Security Advisory

CVE-2018-17924: Rockwell CIP Unauthenticated IP Change

Last updated:
  • CVE-2018-17924

CVE-2018-17924 lets an unauthenticated remote attacker send a CIP connection request to a Rockwell Automation MicroLogix 1400 controller or 1756 ControlLogix EtherNet/IP module and then push a new IP configuration, even with the controller in Hard RUN mode. The device then loses contact with the rest of the system. NVD and CISA score it 8.6; newer firmware plus a protected mode fixes the current hardware series.

Vulnerability summary

CVSS base score

8.6

High severity

EPSS score (FIRST)

5.8%

Probability of exploitation in the wild in the next 30 days

CISA KEV catalog

No

Not listed

Published

Vulnerability ID: CVE-2018-17924 · Source: NVD

CVSS v3.1 severity rating scale: None 0.0, Low 0.1 to 3.9, Medium 4.0 to 6.9, High 7.0 to 8.9, Critical 9.0 to 10.0
How a CVSS v3.1 base score maps to a severity rating. Source: FIRST CVSS v3.1 specification, section 5.

Affected components

ComponentCPEVersion range
Rockwell Automation MicroLogix 1400 controllers (1766-Lxxx)cpe:2.3:o:rockwellautomation:micrologix_1400_firmware:-:*:*:*:*:*:*:*Series A all versions; Series B and C v21.003 and earlier (CVE record); fix FRN 21.004 or later for Series B and C, then RUN mode from the LCD display
Rockwell Automation 1756-EN2F, 1756-EN2T, 1756-EN2TR, 1756-EN3TR ControlLogix EtherNet/IP modulescpe:2.3:o:rockwellautomation:1756-en2t_series_d_firmware:*:*:*:*:*:*:*:*EN2F Series C, EN2T Series D, EN2TR Series C, EN3TR Series B: v10.10 and earlier, fix FRN 11.001 or later with Explicit Protected Mode; earlier series of these modules: all versions, no direct fix (CVE record)
Rockwell Automation 1756-ENBT and 1756-EWEB ControlLogix modulescpe:2.3:o:rockwellautomation:1756-enbt_firmware:-:*:*:*:*:*:*:*1756-ENBT all versions; 1756-EWEB Series A and B all versions (CVE record); network mitigations only

What does this mean for affected devices?

The CVE record from CISA says an attacker "could send a CIP connection request to an affected device, and upon successful connection, send a new IP configuration to the affected device even if the controller in the system is set to Hard RUN mode. When the affected device accepts this new IP configuration, a loss of communication occurs between the device and the rest of the system as the system traffic is still attempting to communicate with the device via the overwritten IP address." NVD's Primary score is 8.6 (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:N/I:N/A:H, CVSS 2.0 7.8) with CWE-306, missing authentication for a critical function; CISA's advisory gives the same 8.6 vector under CVSS 3.0, and CISA's ADP enrichment adds 7.5 with an unchanged scope (NVD, CVE record).

Which Rockwell devices are affected?

CISA's ICSA-18-310-02, first released on 2018-11-06 and updated on 2018-12-06, and the CVE record list:

  • MicroLogix 1400 controllers: Series A all versions, Series B and C v21.003 and earlier;
  • 1756-ENBT all versions and 1756-EWEB Series A and B all versions;
  • 1756-EN2F Series A and B, 1756-EN2T Series A to C, 1756-EN2TR Series A and B and 1756-EN3TR Series A: all versions;
  • 1756-EN2F Series C, 1756-EN2T Series D, 1756-EN2TR Series C and 1756-EN3TR Series B: v10.10 and earlier.

CISA lists the critical manufacturing, food and agriculture, transportation, and water and wastewater sectors, deployment worldwide, and a United States headquarters. David Noren reported the flaw. NVD's CPE list uses 10.10 as the upper bound for the newest module series and no version for the others.

How do you fix CVE-2018-17924?

Rockwell's remedies, as listed by CISA:

  • MicroLogix 1400 Series B or C: apply FRN 21.004 or later, then use the LCD display to put the controller in RUN mode, which blocks configuration changes;
  • 1756-EN2F Series C, 1756-EN2T Series D, 1756-EN2TR Series C and 1756-EN3TR Series B: apply FRN 11.001 or later, then enable Explicit Protected Mode;
  • older module series, 1756-ENBT and 1756-EWEB: no direct fix; block EtherNet/IP traffic from outside the operational zone on port 2222 TCP and UDP and port 44818, and use a hardware key switch where the product has one.

The Rockwell Logix controller guide and the EtherNet/IP and CIP protocol guide cover these controls in context. Other flaws in the same products are CVE-2023-3595 (ControlLogix EN2/EN3 module code execution) and CVE-2021-22659 (MicroLogix 1400 Modbus denial of service).

