CVE-2018-5452 is a stack buffer overflow in Emerson ControlWave Micro process automation controllers running firmware CWM 05.78.00 and earlier. Crafted packets sent to port 20547 force the controller into halt mode, with no login needed. NVD and CISA both score it 7.5. Emerson fixes it in firmware 05.79.00.
Vulnerability summary
CVSS base score
7.5
High severity
EPSS score (FIRST)
2.2%
Probability of exploitation in the wild in the next 30 days
CISA KEV catalog
No
Not listed
Published
Vulnerability ID: CVE-2018-5452 · Source: NVD
Affected components
| Component | CPE | Version range |
|---|---|---|
| Emerson ControlWave Micro Process Automation Controller (ProConOS v4.01.280) | cpe:2.3:o:emerson:controlwave_micro_firmware:*:*:*:*:*:*:*:* | CWM firmware 05.78.00 and prior; fixed in 05.79.00 (CISA ICSA-18-058-03, NVD up to and including 05.78.00) |
What does this mean for affected devices?
NVD's description: "A stack-based buffer overflow vulnerability caused by sending crafted packets on Port 20547 could force the PLC to change its state into halt mode." It names ControlWave Micro with ProConOS v.4.01.280 and firmware CWM v.05.78.00 and prior. NVD's Primary score is CVSS v3.1 7.5 (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H) and CVSS v2 5.0, with CWE-787; ICS-CERT, the CNA, files it as CWE-121, a stack-based buffer overflow. NVD's CPE covers ControlWave Micro firmware up to and including 05.78.00. The record was published on 2018-03-07 (NVD, CVE record).
What does CISA's advisory add?
CISA's ICSA-18-058-03, "Emerson ControlWave Micro Process Automation Controller", released on 2018-02-27, gives the same 7.5 with CVSS v3.0 and calls it remotely exploitable with a low skill level. Both scores rate availability only: the controller stops, but no data is read or changed. CISA lists the energy and water and wastewater sectors, deployed worldwide, and said no known public exploits targeted it. Younes Dragoni of Nozomi Networks reported it (CSAF).
How do you fix it?
First find which ControlWave products have Ethernet connectivity. Then upgrade to firmware 05.79.00, following the ControlWave Micro instruction manual (part D301392X012). Emerson's release notes and firmware are on its remote automation support portal for registered users. Before the upgrade, run a full alarm and historical collection, including archive files and audit logs. CISA notes the fix is only effective once it is properly incorporated into the application running on the controller. Until then, CISA's general advice applies: keep the controller off the internet, behind firewalls and separate from business networks. For DeltaV flaws of the same year, see CVE-2018-14793 and CVE-2018-19021. See the Emerson DeltaV, Ovation and ROC guide and the memory corruption fix guide.
CVE-2018-5452 is not in the CISA KEV catalog as of 2026-11-23 (catalog version 2026.11.20, 1,790 entries). FIRST EPSS gives it 0.02154, the 82.6th percentile, in the 2026-11-22 dataset (CISA KEV, FIRST EPSS).
Evidence
- NVD (read 2026-11-23): status Modified; published 2018-03-07; NVD Primary CVSS v3.1 7.5 CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H and CVSS v2 5.0 AV:N/AC:L/Au:N/C:N/I:N/A:P; CWE-787 (NVD), CWE-121 (ICS-CERT); CPE emerson:controlwave_micro_firmware up to and including 05.78.00. — NVD
- CISA ICSA-18-058-03 (2018-02-27), CSAF read 2026-11-23: ControlWave Micro [ProConOS v.4.01.280] firmware <= 05.78.00; CVSS v3.0 7.5 AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H; CWE-121; crafted packets on port 20547 force halt mode; remotely exploitable, low skill; fix firmware 05.79.00 (manual D301392X012); assess Ethernet-connected ControlWave products; full alarm and historical collection before upgrade; fix effective only when incorporated into the application; sectors energy, water and wastewater; no known public exploits; reported by Younes Dragoni (Nozomi Networks). — CISA ICSA-18-058-03
- CVE record (checked 2026-11-23): state PUBLISHED, CNA icscert, published 2018-03-07, CWE-121, product Emerson ControlWave Micro Process Automation Controller; no CNA CVSS metric in the record. — CVE.org
- Not in the CISA KEV catalog, catalog version 2026.11.20, 1,790 entries, checked 2026-11-23. — CISA KEV
- EPSS 0.02154, percentile 0.82621, dataset 2026-11-22, read 2026-11-23. — FIRST EPSS

Related advisories
Sources
Frequently asked questions
Which ControlWave Micro firmware fixes CVE-2018-5452?
Firmware 05.79.00. CISA ICSA-18-058-03 lists CWM 05.78.00 and earlier, with ProConOS v4.01.280, as affected.
What happens to the controller when attacked?
Crafted packets to port 20547 overflow a stack buffer and force the PLC into halt mode. No login is needed, and NVD and CISA rate the impact as availability only.
What should I do before upgrading?
CISA's advisory says to run a full alarm and historical collection, including archive files and audit logs, and to follow the upgrade steps in the ControlWave Micro instruction manual, part D301392X012.
Is CVE-2018-5452 in the CISA KEV catalog?
No, not as of 2026-11-23 (catalog version 2026.11.20, 1,790 entries). FIRST EPSS rates it 0.02154 (82.6th percentile) in the 2026-11-22 dataset.