CVE-2019-5073 is an information exposure in the I/O-Check commissioning service (iocheckd, TCP port 6626) of WAGO PFC100 and PFC200 controllers. Crafted unauthenticated packets make an external tool fail, and the service then copies uninitialized stack data into its reply. NVD scores it 5.3; WAGO fixes it in firmware FW15.
Vulnerability summary
CVSS base score
5.3
Medium severity
EPSS score (FIRST)
1.6%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2019-5073 · Source: NVD
Affected components
| Component | CPE | Version range |
|---|---|---|
| WAGO PFC200 (750-82xx/xxx-xxx), iocheckd I/O-Check service | cpe:2.3:o:wago:pfc_200_firmware:03.01.07\(13\):*:*:*:*:*:*:* | Firmware before FW15; fixed in FW15 (CERT@VDE VDE-2019-022). NVD lists firmware 03.01.07(13) and 03.00.39(12) |
| WAGO PFC100 (750-81xx/xxx-xxx), iocheckd I/O-Check service | cpe:2.3:o:wago:pfc_100_firmware:03.00.39\(12\):*:*:*:*:*:*:* | Firmware before FW15; fixed in FW15 (CERT@VDE VDE-2019-022). NVD lists firmware 03.00.39(12) |
What does this mean for affected devices?
NVD carries the Cisco Talos description: "A specially crafted set of packets can cause an external tool to fail, resulting in uninitialized stack data to be copied to the response packet buffer. An attacker can send unauthenticated packets to trigger this vulnerability." It names WAGO PFC200 firmware 03.01.07(13) and 03.00.39(12) and PFC100 firmware 03.00.39(12). NVD's Primary score is CVSS v3.1 5.3 (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:N) with CWE-200; Cisco Talos, the CNA, published the record on 2019-12-18 and NVD links it to Talos report TALOS-2019-0862 (NVD, CVE record).
Why does a 5.3 leak matter on a controller?
On its own the flaw only discloses memory: CISA's ICSA-20-065-01 says a crafted packet "could cause the server to send back packets containing data from the stack", scores it CVSS v3.0 5.3 and classes it CWE-201. Both scores rate the confidentiality impact as low and the integrity and availability impact as none. The concern is the service it sits in: the same unauthenticated I/O-Check service on port 6626 also has memory corruption flaws, the stack overflows CVE-2019-5074 and CVE-2019-5075 and the heap overflows CVE-2019-5079 and CVE-2019-5081, all rated 9.8 by NVD. Other WAGO disclosure flaws from the same period sit in the web-based management, such as CVE-2019-5134 and CVE-2019-5135.
Which firmware fixes it?
WAGO's coordinated advisory VDE-2019-022 names Series PFC100 (750-81xx/xxx-xxx) and Series PFC200 (750-82xx/xxx-xxx) and lists CVE-2019-5073 among the flaws that "can be fixed alternatively by a firmware update >= FW 15". Its first measure is not the update: "The I/O-Check service protocol is only needed during installation and commissioning, not during normal operations. It is highly recommended to disable the IP-port 6626 after commissioning." CISA's ICSA-20-065-01 repeats the FW15 advice. NVD's CPE lists only PFC200 firmware 03.01.07(13) and 03.00.39(12) and PFC100 firmware 03.00.39(12), the builds named in the description, so a scanner keyed on NVD alone misses other firmware below FW15.
What should operators do?
Update to FW15 or later and disable I/O-Check after commissioning; WAGO calls this "the easiest and securest way to protect your device". Restrict network access to the controller and keep it off the internet. A WBM administrator account that falls to an attacker leads further, as CVE-2020-6090 shows, so keep the management interfaces off shared networks too. The WAGO PFC controller guide lists the other WAGO services to close.
CVE-2019-5073 is not in the CISA KEV catalog as of 2026-11-22 (catalog version 2026.11.20, 1,790 entries). FIRST EPSS gives it 0.01621, the 76.7th percentile, in the 2026-11-21 dataset (CISA KEV, FIRST EPSS).
Evidence
- NVD (read 2026-11-22): status Modified; published 2019-12-18; NVD Primary CVSS v3.1 5.3 CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:N, v2 5.0; CWE-200 (NVD); CPE pfc_200_firmware 03.01.07(13) and 03.00.39(12), pfc_100_firmware 03.00.39(12); reference TALOS-2019-0862. — NVD
- CERT@VDE VDE-2019-022 (initial release 2019-12-16), HTML and CSAF read 2026-11-22: affects Series PFC100 (750-81xx/xxx-xxx) and PFC200 (750-82xx/xxx-xxx); CVE-2019-5073 CVSS v3.1 5.3, CWE-200; disable IP port 6626 after commissioning; restrict network access, no direct internet connection, disable unused ports; CVE-2019-5073, 5074, 5075, 5079, 5081, 5082 can alternatively be fixed by firmware >= FW15; reported by Kelly Leuschner of Cisco Talos. — CERT@VDE VDE-2019-022
- CISA ICSA-20-065-01 CSAF (2020-03-05), read 2026-11-22: CVE-2019-5073 CVSS v3.0 5.3 (AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:N), CWE-201, a specially crafted packet could cause the server to send back packets containing data from the stack; WAGO recommends FW 15 or above, disabling IP port 6626 after commissioning, disabling unused ports and restricting network access; exploitability note: no known public exploits specifically target these vulnerabilities. — CISA CSAF ICSA-20-065-01
- CVE record (checked 2026-11-22): state PUBLISHED, CNA Cisco Talos (talos), published 2019-12-18; problem type "information exposure"; affected WAGO PFC200 firmware 03.01.07(13) and 03.00.39(12), PFC100 firmware 03.00.39(12); no CNA CVSS score in the record. — CVE.org
- Not in the CISA KEV catalog, catalog version 2026.11.20, 1,790 entries, checked 2026-11-22. — CISA KEV
- EPSS 0.01621, percentile 0.76696, dataset 2026-11-21, read 2026-11-22. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
Which WAGO firmware fixes CVE-2019-5073?
FW15 or later. CERT@VDE VDE-2019-022 lists CVE-2019-5073 among the flaws fixed by a firmware update >= FW 15, and CISA ICSA-20-065-01 recommends FW 15 or above.
What data leaks?
Uninitialized stack data. When a crafted set of packets makes an external tool fail, iocheckd copies stack memory into the response packet buffer, per the NVD description. CISA says the server sends back packets containing data from the stack.
Does an attacker need a login?
No. The packets are unauthenticated; the attacker only needs network access to TCP port 6626 on a PFC100 or PFC200 controller with firmware before FW15.
How do I check exposure without updating first?
Check whether TCP port 6626 answers from networks other than the commissioning laptop. WAGO says the I/O-Check protocol is only needed during installation and commissioning and recommends disabling the port afterwards.
Is CVE-2019-5073 in the CISA KEV catalog?
No, not as of 2026-11-22 (catalog version 2026.11.20, 1,790 entries). FIRST EPSS rates it 0.01621 (76.7th percentile) in the 2026-11-21 dataset.
Questions about this page?