Security Advisory

CVE-2019-13537: Citect IEC870IP Driver Overflow

Last updated:
  • CVE-2019-13537

CVE-2019-13537 is a stack-based buffer overflow in the IEC870IP driver, which handles IEC 60870-5-104 traffic for AVEVA Vijeo Citect, Citect SCADA and Schneider Electric Power SCADA Operation. Driver v4.14.02 and earlier could crash the SCADA server. NVD scores it 7.5. Driver v4.15.00 fixes it without a SCADA upgrade.

Vulnerability summary

CVSS base score

7.5

High severity

EPSS score (FIRST)

1.3%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2019-13537 · Source: NVD

CVSS v3.1 severity rating scale: None 0.0, Low 0.1 to 3.9, Medium 4.0 to 6.9, High 7.0 to 8.9, Critical 9.0 to 10.0
How a CVSS v3.1 base score maps to a severity rating. Source: FIRST CVSS v3.1 specification, section 5.

Affected components

ComponentCPEVersion range
IEC870IP driver for AVEVA Vijeo Citect and Citect SCADAcpe:2.3:o:aveva:iec870ip_firmware:*:*:*:*:*:*:*:*v4.14.02 and earlier; fixed in v4.15.00
IEC870IP driver for Schneider Electric Power SCADA Operation 9.0 and Power SCADA Expert 7.3 to 8.2—Driver v4.14.02 and earlier with any cumulative update; fixed in driver v4.15.00

What does this mean for affected devices?

AVEVA's bulletin LFSEC00000139, dated 15 October 2019, says "the IEC870IP driver for Vijeo Citect and Citect SCADA has a buffer overflow that could cause a server-side crash." Schneider's notice SEVD-2019-344-04 of 10 December 2019 covers the same driver in Power SCADA Operation and explains that it "handles communication for connected products using the IEC 60870-5-104 protocol". CISA published both angles in ICSA-19-290-01, updated on 19 December 2019. AVEVA credits the VAPT Team of the C3i Center at IIT Kanpur.

How severe is CVE-2019-13537?

NVD's Primary score is CVSS v3.1 7.5, AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H, plus a Primary CVSS v2 score of 5.0 (NVD). AVEVA, Schneider and CISA give the same 7.5 under CVSS v3.0. The only difference is the weakness: CISA, AVEVA and Schneider say CWE-121, stack-based buffer overflow, while NVD files it as CWE-787, out-of-bounds write. The impact is availability: a crashed SCADA server stops polling its field devices.

Which versions are affected and what is the fix?

Any installation using IEC870IP driver v4.14.02 or earlier is affected. On the Schneider side that means Power SCADA Operation 9.0 and Power SCADA Expert 8.2, 8.1, 8.0, 7.4 and 7.3 with all cumulative updates. The fix is IEC870IP driver v4.15.00. Both vendors say the flaw is in the driver only, so the core Citect SCADA or Power SCADA Operation software does not need an upgrade. AVEVA and Schneider add that the IEC870IP protocol provides no authentication, so its use should be evaluated, and they point to NIST SP 800-82r2 for securing industrial control systems.

The Schneider EcoStruxure HMI and SCADA software guide explains how Citect moved from Schneider to AVEVA. Related Citect flaws are the exception-handler crash CVE-2013-2824 and AVEVA Plant SCADA's CVE-2023-1256. For the weakness class, see the memory corruption fix guide.

Is CVE-2019-13537 exploited?

It is not in the CISA KEV catalog as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS gives it 0.0130, the 70th percentile, in the 2026-11-27 dataset (CISA KEV, FIRST EPSS).