Is CVE-2018-17924 exploited?

CVE-2018-17924 is not in the CISA KEV catalog as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS gives it 0.05845, the 93.95th percentile, in the 2026-11-26 dataset (CISA KEV, FIRST EPSS). CISA reported no known public exploits specifically targeting this vulnerability at publication.

Three signals on every advisory: CVSS says how severe the flaw is, EPSS gives the probability of exploitation in the wild in the next 30 days, and a CISA KEV listing means the flaw has been exploited in the wild
CVSS rates severity, EPSS estimates the likelihood of exploitation, and CISA KEV records exploitation seen in the wild. Source: FIRST EPSS; CISA KEV catalog.
How to fix this class of issueThis advisory's weakness class is Authentication bypass. Our practical guide covers how to detect, fix, verify and disclose it: How to fix authentication bypass in embedded firmware.
From advisory to verified fix in four steps: read the advisory, find the affected component in the firmware SBOM, apply the fixed version or vendor mitigation, then re-scan the image to confirm the vulnerable version is gone
Read the advisory, find the component in your firmware SBOM, apply the fix, then re-scan to confirm it.

Evidence

  • NVD (read 2026-11-27): status Modified; published 2018-12-07; [email protected] Primary CVSS 3.1 8.6 AV:N/AC:L/PR:N/UI:N/S:C/C:N/I:N/A:H, CVSS 2.0 7.8; CISA-ADP Secondary CVSS 3.1 7.5 (S:U); CWE-306; CPE micrologix_1400_firmware, 1756-enbt, 1756-eweb series a/b, 1756-en2f/en2t/en2tr/en3tr series firmware, with versions up to and including 10.10 for en2f series c, en2t series d, en2tr series c, en3tr series b. — NVD
  • CISA ICSA-18-310-02 (2018-11-06, updated 2018-12-06): MicroLogix 1400 and 1756 ControlLogix EtherNet/IP modules; CVE-2018-17924 CWE-306 CVSS 3.0 8.6 AV:N/AC:L/PR:N/UI:N/S:C/C:N/I:N/A:H; MicroLogix 1400 B/C FRN 21.004 then RUN mode via LCD; EN2F C, EN2T D, EN2TR C, EN3TR B FRN 11.001 then Explicit Protected Mode; older series no direct mitigation; block ports 2222 TCP/UDP and 44818; sectors Critical Manufacturing, Food and Agriculture, Transportation Systems, Water and Wastewater; reported by David Noren; no known public exploits. — CISA CSAF
  • CVE.org record (CNA icscert): published 2018-12-07; affected list MicroLogix 1400 Series A all, B and C v21.003 and earlier; 1756-ENBT all; 1756-EWEB A and B all; 1756-EN2F A, B all, C v10.10 and earlier; 1756-EN2T A-C all, D v10.10 and earlier; 1756-EN2TR A, B all, C v10.10 and earlier; 1756-EN3TR A all, B v10.10 and earlier; CWE-306; CISA-ADP CVSS 3.1 7.5. — CVE.org
  • CISA KEV catalog version 2026.11.25, 1,805 entries: CVE-2018-17924 not listed; checked 2026-11-27. — CISA KEV
  • EPSS 0.05845, percentile 0.93945, dataset 2026-11-26, read 2026-11-27. — FIRST EPSS

Related advisories

Sources

  1. NVD
  2. CISA ICSA-18-310-02: Rockwell Automation MicroLogix 1400 Controllers and 1756 ControlLogix Communications Modules (CSAF)
  3. CISA ICSA-18-310-02 advisory page
  4. CVE.org record CVE-2018-17924
  5. CISA KEV
  6. FIRST EPSS

Frequently asked questions

Which Rockwell products are affected by CVE-2018-17924?

MicroLogix 1400 controllers (Series A all versions, Series B and C v21.003 and earlier) and 1756 ControlLogix EtherNet/IP modules: ENBT, EWEB, EN2F, EN2T, EN2TR and EN3TR. The newest series of the last four are affected at v10.10 and earlier.

Which firmware fixes CVE-2018-17924?

FRN 21.004 or later for MicroLogix 1400 Series B and C, with the controller put in RUN mode from the LCD. FRN 11.001 or later for 1756-EN2F Series C, EN2T Series D, EN2TR Series C and EN3TR Series B, with Explicit Protected Mode enabled.

What if my module series has no fix for CVE-2018-17924?

Block EtherNet/IP traffic from outside the operational zone on ports 2222 TCP and UDP and 44818, keep control networks off the Internet and behind firewalls, and use a hardware key switch where available.

Is CVE-2018-17924 in the CISA KEV catalog?

No, not as of 2026-11-27 (catalog version 2026.11.25, 1,805 entries). FIRST EPSS rates it 0.05845, the 93.95th percentile, in the 2026-11-26 dataset.