CVE-2019-5075 is a stack buffer overflow in getcouplerdetails, a command line utility that the I/O-Check commissioning service (iocheckd, TCP port 6626) starts on WAGO PFC100 and PFC200 controllers. Unauthenticated packets to the service overflow the utility's stack and give code execution. NVD scores it 9.8; WAGO fixes it in firmware FW15.
Vulnerability summary
CVSS base score
9.8
Critical severity
EPSS score (FIRST)
3.9%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2019-5075 · Source: NVD
Affected components
| Component | CPE | Version range |
|---|---|---|
| WAGO PFC200 (750-82xx/xxx-xxx), iocheckd I/O-Check service and getcouplerdetails utility | cpe:2.3:o:wago:pfc_200_firmware:03.01.07\(13\):*:*:*:*:*:*:* | Firmware before FW15; fixed in FW15 (CERT@VDE VDE-2019-022). NVD lists firmware 03.01.07(13) and 03.00.39(12) |
| WAGO PFC100 (750-81xx/xxx-xxx), iocheckd I/O-Check service and getcouplerdetails utility | cpe:2.3:o:wago:pfc_100_firmware:03.00.39\(12\):*:*:*:*:*:*:* | Firmware before FW15; fixed in FW15 (CERT@VDE VDE-2019-022). NVD lists firmware 03.00.39(12) |
What does this mean for affected devices?
NVD carries the Cisco Talos description: "A specially crafted set of packets sent to the iocheckd service "I/O-Check" can cause a stack buffer overflow in the sub-process getcouplerdetails, resulting in code execution. An attacker can send unauthenticated packets to trigger this vulnerability." It names WAGO PFC200 firmware 03.01.07(13) and 03.00.39(12) and PFC100 firmware 03.00.39(12). NVD's Primary score is CVSS v3.1 9.8 (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H) with CWE-787; Cisco Talos, the CNA, published the record on 2019-12-18 and NVD links it to Talos report TALOS-2019-0864 (NVD, CVE record).
Why does a helper utility matter here?
The overflow is not in iocheckd itself. The service hands attacker-supplied data to a separate process, getcouplerdetails, and that process copies it into a fixed stack buffer. The result is the same as an overflow in the daemon: code runs on the controller without a login. CISA describes it as a buffer overflow "due to the lack of input validation, which may allow remote execution of arbitrary code", scores it CVSS v3.0 9.8 and classes it CWE-805. The same unauthenticated port carries the other 2019 I/O-Check overflows, CVE-2019-5074, CVE-2019-5079, CVE-2019-5081 and CVE-2019-5082.
Which firmware fixes it?
WAGO's coordinated advisory VDE-2019-022 names Series PFC100 (750-81xx/xxx-xxx) and Series PFC200 (750-82xx/xxx-xxx) and lists CVE-2019-5075 among the flaws that "can be fixed alternatively by a firmware update >= FW 15". Its first measure is not the update: "The I/O-Check service protocol is only needed during installation and commissioning, not during normal operations. It is highly recommended to disable the IP-port 6626 after commissioning." CISA's ICSA-20-065-01 repeats the FW15 advice. NVD's CPE lists only PFC200 firmware 03.01.07(13) and 03.00.39(12) and PFC100 firmware 03.00.39(12), the builds named in the description, so a scanner keyed on NVD alone misses other firmware below FW15.
What should operators do?
Update to FW15 or later, then switch I/O-Check off once commissioning is done and keep port 6626 reachable only from the commissioning laptop. Disabling the port matters beyond this CVE: WAGO's 2025 advisory for CVE-2019-5080 lists every firmware version as affected, and the command injection CVE-2020-12522 uses the same service. The WAGO PFC controller guide covers the full WAGO attack surface, and the memory corruption fix guide covers this class of bug.
CVE-2019-5075 is not in the CISA KEV catalog as of 2026-11-22 (catalog version 2026.11.20, 1,790 entries). FIRST EPSS gives it 0.03866, the 90.4th percentile, in the 2026-11-21 dataset (CISA KEV, FIRST EPSS).
Evidence
- NVD (read 2026-11-22): status Modified; published 2019-12-18; NVD Primary CVSS v3.1 9.8 CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H, v2 10.0; CWE-787 (NVD); CPE pfc_200_firmware 03.01.07(13) and 03.00.39(12), pfc_100_firmware 03.00.39(12); reference TALOS-2019-0864. — NVD
- CERT@VDE VDE-2019-022 (initial release 2019-12-16), HTML and CSAF read 2026-11-22: affects Series PFC100 (750-81xx/xxx-xxx) and PFC200 (750-82xx/xxx-xxx); CVE-2019-5075 CVSS v3.1 9.8, CWE-787; disable IP port 6626 after commissioning; restrict network access, no direct internet connection, disable unused ports; CVE-2019-5073, 5074, 5075, 5079, 5081, 5082 can alternatively be fixed by firmware >= FW15; reported by Kelly Leuschner of Cisco Talos. — CERT@VDE VDE-2019-022
- CISA ICSA-20-065-01 CSAF (2020-03-05), read 2026-11-22: CVE-2019-5075 CVSS v3.0 9.8 (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H), CWE-805, buffer overflow due to lack of input validation that may allow remote execution of arbitrary code; WAGO recommends FW 15 or above, disabling IP port 6626 after commissioning, disabling unused ports and restricting network access; exploitability note: no known public exploits specifically target these vulnerabilities. — CISA CSAF ICSA-20-065-01
- CVE record (checked 2026-11-22): state PUBLISHED, CNA Cisco Talos (talos), published 2019-12-18; problem type "stack buffer overflow"; affected WAGO PFC200 firmware 03.01.07(13) and 03.00.39(12), PFC100 firmware 03.00.39(12); no CNA CVSS score in the record. — CVE.org
- Not in the CISA KEV catalog, catalog version 2026.11.20, 1,790 entries, checked 2026-11-22. — CISA KEV
- EPSS 0.03866, percentile 0.90441, dataset 2026-11-21, read 2026-11-22. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
Which WAGO firmware fixes CVE-2019-5075?
FW15 or later. CERT@VDE VDE-2019-022 lists CVE-2019-5075 among the flaws fixed by a firmware update >= FW 15, and CISA ICSA-20-065-01 recommends FW 15 or above.
Does an attacker need a login?
No. NVD, CERT@VDE and CISA all describe unauthenticated packets sent to the I/O-Check service on port 6626, which pass data to the getcouplerdetails sub-process and overflow its stack.
Which controllers are affected?
WAGO Series PFC100 (750-81xx/xxx-xxx) and Series PFC200 (750-82xx/xxx-xxx) with firmware before FW15, per CERT@VDE VDE-2019-022.
What can operators do besides updating?
Disable the I/O-Check service (IP port 6626) after commissioning, restrict network access to the controller, keep it off the internet and disable unused TCP/UDP ports, as WAGO recommends in VDE-2019-022.
Is CVE-2019-5075 in the CISA KEV catalog?
No, not as of 2026-11-22 (catalog version 2026.11.20, 1,790 entries). FIRST EPSS rates it 0.03866 (90.4th percentile) in the 2026-11-21 dataset.
Questions about this page?