CVE-2019-10970 is an access control flaw in Rockwell Automation PanelView 5510 operator terminals built before 13 March 2019 that never received v4.003, v5.002 or later firmware: a remote, unauthenticated attacker who can reach the terminal may gain root access to its file system. NVD scores it 9.8, CISA 7.5. Update the firmware.
Vulnerability summary
CVSS base score
9.8
Critical severity
EPSS score (FIRST)
4.6%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2019-10970 · Source: NVD

Affected components
| Component | CPE | Version range |
|---|---|---|
| Rockwell Automation PanelView 5510 graphic terminal, firmware v4 | cpe:2.3:o:rockwellautomation:panelview_5510_firmware:*:*:*:*:*:*:*:* | Before 4.003 (NVD); units manufactured before 13 March 2019 and never updated (CISA ICSA-19-190-02); fixed in v4.003 or later |
| Rockwell Automation PanelView 5510 graphic terminal, firmware v5 | cpe:2.3:o:rockwellautomation:panelview_5510_firmware:*:*:*:*:*:*:*:* | 5.000 to before 5.002 (NVD); fixed in v5.002 or later (CISA) |
What does this mean for affected devices?
CVE-2019-10970 affects the Rockwell Automation PanelView 5510, a graphic HMI terminal. The CVE record, published by CISA on 2019-07-11, says that on PanelView 5510 units "manufactured before March 13, 2019 that have never been updated to v4.003, v5.002, or later", a remote, unauthenticated threat actor with access to the terminal "may boot-up the terminal and gain root-level access to the device's file system" (NVD, CVE record). NVD's Primary score is 9.8, CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H, with the generic weakness NVD-CWE-Other; CISA classifies it as CWE-284, improper access control. CISA's own score is 7.5, CVSS:3.0/AV:N/AC:H/PR:L/UI:N/S:U/C:H/I:H/A:H, which assumes high attack complexity and a low-privileged attacker.
Which PanelView terminals are affected?
CISA's ICSA-19-190-02, released on 2019-07-09, limits the issue to PanelView 5510 terminals with a manufacturing date before 13 March 2019 that have not been updated. NVD's configuration expresses this as firmware before 4.003, and 5.000 up to but not including 5.002. The sectors are Critical Manufacturing, Food and Agriculture, Transportation, and Water and Wastewater, deployed worldwide. Rockwell Automation reported the issue itself; CISA refers to Rockwell security advisory 1088080 in the Rockwell knowledge base for details.
How do you fix CVE-2019-10970?
Rockwell's guidance, as quoted by CISA, is to update: apply v4.003 or later to terminals running v4, and v5.002 or later to terminals running v5. Check both the firmware revision and the manufacturing date on the label; a terminal built after 13 March 2019 or already on a fixed revision is not affected. Rockwell also recommends blocking all traffic to EtherNet/IP and other CIP devices from outside the manufacturing zone by restricting ports 2222 and 44818 (TCP and UDP) at firewalls, and using only trusted software and patches. The Rockwell Logix controller guide covers the controllers these terminals talk to, and the EtherNet/IP and CIP guide explains the zone and port filtering. Related Rockwell pages include the Logix key bypass CVE-2021-22681 and the FactoryTalk Linx overflow CVE-2020-27251.
Is CVE-2019-10970 exploited?
CVE-2019-10970 is not in the CISA KEV catalog as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). CISA reported no known public exploits specifically targeting it at release. FIRST EPSS gives it 0.04597, the 92.42th percentile, in the 2026-11-26 dataset (CISA KEV, FIRST EPSS).


Evidence
- NVD (read 2026-11-27): status Modified, published 2019-07-11; [email protected] Primary CVSS 3.1 9.8 AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H, CVSS 2.0 10.0; NVD-CWE-Other (NVD), CWE-284 (ICS-CERT); CPE panelview_5510_firmware < 4.003 and 5.000 to < 5.002. — NVD
- CISA ICSA-19-190-02 (2019-07-09): PanelView 5510 manufactured before 13 March 2019, not updated to v4.003/v5.002; CWE-284; CVSS v3 7.5 AV:N/AC:H/PR:L/UI:N/S:U/C:H/I:H/A:H; fix v4.003 or later / v5.002 or later; block ports 2222 and 44818 TCP/UDP from outside the manufacturing zone; Rockwell advisory 1088080; reported by Rockwell Automation; no known public exploits. — CISA CSAF
- CVE record (CNA ICS-CERT): published 2019-07-11; CWE-284; affected PanelView 5510 'all versions manufactured before March 13, 2019 that have never been updated to v4.003, v5.002, or later'. — CVE.org
- CISA KEV catalog 2026.11.25 (1,805 entries): not listed, checked 2026-11-27. — CISA KEV
- EPSS 0.04597, percentile 0.92425, dataset 2026-11-26. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
Which PanelView terminals are affected by CVE-2019-10970?
PanelView 5510 graphic terminals manufactured before 13 March 2019 that were never updated to firmware v4.003, v5.002 or later (CISA ICSA-19-190-02). NVD lists firmware before 4.003 and 5.000 to before 5.002.
Which firmware fixes CVE-2019-10970?
v4.003 or later for terminals on the v4 line and v5.002 or later for terminals on the v5 line, per Rockwell's guidance in the CISA advisory.
Why does NVD score CVE-2019-10970 9.8 while CISA gives 7.5?
NVD scores low attack complexity with no privileges. CISA scores high attack complexity and a low-privileged attacker, which lowers the result to 7.5.
Is CVE-2019-10970 exploited in the wild?
It is not in the CISA KEV catalog as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS rates it 0.04597, the 92.42th percentile, in the 2026-11-26 dataset.
Questions about this page?