Three signals on every advisory: CVSS says how severe the flaw is, EPSS gives the probability of exploitation in the wild in the next 30 days, and a CISA KEV listing means the flaw has been exploited in the wild
CVSS rates severity, EPSS estimates the likelihood of exploitation, and CISA KEV records exploitation seen in the wild. Source: FIRST EPSS; CISA KEV catalog.
How to fix this class of issueThis advisory's weakness class is Memory corruption. Our practical guide covers how to detect, fix, verify and disclose it: How to fix memory corruption in embedded firmware.
From advisory to verified fix in four steps: read the advisory, find the affected component in the firmware SBOM, apply the fixed version or vendor mitigation, then re-scan the image to confirm the vulnerable version is gone
Read the advisory, find the component in your firmware SBOM, apply the fix, then re-scan to confirm it.

Evidence

  • NVD (read 2026-11-28): published 2020-01-14, status Modified; NVD Primary CVSS v3.1 7.5 AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H; NVD Primary CVSS v2 5.0 AV:N/AC:L/Au:N/C:N/I:N/A:P; CWE-787 (NVD Primary), CWE-121 (ICS-CERT Secondary); CPE aveva:iec870ip_firmware up to and including 4.14.02. — NVD
  • AVEVA Security Bulletin LFSEC00000139 (15 October 2019, PDF read 2026-11-28): IEC870IP driver v4.14.02 and earlier for Vijeo Citect and Citect SCADA; upgrade to v4.15.00; core software upgrade not necessary; CWE-121; CVSS v3.0 7.5 AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H; protocol provides no authentication; NIST SP800-82r2; credit VAPT Team, C3i Center, IIT Kanpur. — AVEVA
  • Schneider SEVD-2019-344-04 (10 December 2019, PDF read 2026-11-28): Power SCADA Operation 9.0 and Power SCADA Expert 8.2, 8.1, 8.0, 7.4, 7.3 (all cumulative updates); driver handles IEC 60870-5-104; fixed in v4.15.00; CWE-121, CVSS v3.0 7.5. — Schneider Electric
  • CISA ICSA-19-290-01 Update A CSAF (2019-10-17, updated 2019-12-19): IEC870IP driver v4.14.02 and prior; upgrade to v4.15.00 for Vijeo Citect/Citect SCADA and Power SCADA Operation; CWE-121, CVSS v3 7.5. — CISA
  • CVE.org record (read 2026-11-28): assigner ICS-CERT, CWE-121, affected AVEVA Vijeo Citect and Citect SCADA IEC870IP driver v4.14.02 and prior; no CNA CVSS metric. — CVE.org
  • Not in the CISA KEV catalog, catalog version 2026.11.27, 1,808 entries, checked 2026-11-28. — CISA KEV
  • EPSS 0.01297, percentile 0.70479, dataset 2026-11-27, read 2026-11-28. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. AVEVA Security Bulletin LFSEC00000139: IEC870IP driver for Vijeo Citect and Citect SCADA
  3. Schneider Electric SEVD-2019-344-04: Power SCADA Operation
  4. CISA ICSA-19-290-01: AVEVA Vijeo Citect and Citect SCADA (Update A, CSAF)
  5. CVE.org record (JSON)
  6. CISA KEV
  7. FIRST EPSS

Frequently asked questions

Do I need to upgrade Citect SCADA or Power SCADA Operation?

No. AVEVA and Schneider both say the flaw is only in the IEC870IP driver. Installing IEC870IP driver v4.15.00 fixes it without upgrading the core SCADA software.

Which Schneider products use the affected driver?

Schneider's SEVD-2019-344-04 lists Power SCADA Operation 9.0 and Power SCADA Expert 8.2, 8.1, 8.0, 7.4 and 7.3, including all cumulative updates, when they use IEC870IP driver v4.14.02 or earlier.

Why do the CWE labels differ?

CISA, AVEVA and Schneider classify it as CWE-121, a stack-based buffer overflow. NVD's own analysis files it under the broader CWE-787, out-of-bounds write. The score, 7.5, is the same everywhere.

Is CVE-2019-13537 in the CISA KEV catalog?

No, not as of 2026-11-28 (catalog version 2026.11.27, 1,808 entries). FIRST EPSS rates it 0.0130, the 70th percentile, in the 2026-11-27 dataset.