisory)
- Cisco Talos TALOS-2019-0872: WAGO PFC200 iocheckd service I/O-Check denial of service
- CISA CSAF: ICSA-20-065-01 WAGO I/O-CHECK (machine-readable advisory)
- CVE.org record CVE-2019-5080
- CISA KEV
- FIRST EPSS
Frequently asked questions
Does FW15 fix CVE-2019-5080?
WAGO does not say so. CISA ICSA-20-065-01 (2020) advised FW15 or above, but WAGO advisory VDE-2025-080 (2025-09-09) lists all firmware versions as affected and names no fixed version. Disable port 6626 instead.
What does the attack do to a running controller?
Talos says one unauthenticated packet restores factory settings, which brings back the documented default passwords for Linux and web server users, and stops the CODESYS runtime, which halts the industrial application (TALOS-2019-0872).
Which WAGO products are affected?
VDE-2025-080 lists CC100, PFC100 G1 and G2, PFC200 G1 and G2, Basic Controller 100, Touch Panel 600 lines, the Edge Controller, controllers such as 750-823, 750-829, 750-842, 750-862 and several discontinued 750-8xx models, and fieldbus couplers 750-331 to 750-377, all firmware versions.
Is CVE-2019-5080 in the CISA KEV catalog?
No, not as of 2026-11-21 (catalog version 2026.11.20, 1,790 entries). FIRST EPSS rates it 0.01866 (79.8th percentile) in the 2026-11-20 dataset.